2829596 | 91566 | None | code01 | LT Cable: Earth work excavation for pipelines/cables by Manual means upto 600 mm trench width, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter, including dressing of excavated surfaces, disposing off or leveling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m. Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering and lift upto 1.5 m including cost of labour, tools, usage& other appurtenances required to complete the work. | Cum | 532.4 | 532.4 | 1163.7 | False | None | None | False | None | False | 619553.88 | 0 |
2829597 | 91566 | None | code02 | Earth work excavation by manual means for drains, canals, waste weir, draft, approach channels, key trenches, foundation of Buildings & bridges and such simillar works in all kinds of soils, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter, excavated surface leveled and sides neatly dressed disposing off the excavated stuff or sorting & stacking the selected stuff for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools & other appurtenaces required to complete the work. | Cum | 266.2 | 266.2 | 24.6735 | False | None | None | False | None | False | 6568.0857 | 0 |
2829598 | 91566 | None | code03 | Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork shall be paid separately)Mix 1:4:8( M5) Using 40 mm nominal size graded crushed coarse aggregates | Cum | 6230.4 | 6230.4 | 1.8315 | False | None | None | False | None | False | 11410.9776 | 0 |
2829599 | 91566 | None | code04 | Providing and laying in position Reinforced cement concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork to be paid separately)M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates | Cum | 7607.26 | 7607.26 | 14.418 | False | None | None | False | None | False | 109681.47468 | 0 |
2829600 | 91566 | None | code05 | Supplying, fitting and placing TMT Fe 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification. h.All other type of structures | Tonne | 86912.1 | 86912.1 | 0.52 | False | None | None | False | None | False | 45194.292 | 0 |
2829601 | 91566 | None | code06 | Refilling available earth around trenches/pipelines, cables in layers not exceeding 20 cms in depth, compacting each deposited layer by ramming after watering with a lead upto 50 m, and lift upto 1.5 m. Including cost of all labour complete as per specifications | Cum | 176.0 | 176.0 | 1163.7 | False | None | None | False | None | False | 204811.2 | 0 |
2829602 | 91566 | None | code07 | 1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975-16 Sqmm, 4 Core, (11 GI Strips - 4 x 0.8 mm) | Km | 156026.2 | 156026.2 | 4.25 | False | None | None | False | None | False | 663111.35 | 0 |
2829603 | 91566 | None | code08 | 1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975-35 Sqmm, 3.5 Core, (14 GI Strips - 4 x 0.8 mm) | Km | 169468.2 | 169468.2 | 4.0 | False | None | None | False | None | False | 677872.8 | 0 |
2829604 | 91566 | None | code09 | 1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975-300 Sqmm, 3.5 Core, (32 GI Strips - 4 x 0.8 mm) | Km | 1172615.4 | 1172615.4 | 0.12 | False | None | None | False | None | False | 140713.848 | 0 |
2829605 | 91566 | None | code10 | Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff-2.5 to 25 Sqmm | Km | 22974.6 | 22974.6 | 4.25 | False | None | None | False | None | False | 97642.05 | 0 |
2829606 | 91566 | None | code11 | Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff-35 to 95 Sqmm | Km | 34252.9 | 34252.9 | 4.0 | False | None | None | False | None | False | 137011.6 | 0 |
2829607 | 91566 | None | code12 | Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff-300 to 400 Sqmm | Km | 37593.6 | 37593.6 | 0.12 | False | None | None | False | None | False | 4511.232 | 0 |
2829608 | 91566 | None | code13 | Epoxy Terminating Kit (Pothead) suitable for 1.1 kV, LTUG Cable-3.5 x 400/500 Sqmm | Nos | 787.6 | 787.6 | 52.0 | False | None | None | False | None | False | 40955.2 | 0 |
2829609 | 91566 | None | code14 | Supply & Installing 3.5C x 35sq mm LT XLPE Insulated Alluminium Armoured UG Cable end termination. | Nos | 855.0 | 855.0 | 280.0 | False | None | None | False | None | False | 239400.0 | 0 |
2829610 | 91566 | None | code15 | Supply and installation of 4C x 16sq mm UG Cable End terminations | Nos | 235.0 | 235.0 | 62.0 | False | None | None | False | None | False | 14570.0 | 0 |
2829611 | 91566 | None | code16 | Supply & Installing 3.5C x 240sq mm LT XLPE Insulated Alluminium Armoured UG Cable end termination. | Nos | 1850.0 | 1850.0 | 28.0 | False | None | None | False | None | False | 51800.0 | 0 |
2829612 | 91566 | None | code17 | Supply & Installing of 3.5C 300sq mm LT Cable End termination. | Nos | 2250.0 | 2250.0 | 24.0 | False | None | None | False | None | False | 54000.0 | 0 |
2829613 | 91566 | None | code18 | Supply and erection of 14 Feet Height Street Light Pole 14 Feet Height Street Light Pole on suitable cement concrete foundation with 2.5 Feet height dia 95 mm cast iron decorative round pedestal as per design weighing not less than 37Kgs, the pedestal shall be fitted with Class'C'G.I.Pipe 7 Feet height 75mm outer dia and 7 feet height top piece outer dia of 65mm fixed by measure of threading/welding/coupling complete. (excluding foundation).. | Nos | 22660.0 | 22660.0 | 30.0 | False | None | None | False | None | False | 679800.0 | 0 |
2829614 | 91566 | None | code19 | Fabrication,Supplying,Erection,Testing and Commissioning of......ms long Polygon high mast with Single/Multiple telescopic sections having ,(minimum over lap distance of 1.5 times of top section) thickness as per BSEN10025 grades 355JO/ASTMA572-50 steel sheet plate for shaft suitable to with stand a wind velocity of 47m/s as per IS875 part 3 (as per GA Drawing). Base plate as per IS2062/ASTMA572-50.The mast shall be Galvanized in single Hot dip as per BSENISO 1461/ ASTMA 123 with an average 70 microns as per IS2629, and welded as per BS5135 Single L Seam joint The mast shall have 2 Way head frame with die cast LM-6 pulleys,stain less steel axle, Phosphorus Bronze bearing bush press-fitted with separate guides for 2runs of 5mm dia,stainless steel wire rope of AISI304 grade7/19-core ,(Factor of Safety as per TRno-7). 2.5 mm2 EPR insulated PCP sheathed trailing power cable housed in side the bottom shaft of mast with door having locking arrangement The mast shall have manual /power tool (Suitable reversible geared motor operating on 230/415V, 50Hz, shall be provide above 15Mtr mast) The mast shall have lantern of 2 segments, suitable dia with max load carrying capacity as per IS1239. The mast shall be erected on existing RCC footing. The mast shall be supplied with 3mm thick template, lightning arrester of 1.2m length galvanized pipe with top arrow fitted on top of the head frame cover and GLS type aviation twin lA fitting with wiring complete.(excludingfoundation)asper technical data.-12 m/12.5 m - Top 100 mm and Bottom 310 mm dia | Nos | 144100.0 | 144100.0 | 1.0 | False | None | None | False | None | False | 144100.0 | 0 |
2829615 | 91566 | None | code20 | Supply of LED Street light luminaire with pressure diecast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of antiglare clear diffuser with Injection moulded polycarbonate material, delivering superior light out put Rated life Burning Hrs50000hr @ Lumen Maintenance of 70%, maximum light intensity should be between 60 degrees to70 degrees. CCT grteater than 5500K, IP66 optical and electrical compartment & impact resistance of complete luminaire greater than IK08. Power Factor greater than 0.9 with mains, Surge Protection -Min 5KV along with Over voltage/Overload, short circuit/miss-wiring protection. Compatible for pole mounting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS10322 /IEC60598, LM79&LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized mini maltools.LED Light fixture with 90W System Power consumption.LED Efficiency greater than1301m/w, nominal CRI greater than 75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO9001:2008 .Housing with supplier word mark/ name shall be Engraved /Embossing on the die cast housing /Body part. Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer AND Cree/Nichia/Lumileds/Osram make LED Source.-LED Streetlight 90 W | Nos | 9746.0 | 9746.0 | 30.0 | False | None | None | False | None | False | 292380.0 | 0 |
2829616 | 91566 | None | code21 | Supply o f LED flood light luminaire with pressure diecast aluminium housing body for optimal thermal dissipation .Lamp compartment comprising of anti glare clear diffuser with Injectio nmoulded polycarbonate /clear glass material, delivering superior light output Rated life Burning Hrs 50000hr @ Lumen Maintenance of 70%,CCT greater than 5500K, IP66 optical and electrical compartment & impact resistance of complete luminaire greater than IK08. Power Factor greater than 0.9 with mains, Surge Protection-Min 5KV along with Over voltage/ Overload,shortcircuit/miss-wiring protection. Compatible for pole mauling with outer dia of 40mm to 50mm .Universal Voltage driver to operate wide voltage range from 100V to 270V50 /60Hz application. Compliance to IS10322/IEC60598, LM79&LM80 Adherence withRoHS. ULapproved MCPCB. Top access streetlight with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools.LED Light fixture with 240W System Power consumption.LED Efficiency greater than 1301m/w , nominal CRI greater than 75. Luminaire manufacturer should have in-house facility accred it edby NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO9001:2008. Housing with supplier word mark/name shall be Engraved /Embossing on the die cast housing/ Body part Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer &Cree/Nichia/Lumileds/Osrammake LED Source - LED Floodlight 240W | Nos | 24274.8 | 24274.8 | 6.0 | False | None | None | False | None | False | 145648.8 | 0 |
2829617 | 91566 | None | code22 | Providing, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with latest ammendments and conveying to work site including loading and unloading at both destinations and rolling and lowering into trenches, laying true to line and jointing of pipes and specials with electrofusion welding, giving hydraulic test as per relevant ISS with all lead and lifts including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excation, testing and commissioning. The rate is exclusive of required specials and fittings wherever necessary like saddle Tee, stub ends, flanged sets, bedns, reducers etc. complete (Contractor will make his own arrangements for procuring water for testing) etc. complete. NOTE: Upto 110mm dia Coil shall be used. For :HDPE Grade PE80-PN6.0, 63mm dia | m | 207.9 | 207.9 | 4310.0 | False | None | None | False | None | False | 896049.0 | 0 |
2829618 | 91566 | None | code23 | Providing M-Sand : Supplying and filling in plinth, foundations / UG cable work with approved M-sand
including watering, ramming, consolidating and dressing. The rate includes the cost of material, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer- in-charge of works as per the standard procedure. | Cum | 2161.5 | 2161.5 | 365.4 | False | None | None | False | None | False | 789812.1 | 0 |
2829619 | 91566 | None | code24 | Supplying, fixing, wiring, earth electrode for grounding conduits, I.C. cut out sand other equipment's on the meter board using 40 mm dia 2.90mm thick GIpipe 2.5m long buried in a pit. The pit should be filled with equal proportion of salt and charcoal 150 mm all-round the pipe to complete depth. The connection from the pipe to the conduit etc.,is to be established through GI wire of size as per lSI specification 7.3.3.of IS 732 using12 mm dia bolts,nuts, washer sand check nuts etc., the pipe shall have 16 through holes of 12 mm dia | Nos | 3861.0 | 3861.0 | 199.0 | False | None | None | False | None | False | 768339.0 | 0 |
2829620 | 91566 | None | code25 | Supplying fixing and wiring earth electrode for grounding o flifts, transformers, DG sets etc.using 40mm dia 2.9mm thick 2.5mlong GI pipe with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode. The funnel should be enclosed in a CC chamber of 400x400x400 mm with a castir on cover. The earth electrode shall have staggered holes of 12mm dia and the electrode should be covered 150mm all-round with alternate layers of salt and charcoal from the bottom of the CC chamber.The connection from the electrode is to be established through GI strip using GI bolts and nuts. | Nos | 4681.6 | 4681.6 | 12.0 | False | None | None | False | None | False | 56179.2 | 0 |
2829621 | 91566 | None | code26 | GI/Copper strips for grounding connections, using necessary fixing materials as required- 25 x 6 mm Copper strip | m | 1210.0 | 1210.0 | 96.0 | False | None | None | False | None | False | 116160.0 | 0 |
2829622 | 91566 | None | code27 | GI/Copper strips for grounding connections, using necessary fixing materials as required - 600 x 600 x 3 mm Copper plate | Each | 8163.1 | 8163.1 | 6.0 | False | None | None | False | None | False | 48978.6 | 0 |
2829623 | 91566 | None | code28 | Fabricating supplying and mounting MS box made out 16 SWG suitable for floor/wall mounting ,fully weather proof with provision for better heat dissipation, provided with hinged front cover,equipped with tamper proof locking arrangements, with suitable size clamps with necessary cable entry pipe with gland and box should be finished with 7 tank streatment with powder coated paint and finally finished with approved colour etc., complete.-16 SWG | Sq CM | 0.47 | 0.47 | 1010700.0 | False | None | None | False | None | False | 475029.0 | 0 |
2829624 | 91566 | None | code29 | Wiring for lighting /power circuit using one of FRLS PVC insulated 1100V grade, multi strand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:2010-6 mm2 | m | 101.2 | 101.2 | 2200.0 | False | None | None | False | None | False | 222640.0 | 0 |
2829625 | 91566 | None | code30 | Wiring for lighting /power circuit using one of FRLS PVC insulated 1100V grade, multi strand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:2010-2.5 mm2 | m | 46.2 | 46.2 | 795.0 | False | None | None | False | None | False | 36729.0 | 0 |
2829626 | 91566 | None | code31 | Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve,indicator ON/OFF,energy cross-3with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC60898.-6-32 A SP | Each | 456.5 | 456.5 | 153.0 | False | None | None | False | None | False | 69844.5 | 0 |
2829627 | 91566 | None | code32 | Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws,bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuit with adjustable thermal magnetic release,Micro process or release shall have Earth Fault as per IS/IEC60947-2.(Icu=100%lcs).In 4 PMCCB ,all Poles should have protecti on for Short Cicrcuit/OverLoad.For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB .MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoidany accidental contact with live current carrying path with the front cover open).Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.-FOUR Pole 100 A 25 kA | Each | 9335.7 | 9335.7 | 10.0 | False | None | None | False | None | False | 93357.0 | 0 |
2829628 | 91566 | None | code33 | Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws,bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuit with adjustable thermal magnetic release,Micro process or release shall have Earth Fault as per IS/IEC60947-2.(Icu=100%lcs).In 4 PMCCB ,all Poles should have protection for Short-Cicrcuit/Over Load. For Micro processor MCCB SF acility for segregating Priority and Non-PriorityloadsmustbeavailableintheMCCB.MCCB shall be provided with double in sulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open).Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.-FOUR Pole 400 A 36 kA | Each | 31037.6 | 31037.6 | 6.0 | False | None | None | False | None | False | 186225.6 | 0 |
2829629 | 91566 | None | code34 | Supplying & fixing of Porcelain fuse channel with cutout on existing wooden/panel using necessary nuts, bolts and washers.-32 A | Each | 265.1 | 265.1 | 153.0 | False | None | None | False | None | False | 40560.3 | 0 |
2829630 | 91566 | None | code35 | Supplying and fixing angle iron frame work fabricated out of M.S.angleiron..and M.S.Flat 50x50x6 mm with bolts,washers etc.,and painted with 2 coats of red oxide and then two coats of approved paint.-50 x 50 x 6 mm | m | 434.5 | 434.5 | 21.6 | False | None | None | False | None | False | 9385.2 | 0 |
2829631 | 91566 | None | code36 | Supplying & Fixing Aluminium Bus Bar- 25/6 mm | Kgs | 510.0 | 510.0 | 88.0 | False | None | None | False | None | False | 44880.0 | 0 |
2829632 | 91566 | None | code37 | Supplying & Fixing Aluminium Bus Bar- 45/10 mm | Kgs | 510.0 | 510.0 | 175.0 | False | None | None | False | None | False | 89250.0 | 0 |
2829633 | 91566 | None | code38 | Providing and laying factory made Precast concrete solid blocks of 200 mm thickness of grade M10 made of C&D waste including cost of all materials, labour, scaffolding and usage charges of machineries & other incidental charges complete as per the direction of engineer incharge of work. | Cum | 6939.9 | 6939.9 | 36.966 | False | None | None | False | None | False | 256540.3434 | 0 |
2829634 | 91566 | None | code39 | Providing 20 mm cement plaster of mix :1:4 (1 cement: 4 fine sand) to brick/stone masonary including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per
directions of Engineer-in-charge. | Sqm | 389.4 | 389.4 | 359.04 | False | None | None | False | None | False | 139810.176 | 0 |
2829635 | 91566 | None | code40 | Providing and fixing SFRC frame and cover conforming to IS 12592 (part-I)-1988 and IS 12592 (part-II)- 1991 with latest amendment, including cutting slabs to the required size for the opening and fixing the cover in C.C. 1:2:4 and C.M. 1:3 plastering 20 mm thick to all exposed faces, curing for 10 days with all lead and lift with appurtenances. complete. | Sqm | 2105.4 | 2105.4 | 211.0 | False | None | None | False | None | False | 444239.4 | 0 |
2829636 | 91566 | None | code41 | Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm including the cost of materials, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineerin- charge of works as per the standard procedure. | Cum | 1950.3 | 1950.3 | 14.72 | False | None | None | False | None | False | 28708.416 | 0 |
2829637 | 91566 | None | code42 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineerin- charge. (Made of G.I. wire of dia. 4 mm, PVC coated to achieve outer dia not less than 5 mm in required colour and shade) | Sqm | 925.1 | 925.1 | 61.92 | False | None | None | False | None | False | 57282.192 | 0 |
2829638 | 91566 | None | code43 | Providing and fixing RCC precast fencing pole of size 0.15mx0.15mx2.0m casted in M 20 with 20mm down size aggregates making holes for drawing barbed wire at 30 cm c/c using 8 mm dia vertical 4 TMT steel rods and 6 mm dia stirups at 15 cm c/c fixed 1.5 m above Ground level using steel moulding , curing , transportation to work spot including excavation in all types of soil, fixing in plain cement concrete M15 using 20 mm downsize aggregate including aligning to plumb and line providing including cost of all materials, labour,usage charges of machinery complete. | Each | 1193.5 | 1193.5 | 22.0 | False | None | None | False | None | False | 26257.0 | 0 |
2829639 | 91566 | None | code44 | Providing and installing at site of work P.V.C. pipes including cost of pipes and specials and labour, including lowering into trenches, laying true to line, level and perfect linking at joints leak proof including jointing of approved type with all labour charges and all lift charges, handling charges including encasing the pipe around to a depth not less than 15 cms with gravel or selected earth available from the excavation etc. complete.6 kg/m 110mm Dia | m | 393.8 | 393.8 | 240.0 | False | None | None | False | None | False | 94512.0 | 0 |
2829640 | 91566 | None | code45 | Supplying and fixing Electronic Trivector Meter(ETV) suitable for operation LT operation and-CT operated meter in polycarbonate body in class 0.5 accuracy as per IS14697 and completely wired. | Each | 4829.0 | 4829.0 | 7.0 | False | None | None | False | None | False | 33803.0 | 0 |
2829641 | 91566 | None | code46 | Supplying, fixing and wiring Electronic Trivector Meter (ETV) 5to20 A single phase Class-1 Accuracy with Temper Proof EnergyMeter. | Each | 1518.0 | 1518.0 | 1111.0 | False | None | None | False | None | False | 1686498.0 | 0 |
2829642 | 91566 | None | code47 | BESCOM Application,Registration Fees, Site Drawing with Skitch, Power Supply Agreement/E-Stamp Paper,Working Completion Report..etc | LS | 3535.0 | 3535.0 | 1114.0 | False | None | None | False | None | False | 3937990.0 | 0 |
2829643 | 91566 | None | code48 | LT Current Transformer, 3.75 VA, Ring type as per IS-2705 Part-1&2-CT Ratio - 400/5A, 0.5 Accuracy Class | Each | 641.3 | 641.3 | 24.0 | False | None | None | False | None | False | 15391.2 | 0 |
2829644 | 91566 | None | code49 | GSM modem with connecting cable for remote communicating capabilities | Each | 15856.5 | 15856.5 | 6.0 | False | None | None | False | None | False | 95139.0 | 0 |