2862897 | 93079 | None | 1.14.1 | Godown: Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work In all kinds of soils Depth upto 3 m | Cum | 76.65 | 76.65 | 27.27 | False | None | None | False | None | False | 2090.2455 | 0 |
2862898 | 93079 | None | 2.1.4 | Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork shall be paid separately) Mix 1:3:6 (M10) Using 20 mm nominal size graded crushed coarse aggregates | Cum | 6014.4 | 6014.4 | 9.14 | False | None | None | False | None | False | 54971.616 | 0 |
2862899 | 93079 | None | 5.1.1 | Providing Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) upto plinth level with :Cement mortar 1:6 (1 cement : 6 coarse sand) | Cum | 4987.5 | 4987.5 | 8.3 | False | None | None | False | None | False | 41396.25 | 0 |
2862900 | 93079 | None | 2.4.3 | Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork to be paid separately) M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregate | Cum | 6794.93 | 6794.93 | 18.25 | False | None | None | False | None | False | 124007.4725 | 0 |
2862901 | 93079 | None | 1.9 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. | Cum | 214.2 | 214.2 | 27.27 | False | None | None | False | None | False | 5841.234 | 0 |
2862902 | 93079 | None | 1.8 | Construction of Embankment by excavating the available approved Gravel/Murrum deposited at a place or borrow pits during or prior excavation with all lifts and lead, transportation to site, spreading, grading to required slope and compacting to meet the requirement complete as per specifications, including cost of labour,rolling,water,all materials,usage& all other appurtenaces required to complete the work. | Cum | 422.1 | 422.1 | 26.57 | False | None | None | False | None | False | 11215.197 | 0 |
2862903 | 93079 | None | 6.7 | Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level in all shapes and sizes in Cement mortar 1:4 (1 cement : 4 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work. | Cum | 7295.4 | 7295.4 | 11.85 | False | None | None | False | None | False | 86450.49 | 0 |
2862904 | 93079 | None | 11.34B | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to openings / wooden frames with rawl plugs screws etc. | Kg | 150.15 | 150.15 | 247.86 | False | None | None | False | None | False | 37216.179 | 0 |
2862905 | 93079 | None | 11.32 | Providing Thermo-Mechanically Treated bars of grade Fe-500D or more Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position, binding and anchoring to adjacent members whereever necessary complete as per Design including cost of material, labour, usage charges complete as per specifications. (The laps and wastages shall not be measured separately) | MT | 87150.0 | 87150.0 | 1.92 | False | None | None | False | None | False | 167328.0 | 0 |
2862906 | 93079 | None | 8.1.2 | Providing 12 mm cement plaster with cement mortar 1:6 (1 cement: 6 fine sand) including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 207.9 | 207.9 | 51.87 | False | None | None | False | None | False | 10783.773 | 0 |
2862907 | 93079 | None | 8.8 | Providing 18 mm cement plaster in two coats under layer 12 mm thick cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster with cement mortar 1:6 (1 cement : 6 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 322.35 | 322.35 | 165.51 | False | None | None | False | None | False | 53352.1485 | 0 |
2862908 | 93079 | None | 8.21 | Providing White washing with lime to give an even shade :New work (three coats) with lime of approved quality, including cost of materials, labour complete as per specifications and as per directions of Engineerin-charge | Sqm | 19.95 | 19.95 | 165.51 | False | None | None | False | None | False | 3301.9245 | 0 |
2862909 | 93079 | None | 8.33.3 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two coat applied @ 0.90 ltr/10 m² over an under coat of primer applied @ 0.80 ltr/10 m² of approved brand and manufacture including preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 111.3 | 111.3 | 16.38 | False | None | None | False | None | False | 1823.094 | 0 |
2862910 | 93079 | None | 19.7.1 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material to the appropriate disposal area as per direction of Engineer-in-charge | Cum | 387.45 | 387.45 | 17.25 | False | None | None | False | None | False | 6683.5125 | 0 |
2862911 | 93079 | None | 1.2.1 | Electrification: Concealed conduit system : Supplying heavy gauge PVC conduit pipe ……mm dia .mm thick confirming to IS 2509 with suitable size bends, metal/PVC junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary. 19/20mm dia 2mm thick ( Page No.1, Item No.1.2.1 of PWD Electrical SR 2021-22) | m | 61.0 | 61.0 | 25.0 | False | None | None | False | None | False | 1525.0 | 0 |
2862912 | 93079 | None | 1.3.1 | Supplying heavy gauge PVC Conduit Pipe ….dia .mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering up to the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary. 19/20mm dia 2mm thick ( Page No.1, Item No.1.3.1 of PWD Electrical SR 2021-22) | m | 75.0 | 75.0 | 15.0 | False | None | None | False | None | False | 1125.0 | 0 |
2862913 | 93079 | None | 2.1.1 | Point wiring using Copper wire with switch : Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) with a 6Amps flush type SP control switch shall be fixed on the existing plastic sheet/gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet. Short point upto 3Mtr from tapping point to out let via switch ( Page No.2, Item No.2.1.1 of PWD Electrical SR 2021-22) | Point | 276.0 | 276.0 | 6.0 | False | None | None | False | None | False | 1656.0 | 0 |
2862914 | 93079 | None | 2.1.2 | Point wiring using Copper wire with switch : Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) with a 6Amps flush type SP control switch shall be fixed on the existing plastic sheet/gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet. Medium point above 3Mtr upto 6Mtr from tapping point to out let via switch ( Page No.3, Item No.2.1.2 of PWD Electrical SR 2021-22) | Point | 386.0 | 386.0 | 6.0 | False | None | None | False | None | False | 2316.0 | 0 |
2862915 | 93079 | None | 2.1.3 | Point wiring using Copper wire with switch : Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) with a 6Amps flush type SP control switch shall be fixed on the existing plastic sheet/gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet. Long point above 6Mtr upto 10Mtr from tapping point to out let via switch ( Page No.3, Item No.2.1.3 of PWD Electrical SR 2021-22) | Point | 567.0 | 567.0 | 6.0 | False | None | None | False | None | False | 3402.0 | 0 |
2862916 | 93079 | None | 3.7 | Supplying and fixing 32Amps security and energy saving DP switch with key tag suitable to operate suitable to operate on 230 Volts, 50Hz AC supply & completely wired on existing box. ( Page No.6, Item No.3.7 of PWD Electrical SR 2021-22) | Each | 747.0 | 747.0 | 1.0 | False | None | None | False | None | False | 747.0 | 0 |
2862917 | 93079 | None | 3.5.1 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. " A Group 1 to 3 Module (Page No.5, Item No.3.5.1 of PWD Electrical SR 2021-22) | Each | 152.0 | 152.0 | 1.0 | False | None | None | False | None | False | 152.0 | 0 |
2862918 | 93079 | None | 3.5.2 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. " A Group 4 Module ( Page No.5, Item No.3.5.2 of PWD Electrical SR 2021-22) | Cm/weight | 175.0 | 175.0 | 1.0 | False | None | None | False | None | False | 175.0 | 0 |
2862919 | 93079 | None | 3.5.3 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. " A Group 6 Module A Group 6 Module ( Page No.5, Item No.3.5.3 of PWD Electrical SR 2021-22) | Each | 244.0 | 244.0 | 1.0 | False | None | None | False | None | False | 244.0 | 0 |
2862920 | 93079 | None | 3.5.4 | Supplying and fixing superior quality modular switch mounting polycorbonate plate with necessary supporting back plate with required no's of machine screwes, bolts, nuts etc., complete on the existing metal/ PVC box. " A Group 8 Module( Page No.5, Item No.3.5.4 of PWD Electrical SR 2021-22) | Each | 302.0 | 302.0 | 2.0 | False | None | None | False | None | False | 604.0 | 0 |
2862921 | 93079 | None | 3.6.1 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. Using Group " A" Materials 6Amps one way. ( Page No.5, Item No.3.6.1 of PWD Electrical SR 2021-22) | Each | 88.0 | 88.0 | 2.0 | False | None | None | False | None | False | 176.0 | 0 |
2862922 | 93079 | None | 3.6.2 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. Using Group " A" Materials 6Amps Two way. ( Page No.5, Item No.3.6.2 of PWD Electrical SR 2021-22) | Each | 152.0 | 152.0 | 2.0 | False | None | None | False | None | False | 304.0 | 0 |
2862923 | 93079 | None | 3.6.4 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. Using Group " A" Materials Stepped Fan regulator. ( Page No.5, Item No.3.6.4 of PWD Electrical SR 2021-22) | Each | 313.0 | 313.0 | 2.0 | False | None | None | False | None | False | 626.0 | 0 |
2862924 | 93079 | None | 3.6.9 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. Using Group " A" Materials 6Amps Bell bush. ( Page No.5, Item No.3.6.9 of PWD Electrical SR 2021-22) | Each | 159.0 | 159.0 | 2.0 | False | None | None | False | None | False | 318.0 | 0 |
2862925 | 93079 | None | 3.6.12 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. Using Group " A" Materials TV/ Telephone socket ( Page No.5, Item No.3.6.12 of PWD Electrical SR2021-22) | Each | 147.0 | 147.0 | 2.0 | False | None | None | False | None | False | 294.0 | 0 |
2862926 | 93079 | None | 2.3.2 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.Group A Materials.1.5 sqmm ( Page No.3, Item No.2.3.2 of PWD Electrical SR 2021-22) | Mtr | 26.0 | 26.0 | 125.0 | False | None | None | False | None | False | 3250.0 | 0 |
2862927 | 93079 | None | 2.3.3 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.Group A Materials.2.5 sqmm ( Page No.3, Item No.2.3.3 of PWD Electrical SR 2021-22) | Mtr | 40.0 | 40.0 | 75.0 | False | None | None | False | None | False | 3000.0 | 0 |
2862928 | 93079 | None | 12.46 | Supplying & Fixing of 70-150 Watts lamp holder 2 Pin ( Page No.43, Item No.12.46 of PWD Electrical SR 2021-22) | No | 118.0 | 118.0 | 5.0 | False | None | None | False | None | False | 590.0 | 0 |
2862929 | 93079 | None | 11.3.3 | Supplying of .feet PVC Batten with integrated LED tube .W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI 80. Power Input: 220-240V @ 50/60Hz & Power factor 0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition. 1x 4' - 36 /40 w ( Page No.34, Item No.11.3.3 of PWD Electrical SR 2021-22) | Each | 1197.0 | 1197.0 | 6.0 | False | None | None | False | None | False | 7182.0 | 0 |
2862930 | 93079 | None | 13.7.1 | Fixing all types and all capacities of fluorescent/false ceiling/spot light/CFL/LED fittings indoor on the wall/ceiling/rafters/girders using 23/0.0076" twin twisted PVC insulated wires, required Nos of round blocks and clamps On wall/Ceiling/Rafter/Girders (Page No.45, Item No. 13.7.1 PWD Electrical SR 2021-22) | Each | 119.0 | 119.0 | 6.0 | False | None | None | False | None | False | 714.0 | 0 |