tenderSubEstimateList | createdTs | version | createdDate | modifiedDate | workCategoryName | subEstimateName | estimateTotal | itemList |
---|
1709119905000 | 0 | None | None | Sub-Station | SUBSTATION SUPPLY | 17606765.83 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
2844846 | 92188 | None | SS1 | Supply and fixing of 2 Nos. of 50 X 8 mm copper flats from Neutral Terminal to the Earthmat through NCT along with necessary Support Pin Insulators. | No | 11800.0 | 11800.0 | 1.0 | False | None | None | False | None | False | 11800.0 | 0 | 2844847 | 92188 | None | SS2 | Supply, Erection & Commissioning of Nitrogen Injection Fire Extinguishing System for Power Transformer | Set | 1347129.3 | 1347129.3 | 1.0 | False | None | None | False | None | False | 1347129.3 | 0 | 2844848 | 92188 | None | SS3 | Circuit Breaker :
SF6 Gas circuit breaker with Semi-Pneumatic / Pneumatic operated / Spring type operating mechanism, including mounting arrangements, rigid bi-metallic terminal connector complete suitable for Drake ACSR conductor and mounting structures as per KPTCL Technical specification
110kV, 1250A,40KA Class
a) For 110kV Transformer
b) For 110kV Line | No | 829551.8 | 829551.8 | 2.0 | False | None | None | False | None | False | 1659103.6 | 0 | 2844849 | 92188 | None | SS4 | Isolators : Isolators including marshalling box and suitable terminal connectors, as required as per technical specification with solid core cylindrical post insulators: as per KPTCL Technical specification
A) 110KV, 1250A, 40KA Class Double Break Manually operated isolator With terminal connectors suitable for Drake ACSR.
a) Upright mounting type with earth switch with live point height 4600mm | Set | 449757.0 | 449757.0 | 2.0 | False | None | None | False | None | False | 899514.0 | 0 | 2844850 | 92188 | None | SS5 | b) Upright mounting type without earth switch with live point height 4600 mm | Set | 379794.8 | 379794.8 | 4.0 | False | None | None | False | None | False | 1519179.2 | 0 | 2844851 | 92188 | None | SS6 | B) 11KV Isolators:
i) 11KV isolators, Double Break 400A, 25KA capacity with rigid bi-metallic terminal connectors suitable for Coyote ACSR. | Set | 25086.8 | 25086.8 | 1.0 | False | None | None | False | None | False | 25086.8 | 0 | 2844852 | 92188 | None | SS7 | ii) 11KV isolators, Single break 400A, 25KA capacity with Roster switch with rigid bi-metallic terminal connectors suitable for Coyote ACSR. | Set | 17648.08 | 17648.08 | 5.0 | False | None | None | False | None | False | 88240.4 | 0 | 2844853 | 92188 | None | SS8 | Current Transformer : Current Transformer including Marshalling box, Single phase, oil filled outdoor type with rigid bimetallic terminal connectors suitable for Drake ACSR.
i) 110 KV Class, 31.5 KA, CT of ratio 400-200/1-1-1A for Lines.
For metering: Accuracy 0.2s, Burden 10VA
For back up protection : Accuracy class 5P20, Burden 30VA
For differential/ distance protection:Accuracy class- PS, Vk 800V, Rct 4ohm at 400/1A | No | 159913.6 | 159913.6 | 3.0 | False | None | None | False | None | False | 479740.8 | 0 | 2844854 | 92188 | None | SS9 | ii)110 KV Class, 31.5 KA, CT of ratio 200-100/1-1-1A for Transformers.
For metering: Accuracy class- 0.2s, Burden 10VA
For back up protection : Accuracy class - 5P20, Burden 30VA
For differential/ distance protection: Accuracy class-PS, Vk-400V, Rct 2ohm at 200/1A | No | 158485.8 | 158485.8 | 3.0 | False | None | None | False | None | False | 475457.4 | 0 | 2844855 | 92188 | None | SS10 | iii) 11 KV Class, 25KA,NCT of ratio 1200-800/1-1A for REFR Protection. (of similar rating and ratio as that of Incomer of 11kV Switchgear) with terminal connector suitable for 2 Nos. of 50x8mm Copper flats.
Note:
1) For details refer Annexure-IIB: Technical parameters of Current transformers for type and rating attached at the end of this schedule.
2) All the Current transformers in each KV class shall be of One and the same make for interchangeability and reliability of performance.
3) The make and characteristics of 11kV NCT should be the same as that of the incomer CT of 11kV Switchgear
4) The Terminal connectors for 11kV NCT shall be suitable for 50X8mm Copper flat. | No | 67106.6 | 67106.6 | 1.0 | False | None | None | False | None | False | 67106.6 | 0 | 2844856 | 92188 | None | SS11 | Voltage Transformer:
a) Voltage Transformer 110kV, Single Phase, Oil filled outdoor type including marshalling box with rigid bimetallic terminal connectors suitable for drake ACSR as per technical specification. Ratio : 110kV/root3 / 110V/root3 - 110V/root3 - 110V/root3
Core-1: 300 VA, Accuracy class 0.2, metering.
Core-2: 200VA, Accuracy class 3P, protection
Core-3: 50VA, Accuracy class 3P, open delta protection. | No | 177047.2 | 177047.2 | 3.0 | False | None | None | False | None | False | 531141.6 | 0 | 2844857 | 92188 | None | SS12 | Lightning Arrestor :
Surge arrestors (Porcelain housing) Metal Oxide Gap less type as per technical specification with suitable rigid bi-metallic terminal connectors suitable for Drake ACSR.
i) 96 KV, 10 KA, Class - II, Heavy duty metal oxide type | No | 48545.2 | 48545.2 | 9.0 | False | None | None | False | None | False | 436906.8 | 0 | 2844858 | 92188 | None | SS13 | ii) 9 KV, 5KA Station Class with connector and clamps | No | 1085.6 | 1085.6 | 18.0 | False | None | None | False | None | False | 19540.8 | 0 | 2844859 | 92188 | None | SS14 | Capacitor Bank : Design, Engineering , supply, erection, testing & commissioning of 2.9 MVAR, 12.1KV Capacitor Bank, star connected, Double Bank with internal fuses, terminal connectors, with suitable neutral CT and Station Class LA's, 0.2% series reactor on neutral side with mounting structures for NCT, Capacitor Bank, Station Class LA's, Series Reactor etc., with 10%
spare capacitors complete as per specification (including erection and testing & commissioning).
Note : For 11kV Switchgear & remote announciation / control of the Capacitor Bank refer Techno-commercial sheet. | Set | 635371.0 | 635371.0 | 1.0 | False | None | None | False | None | False | 635371.0 | 0 | 2844860 | 92188 | None | SS15 | Control Panels :
Simplex Type Control and Relay Panel complete as per specifications (Control Voltage 110 V DC). (SCADA compatible)
NOTE :
1) All the C&R panels and associated panels shall be of one and same make for uniformity and interchangeability of components.
2) The accuracy class of metering core of CT's shall be 0.2s accuracy class, VTs and Electronic trivector meters of C&R panels shall be 0.2 accuracy class, irrrespective of what has been indicated else where in the bid documents.
3) The Electronic Trivector meters with 0.2s accuracy class with ABT & TOD features & DLMS compliant has to be provided both on HV side and LV side of Transformer.
4) All numerical relays shall conform to IEC 61850 protocol.
a) For Power Transformer 10 MVA, 110/11 KV | No | 745311.6 | 745311.6 | 1.0 | False | None | None | False | None | False | 745311.6 | 0 | 2844861 | 92188 | None | SS16 | b) For 110 KV Transmission line. | No | 538280.6 | 538280.6 | 1.0 | False | None | None | False | None | False | 538280.6 | 0 | 2844862 | 92188 | None | SS17 | B) 11 KV ODS and take off structure
i) Supplying of D.P. Structure with all accessories using 9.5mtrs long, 300Kg WL RCC poles including H frame suitable for mounting roaster GOS / DB GOS with provision for fixing 9KV lightning arrestors etc., complete set with wiring materials. | No | 30748.44 | 30748.44 | 5.0 | False | None | None | False | None | False | 153742.2 | 0 | 2844863 | 92188 | None | SS18 | BUS BAR FORMATION:
Note: The scope also includes installing insulator strings complete with necessary Hardwares and stringing of the conductor / Earth wire etc.
a) Drake ACSR | m | 456.65 | 456.65 | 500.0 | False | None | None | False | None | False | 228325.0 | 0 | 2844864 | 92188 | None | SS19 | BUS BAR FORMATION:
Note: The scope also includes installing insulator strings complete with necessary Hardwares and stringing of the conductor / Earth wire etc.
b) AAAC Moose | m | 651.36 | 651.36 | 30.0 | False | None | None | False | None | False | 19540.8 | 0 | 2844865 | 92188 | None | SS20 | BUS BAR FORMATION:
Note: The scope also includes installing insulator strings complete with necessary Hardwares and stringing of the conductor / Earth wire etc.
c) Coyote ACSR | m | 164.02 | 164.02 | 30.0 | False | None | None | False | None | False | 4920.6 | 0 | 2844866 | 92188 | None | SS21 | Insulators :
i) Post insulators solid core 110 KV Class
1Unit/Stack | No | 14224.9 | 14224.9 | 15.0 | False | None | None | False | None | False | 213373.5 | 0 | 2844867 | 92188 | None | SS22 | Disc insulators
(i) 11kV,90KN Disc insulators | No | 699.74 | 699.74 | 162.0 | False | None | None | False | None | False | 113357.88 | 0 | 2844868 | 92188 | None | SS23 | ii) HARDWARES :
1. Bolted type Tension clamp to suit Drake ACSR - 90kN (110 kV Side) | No | 2862.68 | 2862.68 | 12.0 | False | None | None | False | None | False | 34352.16 | 0 | 2844869 | 92188 | None | SS24 | 4. Bolted type Suspension clamp to suit Drake ACSR - 90KN (110kV side) | No | 1797.13 | 1797.13 | 6.0 | False | None | None | False | None | False | 10782.78 | 0 | 2844870 | 92188 | None | SS25 | Hardwares :
C Type Wedge Connector suitable for Drake - Drake ACSR Conductor
(110kV Bus PI & 11kV incomer) | No | 2719.9 | 2719.9 | 12.0 | False | None | None | False | None | False | 32638.8 | 0 | 2844871 | 92188 | None | SS26 | C type wedge connector suitable for Lynx-Drake ( 110 kV line side) | No | 2266.77 | 2266.77 | 12.0 | False | None | None | False | None | False | 27201.24 | 0 | 2844872 | 92188 | None | SS27 | Post Insulator clamp suitable for Single Drake ACSR and 110 kV Solid Core Insulator | No | 1191.8 | 1191.8 | 12.0 | False | None | None | False | None | False | 14301.6 | 0 | 2844873 | 92188 | None | SS28 | Auxiliary Transformer:
Station Auxiliary Transformer with oil, outdoor type, 100 kVA, 11 kV/433 V, 3 Ph, Vector group Dyn11, off load tap changer (with 5 taps) with step voltage of 2.5%, as per specifications. | Set | 412051.28 | 412051.28 | 1.0 | False | None | None | False | None | False | 412051.28 | 0 | 2844874 | 92188 | None | SS29 | Supply of Double pole structure with 9. 5Mtrs RCC poles and with 11KV, 400A double break isolators, H-Frame and 9KV, 5KA surge arrestors (3 Nos), auxiliary transformer including materials such as DPset, H-Frame, GOS, HG Fuse unit, angle for fixing HG fuse unit (2 pole clamps bolts & nuts), PIN Insulator, PIN for insulator, LTD box, Trivector Meter, 9kV LA) etc. | Set | 91878.34 | 91878.34 | 1.0 | False | None | None | False | None | False | 91878.34 | 0 | 2844875 | 92188 | None | SS30 | LTAC panel (indoor): 415V, as per technical specification comprising of Voltmeter, Ammeter, & 1No. ETV meter. 1No, I/C MCCB 200A+2Nos .3 phase 63A OG HRC fuse+ 2nos. 3 phase 32A OG HRC fuse+ 6Nos. 3 phase,16A HRC fuse etc,. Complete as per technical specification. | No | 101373.8 | 101373.8 | 1.0 | False | None | None | False | None | False | 101373.8 | 0 | 2844876 | 92188 | None | SS31 | B) A.C. Distribution Box (Outdoor) :
AC distribution box single front type, 6 terminals, 1200x1350x300 mm, 1 I/C of 100A, MCCB 20KA + 6 O/G MCB 16A + 1 O/G of 100A , HRC fuse | No | 85668.0 | 85668.0 | 2.0 | False | None | None | False | None | False | 171336.0 | 0 | 2844877 | 92188 | None | SS32 | LT Power armoured UG cable as per specification.
a) 1.1 KV, 4 X 95 Sqmm Aluminium, cable with glands/lugs/ferrules | m | 899.16 | 899.16 | 100.0 | False | None | None | False | None | False | 89916.0 | 0 | 2844878 | 92188 | None | SS33 | b) 1.1 KV, 4 X 25 Sqmm Copper, cable with glands/lugs/ferrules | m | 1021.88 | 1021.88 | 150.0 | False | None | None | False | None | False | 153282.0 | 0 | 2844879 | 92188 | None | SS34 | c) 1.1 KV, 4 X 10 Sqmm Copper, cable with glands/lugs/ferrules | m | 442.5 | 442.5 | 200.0 | False | None | None | False | None | False | 88500.0 | 0 | 2844880 | 92188 | None | SS35 | Station Battery:
110V, 200AH Battery set (Plante/Grid/Nickel Cadmium Type) consists of 55 Nos. of cells with accessories as per specification. | Set | 772851.2 | 772851.2 | 1.0 | False | None | None | False | None | False | 772851.2 | 0 | 2844881 | 92188 | None | SS36 | Station Battery charger: Battery charger suitable for 110V, 200AH, Battery set (Plante/Grid/Nickel Cadmium Type) consisting of 55 No. cells with Float Cum Booster type battery charger as per specification | Set | 199892.0 | 199892.0 | 1.0 | False | None | None | False | None | False | 199892.0 | 0 | 2844882 | 92188 | None | SS37 | DC Distribution Panel (Indoor type) as per Technical specification comprising of Earth fault indicator, Indication circuit for AC main failure, 1 No. 100A SFU for IC + 12 Nos., 32A SFU for OG etc., complete. | No | 61395.4 | 61395.4 | 1.0 | False | None | None | False | None | False | 61395.4 | 0 | 2844883 | 92188 | None | SS38 | Copper Control Cables :
1.1kV PVC insulated Copper Control Cable with Lugs/Ferrules as per technical specifications.
i) 19 C x 2.5 Sqmm | m | 619.5 | 619.5 | 1100.0 | False | None | None | False | None | False | 681450.0 | 0 | 2844884 | 92188 | None | SS39 | ii) 4 C x 6.0 Sqmm | m | 291.46 | 291.46 | 1300.0 | False | None | None | False | None | False | 378898.0 | 0 | 2844885 | 92188 | None | SS40 | iii) 4 C x 2.5 Sqmm | m | 167.56 | 167.56 | 1050.0 | False | None | None | False | None | False | 175938.0 | 0 | 2844886 | 92188 | None | SS41 | iv) 2 C x 2.5 Sqmm | m | 110.92 | 110.92 | 600.0 | False | None | None | False | None | False | 66552.0 | 0 | 2844887 | 92188 | None | SS42 | v) 2 C x 6.0 Sqmm | m | 181.72 | 181.72 | 800.0 | False | None | None | False | None | False | 145376.0 | 0 | 2844888 | 92188 | None | SS43 | vi)10C x 2.5Sqmm | m | 369.34 | 369.34 | 100.0 | False | None | None | False | None | False | 36934.0 | 0 | 2844889 | 92188 | None | SS44 | 11KV U.G. Cable with the required cable terminations at both ends.
a) One run of 11kV, XLPE 95 sq.mm Al., 3 core cable - (to be run for Auxiliary Transformers from 11KV switch Gear to Auxiliary Transformer ). | m | 1049.8 | 1049.8 | 50.0 | False | None | None | False | None | False | 52490.0 | 0 | 2844890 | 92188 | None | SS45 | b) 11KV XLPE cable, 1000Sq. mm. (2runs of 1Cx1000Sqmm)Aluminium cable from transformers to 11KV Switchgear. | m | 1398.3 | 1398.3 | 150.0 | False | None | None | False | None | False | 209745.0 | 0 | 2844891 | 92188 | None | SS46 | c) 11KV XLPE cable, 240Sq. mm. Aluminium cable 3 Core to be run from 11KV Switchgear to 11kV take off DP Structure. | m | 1954.13 | 1954.13 | 200.0 | False | None | None | False | None | False | 390826.0 | 0 | 2844892 | 92188 | None | SS47 | d) Heat Shrinkable type Cable Termination kits suitable for following sizes as per Technical Specification.
i) 95 Sq mm 3 core
ia) Indoor | No | 4417.92 | 4417.92 | 1.0 | False | None | None | False | None | False | 4417.92 | 0 | 2844893 | 92188 | None | SS48 | ib) Outdoor | No | 4799.05 | 4799.05 | 1.0 | False | None | None | False | None | False | 4799.05 | 0 | 2844894 | 92188 | None | SS49 | ii) 1000Sq mm Single core
iia) Indoor | No | 4493.44 | 4493.44 | 4.0 | False | None | None | False | None | False | 17973.76 | 0 | 2844895 | 92188 | None | SS50 | iib) Outdoor | No | 4790.8 | 4790.8 | 4.0 | False | None | None | False | None | False | 19163.2 | 0 | 2844896 | 92188 | None | SS51 | ii) 240Sq mm 3 core
iia) Indoor | No | 5535.38 | 5535.38 | 6.0 | False | None | None | False | None | False | 33212.28 | 0 | 2844897 | 92188 | None | SS52 | iib) Outdoor | No | 6275.24 | 6275.24 | 6.0 | False | None | None | False | None | False | 37651.44 | 0 | 2844898 | 92188 | None | SS53 | Fire fighting equipment with necessary mounting stands.
a) Foam type extinguisher (Mechanical type):
i) 50.0 litres capacity | No | 11932.16 | 11932.16 | 4.0 | False | None | None | False | None | False | 47728.64 | 0 | 2844899 | 92188 | None | SS54 | ii) 9.0 litres capacity | No | 4859.24 | 4859.24 | 4.0 | False | None | None | False | None | False | 19436.96 | 0 | 2844900 | 92188 | None | SS55 | b) Water type (Gas pressure type) - 9.0 litres capacity | No | 2953.54 | 2953.54 | 6.0 | False | None | None | False | None | False | 17721.24 | 0 | 2844901 | 92188 | None | SS56 | c) Carbondioxide type - 4.5 Kg capacity | No | 10255.38 | 10255.38 | 6.0 | False | None | None | False | None | False | 61532.28 | 0 | 2844902 | 92188 | None | SS57 | d) Sand type
i) G.I. Bucket 15 litres capacity | No | 711.54 | 711.54 | 12.0 | False | None | None | False | None | False | 8538.48 | 0 | 2844903 | 92188 | None | SS58 | ii) Steel stands for the above to have 4 Buckets to each stand. | No | 2787.16 | 2787.16 | 3.0 | False | None | None | False | None | False | 8361.48 | 0 | 2844904 | 92188 | None | SS59 | Equipment required for establishing SCADA Communication as per KPTCL specification
Note: 1. Satellite communication required will be arranged by SLDC
2. The detailed BOM & specification of SCADA equipment shall be obtained from SEE-SCADA
a) Remote Terminal Unit (RTU) | No | 1163657.0 | 1163657.0 | 1.0 | False | None | None | False | None | False | 1163657.0 | 0 | 2844905 | 92188 | None | SS60 | b) Data Concentrator Unit (DCU) | No | 44261.8 | 44261.8 | 1.0 | False | None | None | False | None | False | 44261.8 | 0 | 2844906 | 92188 | None | SS61 | c) 2kVA online UPS (230V AC 1Phase 50Hz) | No | 198464.2 | 198464.2 | 1.0 | False | None | None | False | None | False | 198464.2 | 0 | 2844907 | 92188 | None | SS62 | Materials for new bay integration to existing SCADA panel
1) Multi Functional Transducer (MFT) 0.2s class including labour | No | 5752.5 | 5752.5 | 1.0 | False | None | None | False | None | False | 5752.5 | 0 | 2844908 | 92188 | None | SS63 | 2)Opto Coupler (220 or 110kV DC) including Labour | No | 1548.16 | 1548.16 | 1.0 | False | None | None | False | None | False | 1548.16 | 0 | 2844909 | 92188 | None | SS64 | 3)RJ-45 cable for Energy meter integration to DCU | m | 263.14 | 263.14 | 5.0 | False | None | None | False | None | False | 1315.7 | 0 | 2844910 | 92188 | None | SS65 | Supply of following Power cables for SCADA.
i) Current Cables - copper core with c/s 4.0sqmm multistrand 4 core | m | 208.86 | 208.86 | 25.0 | False | None | None | False | None | False | 5221.5 | 0 | 2844911 | 92188 | None | SS66 | ii) Voltage Cables-Copper core with c/s 2.5sqmm multistrand 4core | m | 167.56 | 167.56 | 25.0 | False | None | None | False | None | False | 4189.0 | 0 | 2844912 | 92188 | None | SS67 | iii) Signal cables- armoured copper core with c/s 0.5sqmm multistrand 10core | m | 168.74 | 168.74 | 505.0 | False | None | None | False | None | False | 85213.7 | 0 | 2844913 | 92188 | None | SS68 | iv) Control cables - copper core with c/s 1.5sqmm multistrand 10core | m | 182.9 | 182.9 | 165.0 | False | None | None | False | None | False | 30178.5 | 0 | 2844914 | 92188 | None | SS69 | v) Control cables-copper core with c/s 4.0sqmm multistrand 3core for AC input to UPS & UPS to RTU, confirming to KPTCL specifications. | m | 187.62 | 187.62 | 15.0 | False | None | None | False | None | False | 2814.3 | 0 | 2844915 | 92188 | None | SS70 | vi) Control cables-copper core with c/s 32.0sqmm multistrand for Battery conforming to KPTCL specifications. | m | 448.4 | 448.4 | 30.0 | False | None | None | False | None | False | 13452.0 | 0 | 2844916 | 92188 | None | SS71 | Maintenance Tools and Plants
1) Portable (mobile) oil pumps (1/2 HP Air pump 500 to 1000 gallons) | No | 23891.46 | 23891.46 | 1.0 | False | None | None | False | None | False | 23891.46 | 0 | 2844917 | 92188 | None | SS72 | 2)Telescopic ladder Aluminium 6 Mtr. Height | No | 26693.96 | 26693.96 | 1.0 | False | None | None | False | None | False | 26693.96 | 0 | 2844918 | 92188 | None | SS73 | 3) Ring spanner set | Set | 1038.4 | 1038.4 | 1.0 | False | None | None | False | None | False | 1038.4 | 0 | 2844919 | 92188 | None | SS74 | 4) Tube spanner set | Set | 1693.3 | 1693.3 | 1.0 | False | None | None | False | None | False | 1693.3 | 0 | 2844920 | 92188 | None | SS75 | 5) Pipe wrench 24 inch | No | 1475.0 | 1475.0 | 2.0 | False | None | None | False | None | False | 2950.0 | 0 | 2844921 | 92188 | None | SS76 | 6)Pipe wrench 18 inch. | No | 816.56 | 816.56 | 2.0 | False | None | None | False | None | False | 1633.12 | 0 | 2844922 | 92188 | None | SS77 | 7) Hydraulic crimping tools up to 1000 Sq.mm | No | 73175.34 | 73175.34 | 1.0 | False | None | None | False | None | False | 73175.34 | 0 | 2844923 | 92188 | None | SS78 | 8) Rubber hand gloves (15 kV tested) | Pairs | 345.74 | 345.74 | 3.0 | False | None | None | False | None | False | 1037.22 | 0 | 2844924 | 92188 | None | SS79 | 9)Rechargeable 5W LED hand torch | No | 1509.22 | 1509.22 | 5.0 | False | None | None | False | None | False | 7546.1 | 0 | 2844925 | 92188 | None | SS80 | 10)Hand torch 3 Cells | No | 1180.0 | 1180.0 | 2.0 | False | None | None | False | None | False | 2360.0 | 0 | 2844926 | 92188 | None | SS81 | 11)Insulated cutting plier 12 inch size | No | 463.74 | 463.74 | 3.0 | False | None | None | False | None | False | 1391.22 | 0 | 2844927 | 92188 | None | SS82 | 12)Insulated cutting plier 8 inch size | No | 278.48 | 278.48 | 3.0 | False | None | None | False | None | False | 835.44 | 0 | 2844928 | 92188 | None | SS83 | 13) Line live tester AC/DC 500 V | No | 366.98 | 366.98 | 2.0 | False | None | None | False | None | False | 733.96 | 0 | 2844929 | 92188 | None | SS84 | 14) Screw driver 18" | No | 263.14 | 263.14 | 3.0 | False | None | None | False | None | False | 789.42 | 0 | 2844930 | 92188 | None | SS85 | 15) Screw driver 12" | No | 88.5 | 88.5 | 3.0 | False | None | None | False | None | False | 265.5 | 0 | 2844931 | 92188 | None | SS86 | 16) Hammer 8 lbs | No | 586.46 | 586.46 | 2.0 | False | None | None | False | None | False | 1172.92 | 0 | 2844932 | 92188 | None | SS87 | 17) Hammer 2 lbs | No | 293.82 | 293.82 | 2.0 | False | None | None | False | None | False | 587.64 | 0 | 2844933 | 92188 | None | SS88 | 18) Chain pulley block 5 ton capacity | No | 49366.47 | 49366.47 | 1.0 | False | None | None | False | None | False | 49366.47 | 0 | 2844934 | 92188 | None | SS89 | 19) Hydraulic jack 5T capacity | No | 8316.64 | 8316.64 | 4.0 | False | None | None | False | None | False | 33266.56 | 0 | 2844935 | 92188 | None | SS90 | 20) Pipe derrick suitable for lifting 3 MT and lift of 6 Mtr. Height | No | 32840.58 | 32840.58 | 1.0 | False | None | None | False | None | False | 32840.58 | 0 | 2844936 | 92188 | None | SS91 | 21) Allen keys | Set | 564.04 | 564.04 | 1.0 | False | None | None | False | None | False | 564.04 | 0 | 2844937 | 92188 | None | SS92 | 22) Box spanners | Set | 5271.05 | 5271.05 | 1.0 | False | None | None | False | None | False | 5271.05 | 0 | 2844938 | 92188 | None | SS93 | 23) Transil oil di-electric break down (with 2.5 mm gap 0-60 kV) Tester. | No | 119811.3 | 119811.3 | 1.0 | False | None | None | False | None | False | 119811.3 | 0 | 2844939 | 92188 | None | SS94 | 24) Insulation megger 2.5 - 5 kV | No | 65263.44 | 65263.44 | 1.0 | False | None | None | False | None | False | 65263.44 | 0 | 2844940 | 92188 | None | SS95 | 25) Insulation megger 500 V | No | 20775.08 | 20775.08 | 1.0 | False | None | None | False | None | False | 20775.08 | 0 | 2844941 | 92188 | None | SS96 | 26) SF-6 gas leak Detector | No | 76985.56 | 76985.56 | 1.0 | False | None | None | False | None | False | 76985.56 | 0 | 2844942 | 92188 | None | SS97 | 27) Multimeter electromechanical | No | 4335.32 | 4335.32 | 1.0 | False | None | None | False | None | False | 4335.32 | 0 | 2844943 | 92188 | None | SS98 | 28) Multimeter Electronic | No | 9429.38 | 9429.38 | 1.0 | False | None | None | False | None | False | 9429.38 | 0 | 2844944 | 92188 | None | SS99 | 29) Hydrometer | No | 776.44 | 776.44 | 1.0 | False | None | None | False | None | False | 776.44 | 0 | 2844945 | 92188 | None | SS100 | 30) DC Voltmeter range -5V to + 5V | No | 3186.0 | 3186.0 | 1.0 | False | None | None | False | None | False | 3186.0 | 0 | 2844946 | 92188 | None | SS101 | 31) Hydrometer syring suitable for vent holes | No | 1062.0 | 1062.0 | 1.0 | False | None | None | False | None | False | 1062.0 | 0 | 2844947 | 92188 | None | SS102 | 32) Specific gravity correction chart | No | 1008.0 | 1008.0 | 1.0 | False | None | None | False | None | False | 1008.0 | 0 | 2844948 | 92188 | None | SS103 | 33) Thermometer with wall mounting holder | No | 3186.0 | 3186.0 | 1.0 | False | None | None | False | None | False | 3186.0 | 0 | 2844949 | 92188 | None | SS104 | 34) Rubber appron | No | 2256.16 | 2256.16 | 1.0 | False | None | None | False | None | False | 2256.16 | 0 | 2844950 | 92188 | None | SS105 | 35) Pippette | No | 929.84 | 929.84 | 1.0 | False | None | None | False | None | False | 929.84 | 0 | 2844951 | 92188 | None | SS106 | 36) Protective goggle | No | 1062.0 | 1062.0 | 1.0 | False | None | None | False | None | False | 1062.0 | 0 | 2844952 | 92188 | None | SS107 | 37) Acid resisting jars (4 pint capacity) | No | 1062.0 | 1062.0 | 1.0 | False | None | None | False | None | False | 1062.0 | 0 | 2844953 | 92188 | None | SS108 | 38) Rubber shoes knee height | Pairs | 2522.84 | 2522.84 | 2.0 | False | None | None | False | None | False | 5045.68 | 0 | 2844954 | 92188 | None | SS109 | 39) Glass funnel | No | 797.68 | 797.68 | 2.0 | False | None | None | False | None | False | 1595.36 | 0 | 2844955 | 92188 | None | SS110 | 40) Grounding sticks extendable upto 18ft-3 nos. of each 6ft sticks of 3 phase R,Y,B (3 nos. of 1 set) | Set | 2070.9 | 2070.9 | 6.0 | False | None | None | False | None | False | 12425.4 | 0 | 2844956 | 92188 | None | SS111 | 41) Wall mounting type holder for hydrometer | No | 3186.0 | 3186.0 | 1.0 | False | None | None | False | None | False | 3186.0 | 0 | 2844957 | 92188 | None | SS112 | Furniture for Control Room Staff and Maintenance Staff :
a) Steel Almirahs 6.5 feet | No | 11800.0 | 11800.0 | 2.0 | False | None | None | False | None | False | 23600.0 | 0 | 2844958 | 92188 | None | SS113 | b) Steel Almirahs 6.5 feet with glass panel doors | No | 9440.0 | 9440.0 | 1.0 | False | None | None | False | None | False | 9440.0 | 0 | 2844959 | 92188 | None | SS114 | c) Officer's Tables | No | 10620.0 | 10620.0 | 2.0 | False | None | None | False | None | False | 21240.0 | 0 | 2844960 | 92188 | None | SS115 | d) Steel Slotted Angle rack (big size) | No | 2950.0 | 2950.0 | 4.0 | False | None | None | False | None | False | 11800.0 | 0 | 2844961 | 92188 | None | SS116 | f) Steel Slotted Angle rack (small size) | No | 2360.0 | 2360.0 | 4.0 | False | None | None | False | None | False | 9440.0 | 0 | 2844962 | 92188 | None | SS117 | g) Steel Dust bins | No | 472.0 | 472.0 | 4.0 | False | None | None | False | None | False | 1888.0 | 0 | 2844963 | 92188 | None | SS118 | h) Executive revolving chairs | No | 9440.0 | 9440.0 | 2.0 | False | None | None | False | None | False | 18880.0 | 0 | 2844964 | 92188 | None | SS119 | i) S Type arm chairs | No | 1770.0 | 1770.0 | 6.0 | False | None | None | False | None | False | 10620.0 | 0 | 2844965 | 92188 | None | SS120 | j) Steel folding chairs | No | 590.0 | 590.0 | 4.0 | False | None | None | False | None | False | 2360.0 | 0 | 2844966 | 92188 | None | SS121 | Miscellaneous items: Miscellaneous items like rubber mats, first aid box, danger boards, shock treatment charts, water filter, door locks, fixograph, sub-station name board, and other sundry items (sizes / capacities to be got approved)
Rubber mats 2000mmX1000mm X 12mm size suitable for 15kV class | No | 3540.0 | 3540.0 | 6.0 | False | None | None | False | None | False | 21240.0 | 0 | 2844967 | 92188 | None | SS122 | First aid box | No | 590.0 | 590.0 | 1.0 | False | None | None | False | None | False | 590.0 | 0 | 2844968 | 92188 | None | SS123 | Shock treatment charts, hard board, laminated with coloured pictures & literature both in Kannada & English. | No | 2360.0 | 2360.0 | 1.0 | False | None | None | False | None | False | 2360.0 | 0 | 2844969 | 92188 | None | SS124 | Water filter/ Water purifier: Wall mounting type (Aqua - guard type) | No | 21240.0 | 21240.0 | 1.0 | False | None | None | False | None | False | 21240.0 | 0 | 2844970 | 92188 | None | SS125 | Sub-station name board duly painted as per specification including erection & Civil Works. | No | 11800.0 | 11800.0 | 1.0 | False | None | None | False | None | False | 11800.0 | 0 | 2844971 | 92188 | None | SS126 | Supply and fixing of Fixograph of size 1.5m X 2.5m with English/ Kannada alphabets. | Set | 6136.0 | 6136.0 | 1.0 | False | None | None | False | None | False | 6136.0 | 0 | 2844972 | 92188 | None | SS127 | Door locks 7 levers (Navtal make) | No | 590.0 | 590.0 | 5.0 | False | None | None | False | None | False | 2950.0 | 0 | 2844973 | 92188 | None | SS128 | Danger board ( prohibited ) with support structure including fixing in front of the gate | No | 2360.0 | 2360.0 | 1.0 | False | None | None | False | None | False | 2360.0 | 0 | 2844974 | 92188 | None | SS129 | Equipments name plates and earthing name plates including fixing at outdoor yard | LS | 11800.0 | 11800.0 | 2.0 | False | None | None | False | None | False | 23600.0 | 0 | 2844975 | 92188 | None | SS130 | Station yard lighting (outdoor):
Design of Station Yard illumination in Confirmity with the illumination levels mentioned in the Technical Specification of Station Yard illumination materials / equipments including lamp post (fabricated Galvanised structures), Illumination fittings, Control Gear, UG/OH cables, Conduit Pipes, Control Boxes, etc., including necessary Eection & Civil works, complete for the following Sub-Stations.
Establishing 1x10MVA, 110/11kV sub-station at Hireharkuni(B Taralaghatta) in Kundagol Taluk, Dharwad district | LS | 354000.0 | 354000.0 | 1.0 | False | None | None | False | None | False | 354000.0 | 0 |
| 1709119905000 | 0 | None | None | Sub-Station | LINE SUPPLY | 58494312.0 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
2844976 | 92189 | None | LS1 | LINE SUPPLY PORTION
Total weight of the Towers - Mild Steel
(excluding Bolts & nuts)
(Added Sl. No. SS18 - from Station Supply portion) | MT | 159913.6 | 159913.6 | 163.3719 | False | None | None | False | None | False | 26125388.66784 | 0 | 2844977 | 92189 | None | LS2 | Total weight of the Towers - High Tensile Steel
(excluding Bolts & nuts) | MT | 175619.4 | 175619.4 | 90.4893 | False | None | None | False | None | False | 15891676.57242 | 0 | 2844978 | 92189 | None | LS3 | Total weight of the Towers- Bolts, nuts & washers
(Added Sl. No. SS19 - Station Supply portion) | MT | 168480.4 | 168480.4 | 10.826 | False | None | None | False | None | False | 1823968.8104 | 0 | 2844979 | 92189 | None | LS4 | Tower Accessories
a) Anti Climbing Devices (Set) as per specification - For 110kV DC Towers | Set | 4862.78 | 4862.78 | 59.0 | False | None | None | False | None | False | 286904.02 | 0 | 2844980 | 92189 | None | LS5 | b) Number Plates (1 No. per tower) | No | 375.24 | 375.24 | 59.0 | False | None | None | False | None | False | 22139.16 | 0 | 2844981 | 92189 | None | LS6 | c) Caution Plates (1 No. per tower) | No | 375.24 | 375.24 | 59.0 | False | None | None | False | None | False | 22139.16 | 0 | 2844982 | 92189 | None | LS7 | d) Circuit Plates | No | 375.24 | 375.24 | 61.0 | False | None | None | False | None | False | 22889.64 | 0 | 2844983 | 92189 | None | LS8 | e) Phase Plates (Set of 3 Nos.) | Set | 311.52 | 311.52 | 61.0 | False | None | None | False | None | False | 19002.72 | 0 | 2844984 | 92189 | None | LS9 | f) Grounding of towers including cost of 40 mm dia 2.5 mm thick, class 'C' G.I. Pipe of 3 metres length as per specification with 50 X 6 mm GI Flats 3 metre long, salt, charcoal, including excavation charges | Set | 6164.32 | 6164.32 | 59.0 | False | None | None | False | None | False | 363694.88 | 0 | 2844985 | 92189 | None | LS10 | Earth Bonds - (i) 300mm long | No | 553.42 | 553.42 | 33.0 | False | None | None | False | None | False | 18262.86 | 0 | 2844986 | 92189 | None | LS11 | ii) 450mm long | No | 634.84 | 634.84 | 26.0 | False | None | None | False | None | False | 16505.84 | 0 | 2844987 | 92189 | None | LS12 | Conductor:
Lynx ACSR conductor | Km | 226560.0 | 226560.0 | 39.8317 | False | None | None | False | None | False | 9024269.952 | 0 | 2844988 | 92189 | None | LS13 | b. Groundwire ACSR conductor | Km | 103840.0 | 103840.0 | 13.4599 | False | None | None | False | None | False | 1397676.016 | 0 | 2844989 | 92189 | None | LS14 | INSULATOR STRINGS :110kV lines:
A. Tension insulator strings consisting of any one of the following:
a. Insulator string consisting of 1X8nos. of 90kN Disc insulators
Or
b. Porcelain long rod insulator string equivalent to 1x8nos. of 90kN Disc insulators
Or
c. Silicon rubber composite insulator equivalent to 1X8nos. of 90kN Disc insulators | Strings | 5597.92 | 5597.92 | 186.0 | False | None | None | False | None | False | 1041213.12 | 0 | 2844990 | 92189 | None | LS15 | B. Suspension insulator strings consisting of any one of the following:
a. Insulator string consisting of 1X7nos. of 90kN Disc insulators
Or
b. Porcelain long rod insulator string equivalent to 1X7nos. of 90kN Disc insulators
Or
c. Silicon rubber composite insulator equivalent to 1X7nos. of 90kN Disc insulators) | Strings | 4898.18 | 4898.18 | 150.0 | False | None | None | False | None | False | 734727.0 | 0 | 2844991 | 92189 | None | LS16 | Insulator Hardwares suitable for LYNX ACSR Condyctor:
i) 110kV Clamps, Arcing Horns and Hardwares (Set) suitable for Single Tension String using 8Nos. 90KN EMS, Disc Insulators | Set | 1936.38 | 1936.38 | 162.0 | False | None | None | False | None | False | 313693.56 | 0 | 2844992 | 92189 | None | LS17 | ii) 110kV Clamps, Arcing Horns and Hardwares (Set) suitable for Double Tension String fittings using 2x8Nos. 90KN EMS, Disc Insulators | Set | 5511.78 | 5511.78 | 12.0 | False | None | None | False | None | False | 66141.36 | 0 | 2844993 | 92189 | None | LS18 | iii) 110kV Clamps, Arcing Horns and Hardwares (Set) suitable for Single Suspension String fittings using 7Nos. of 90KN EMS, Disc Insulators | Set | 2351.74 | 2351.74 | 90.0 | False | None | None | False | None | False | 211656.6 | 0 | 2844994 | 92189 | None | LS19 | iv) 110kV Clamps, Arcing Horns and Hardwares (Set) suitable for Double Suspension String fittings using 2x7Nos. of 90KN EMS, Disc Insulators | Set | 4486.36 | 4486.36 | 30.0 | False | None | None | False | None | False | 134590.8 | 0 | 2844995 | 92189 | None | LS20 | Accessories for ACSR Lynx conductor:
a) Mid Span Compression Joint | Nos | 788.24 | 788.24 | 20.0 | False | None | None | False | None | False | 15764.8 | 0 | 2844996 | 92189 | None | LS21 | b) Preformed armour rod | Nos | 1490.34 | 1490.34 | 120.0 | False | None | None | False | None | False | 178840.8 | 0 | 2844997 | 92189 | None | LS22 | c) Repair sleeves | Nos | 698.56 | 698.56 | 20.0 | False | None | None | False | None | False | 13971.2 | 0 | 2844998 | 92189 | None | LS23 | d) P.G. Clamps | Nos | 915.68 | 915.68 | 168.0 | False | None | None | False | None | False | 153834.24 | 0 | 2844999 | 92189 | None | LS24 | e) Vibration dampers | Nos | 1196.52 | 1196.52 | 366.0 | False | None | None | False | None | False | 437926.32 | 0 | 2845000 | 92189 | None | LS25 | Hardware & Accessories for Ground Wire:
a) Mid Span Compression joint | Nos | 539.26 | 539.26 | 7.0 | False | None | None | False | None | False | 3774.82 | 0 | 2845001 | 92189 | None | LS26 | b) Repair sleeves | Nos | 364.62 | 364.62 | 7.0 | False | None | None | False | None | False | 2552.34 | 0 | 2845002 | 92189 | None | LS27 | c) P.G. Clamps | Nos | 475.53 | 475.53 | 52.0 | False | None | None | False | None | False | 24727.56 | 0 | 2845003 | 92189 | None | LS28 | d) Single Tension clamps (Bolted type) | Nos | 1456.12 | 1456.12 | 52.0 | False | None | None | False | None | False | 75718.24 | 0 | 2845004 | 92189 | None | LS29 | e) Suspension clamps(bolted type) | Nos | 1535.18 | 1535.18 | 33.0 | False | None | None | False | None | False | 50660.94 | 0 |
| 1709119905000 | 0 | None | None | Sub-Station | Station Mandatory spares Supply portion | 163949.0 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
2845005 | 92190 | None | SM1 | Circuit Breaker (CB)
Closing coil with resistor (For one Complete Circuit Breaker)
a) for 123KV CB | Set | 10253.0 | 10253.0 | 1.0 | False | None | None | False | None | False | 10253.0 | 0 | 2845006 | 92190 | None | SM2 | Tripping coil with resistor (For one Complete Circuit Breaker)
a) for 123KV CB | Set | 11610.0 | 11610.0 | 1.0 | False | None | None | False | None | False | 11610.0 | 0 | 2845007 | 92190 | None | SM3 | Terminal Pad (For one Complete Circuit Breaker)
a) for 123KV CB | Set | 11091.0 | 11091.0 | 1.0 | False | None | None | False | None | False | 11091.0 | 0 | 2845008 | 92190 | None | SM4 | Terminal Connector (For one Complete Circuit Breaker)
a) for 123KV CB | Set | 9588.0 | 9588.0 | 1.0 | False | None | None | False | None | False | 9588.0 | 0 | 2845009 | 92190 | None | SM5 | SF6 Gas (40% of total gas Qty. for Sub-Station at Hireharkuni) | LS | 51029.0 | 51029.0 | 1.0 | False | None | None | False | None | False | 51029.0 | 0 | 2845010 | 92190 | None | SM6 | Isolator :
Copper Contract fingers male & female (For one Complete Isolator)
a) for 123KV Class | Set | 52624.0 | 52624.0 | 1.0 | False | None | None | False | None | False | 52624.0 | 0 | 2845011 | 92190 | None | SM7 | Terminal Connector (For one Complete Isolator)
a) for 123KV Class | Set | 8961.0 | 8961.0 | 1.0 | False | None | None | False | None | False | 8961.0 | 0 | 2845012 | 92190 | None | SM8 | Terminal Pad (For one Complete Isolator)
a) for 123KV Class | Set | 8793.0 | 8793.0 | 1.0 | False | None | None | False | None | False | 8793.0 | 0 |
| 1709119905000 | 1 | None | None | Sub-Station | Station Erection portion | 3316045.74 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
2845013 | 92191 | None | SE1 | 10 MVA, 110/11 KV, Delta/Star, Dyn11, 3 Ph, 50 Hz, Core type, 2 winding Delta/Star,
Vector Group: Dyn11, OLTC, RTCC Panel, first
filling of oil and 10% spare oil, etc., complete with
Terminal connectors on primary side suitable for Drake ACSR conductor and secondary side suitable for AAAC Moose/2 nos. of 50x8 mm copper flats for each phase from LV side of transformer to cable at 11kV cable terminating structure with suitable support insulator on LV side of transformer and Neutral connectors suitable for 2 Nos. of 50mm x 8mm Copper Flats. | No | 268894.86 | 268894.86 | 1.0 | False | None | None | False | None | False | 268894.86 | 0 | 2845014 | 92191 | None | SE2 | Circuit Breaker :
SF6 Gas circuit breaker with Semi-Pneumatic / Pneumatic operated / Spring type operating mechanism, including mounting arrangements, rigid bi-metallic terminal connector complete suitable for Drake ACSR conductor and mounting structures as per KPTCL Technical specification
110kV, 1250A,40KA Class
a) For 110kV Transformer
b) For 110kV Line | No | 62675.7 | 62675.7 | 2.0 | False | None | None | False | None | False | 125351.4 | 0 | 2845015 | 92191 | None | SE3 | Isolators : Isolators including marshalling box and suitable terminal connectors, as required as per technical specification with solid core cylindrical post insulators: as per KPTCL Technical specification
A) 110KV, 1250A, 40KA Class Double Break Manually operated isolator With terminal connectors suitable for Drake ACSR.
a) Upright mounting type with earth switch with live point height 4600mm
b) Upright mounting type without earth switch with live point height 4600 mm | Set | 11802.36 | 11802.36 | 6.0 | False | None | None | False | None | False | 70814.16 | 0 | 2845016 | 92191 | None | SE4 | B) 11KV Isolators:
i) 11KV isolators, Double Break 400A, 25KA capacity with rigid bi-metallic terminal connectors suitable for Coyote ACSR.
ii) 11KV isolators, Single break 400A, 25KA capacity with Roster switch with rigid bi-metallic terminal connectors suitable for Coyote ACSR. | Set | 1432.52 | 1432.52 | 6.0 | False | None | None | False | None | False | 8595.12 | 0 | 2845017 | 92191 | None | SE5 | Current Transformer : Current Transformer including Marshalling box, Single phase, oil filled outdoor type with rigid bimetallic terminal connectors suitable for Drake ACSR.
i) 110 KV Class, 31.5 KA, CT of ratio 400-200/1-1-1A for Lines.
For metering: Accuracy 0.2s, Burden 10VA
For back up protection : Accuracy class 5P20, Burden 30VA
For differential/ distance protection:Accuracy class- PS, Vk 800V, Rct 4ohm at 400/1A
ii)110 KV Class, 31.5 KA, CT of ratio 200-100/1-1-1A for Transformers.
For metering: Accuracy class- 0.2s, Burden 10VA
For back up protection : Accuracy class - 5P20, Burden 30VA
For differential/ distance protection: Accuracy class-PS, Vk-400V, Rct 2ohm at 200/1A | No | 8061.36 | 8061.36 | 6.0 | False | None | None | False | None | False | 48368.16 | 0 | 2845018 | 92191 | None | SE6 | iii) 11 KV Class, 25KA,NCT of ratio 1200-800/1-1A for REFR Protection. (of similar rating and ratio as that of Incomer of 11kV Switchgear) with terminal connector suitable for 2 Nos. of 50x8mm Copper flats.
Note:
1) For details refer Annexure-IIB: Technical parameters of Current transformers for type and rating attached at the end of this schedule.
2) All the Current transformers in each KV class shall be of One and the same make for interchangeability and reliability of performance.
3) The make and characteristics of 11kV NCT should be the same as that of the incomer CT of 11kV Switchgear
4) The Terminal connectors for 11kV NCT shall be suitable for 50X8mm Copper flat. | No | 3294.95 | 3294.95 | 1.0 | False | None | None | False | None | False | 3294.95 | 0 | 2845019 | 92191 | None | SE7 | Voltage Transformer:
a) Voltage Transformer 110kV, Single Phase, Oil filled outdoor type including marshalling box with rigid bimetallic terminal connectors suitable for drake ACSR as per technical specification. Ratio : 110kV/root3 / 110V/root3 - 110V/root3 - 110V/root3
Core-1: 300 VA, Accuracy class 0.2, metering.
Core-2: 200VA, Accuracy class 3P, protection
Core-3: 50VA, Accuracy class 3P, open delta protection. | No | 8099.12 | 8099.12 | 3.0 | False | None | None | False | None | False | 24297.36 | 0 | 2845020 | 92191 | None | SE8 | Lightning Arrestor :
Surge arrestors (Porcelain housing) Metal Oxide Gap less type as per technical specification with suitable rigid bi-metallic terminal connectors suitable for Drake ACSR.
i) 96 KV, 10 KA, Class - II, Heavy duty metal oxide type | No | 523.92 | 523.92 | 9.0 | False | None | None | False | None | False | 4715.28 | 0 | 2845021 | 92191 | None | SE9 | ii) 9 KV, 5KA Station Class with connector and clamps | No | 46.81 | 46.81 | 18.0 | False | None | None | False | None | False | 842.58 | 0 | 2845022 | 92191 | None | SE10 | Control Panels :
Simplex Type Control and Relay Panel complete as per specifications (Control Voltage 110 V DC). (SCADA compatible)
NOTE :
1) All the C&R panels and associated panels shall be of one and same make for uniformity and interchangeability of components.
2) The accuracy class of metering core of CT's shall be 0.2s accuracy class, VTs and Electronic trivector meters of C&R panels shall be 0.2 accuracy class, irrrespective of what has been indicated else where in the bid documents.
3) The Electronic Trivector meters with 0.2s accuracy class with ABT & TOD features & DLMS compliant has to be provided both on HV side and LV side of Transformer.
4) All numerical relays shall conform to IEC 61850 protocol.
a) For Power Transformer 10 MVA, 110/11 KV
b) For 110 KV Transmission line. | No | 57739.76 | 57739.76 | 2.0 | False | None | None | False | None | False | 115479.52 | 0 | 2845023 | 92191 | None | SE11 | Total Station & Mounting Structure MS weight | t | 6753.13 | 6753.13 | 20.034 | False | None | None | False | None | False | 135292.20642 | 0 | 2845024 | 92191 | None | SE12 | Total Bolt-Nut Weight for Station & Mounting Structures | t | 6753.13 | 6753.13 | 1.312 | False | None | None | False | None | False | 8860.10656 | 0 | 2845025 | 92191 | None | SE13 | iii) Supplying & Erection of D.P. Structure with all accessories using 9.0mtrs long, 145Kg WL RCC poles including H frame suitable for mounting roaster GOS / DB GOS with provision for fixing 9KV lightning arrestors etc., complete set with wiring materials. | No | 3774.81 | 3774.81 | 5.0 | False | None | None | False | None | False | 18874.05 | 0 | 2845026 | 92191 | None | SE14 | Formation of Main/Cross bus with Single Drake /
Note: The scope also includes installing insulator strings complete with necessary hardwares and stringing of the conductor/earthwire etc., | No | 14262.66 | 14262.66 | 4.0 | False | None | None | False | None | False | 57050.64 | 0 | 2845027 | 92191 | None | SE15 | Insulators :
i) Post insulators solid core 110 KV Class
1Unit/Stack | No | 523.92 | 523.92 | 15.0 | False | None | None | False | None | False | 7858.8 | 0 | 2845028 | 92191 | None | SE16 | Auxiliary Transformer:
Station Auxiliary Transformer with oil, outdoor type, 100 kVA, 11 kV/433 V, 3 Ph, Vector group Dyn11, off load tap changer (with 5 taps) with step voltage of 2.5%, as per specifications. | Set | 21938.56 | 21938.56 | 1.0 | False | None | None | False | None | False | 21938.56 | 0 | 2845029 | 92191 | None | SE17 | Supply & erection of Double pole structure with 9 Mtrs RCC poles and with 11KV, 400A double break isolators, H-Frame and 9KV, 5KA surge arrestors (3 Nos), auxiliary transformer including materials such as DPset, H-Frame, GOS, HG Fuse unit, angle for fixing HG fuse unit (2 pole clamps bolts & nuts), PIN Insulator, PIN for insulator, LTD box, Trivector Meter, 9kV LA) etc. | Set | 8752.06 | 8752.06 | 1.0 | False | None | None | False | None | False | 8752.06 | 0 | 2845030 | 92191 | None | SE18 | LTAC panel (indoor): 415V, as per technical specification comprising of Voltmeter, Ammeter, & 1No. ETV meter. 1No, I/C MCCB 200A+2Nos .3 phase 63A OG HRC fuse+ 2nos. 3 phase 32A OG HRC fuse+ 6Nos. 3 phase,16A HRC fuse etc,. Complete as per technical specification. | No | 3784.26 | 3784.26 | 1.0 | False | None | None | False | None | False | 3784.26 | 0 | 2845031 | 92191 | None | SE19 | B) A.C. Distribution Box (Outdoor) :
AC distribution box single front type, 6 terminals, 1200x1350x300 mm, 1 I/C of 100A, MCCB 20KA + 6 O/G MCB 16A + 1 O/G of 100A , HRC fuse | No | 2909.88 | 2909.88 | 2.0 | False | None | None | False | None | False | 5819.76 | 0 | 2845032 | 92191 | None | SE20 | LT Power armoured UG cable as per specification.
a) 1.1 KV, 4 X 95 Sqmm Aluminium, cable with glands/lugs/ferrules
b) 1.1 KV, 4 X 25 Sqmm Copper, cable with glands/lugs/ferrules
c) 1.1 KV, 4 X 10 Sqmm Copper, cable with glands/lugs/ferrules | m | 17.7 | 17.7 | 450.0 | False | None | None | False | None | False | 7965.0 | 0 | 2845033 | 92191 | None | SE21 | Station Battery:
110V, 200AH Battery set (Plante/Grid/Nickel Cadmium Type) consists of 55 Nos. of cells with accessories as per specification. | Set | 13712.77 | 13712.77 | 1.0 | False | None | None | False | None | False | 13712.77 | 0 | 2845034 | 92191 | None | SE22 | Station Battery charger: Battery charger suitable for 110V, 200AH, Battery set (Plante/Grid/Nickel Cadmium Type) consisting of 55 No. cells with Float Cum Booster type battery charger as per specification | Set | 37354.08 | 37354.08 | 1.0 | False | None | None | False | None | False | 37354.08 | 0 | 2845035 | 92191 | None | SE23 | DC Distribution Panel (Indoor type) as per Technical specification comprising of Earth fault indicator, Indication circuit for AC main failure, 1 No. 100A SFU for IC + 12 Nos., 32A SFU for OG etc., complete. | No | 2909.88 | 2909.88 | 1.0 | False | None | None | False | None | False | 2909.88 | 0 | 2845036 | 92191 | None | SE24 | Copper Control Cables:
1.1kV PVC insulated Copper Control Cable with Lugs/Ferrules as per technical specifications.
i) 19 C x 2.5 Sqmm
ii) 4 C x 6.0 Sqmm
iii) 4 C x 2.5 Sqmm
iv) 2 C x 2.5 Sqmm
v) 2 C x 6.0 Sqmm
vi)10CX2.5 Sqmm | m | 17.7 | 17.7 | 4950.0 | False | None | None | False | None | False | 87615.0 | 0 | 2845037 | 92191 | None | SE25 | 11KV Switchgear :
11kV, 500MVA Metal Clad VCB Switchgear (1600A for Incomer and 1250A for feeders), outdoor type comprising of 1I/C+6F+1CB+1AP (Remote Announciation cum Control panel) with CTs & PTs and terminal connectors suitable for Drake / Coyote ACSR etc., complete as per technical specification.
Note: 1. The switchgear for capacitor bank shall have necessary Over voltage / Under voltage / Circulating current relays and other protection relays as per specification
2. The Remote Announciation cum Control panel is Simplex type.
3. The Electronic Trivector meters with ABT features has to be provided. | Set | 107477.94 | 107477.94 | 1.0 | False | None | None | False | None | False | 107477.94 | 0 | 2845038 | 92191 | None | SE26 | 11KV U.G. Cable with the required cable terminations at both ends.
a) One run of 11kV, XLPE 95 sq.mm Al., 3 core cable - (to be run for Auxiliary Transformers from 11KV switch Gear to Auxiliary Transformer ).
b) 11KV XLPE cable, 1000Sq. mm. (2runs of 1Cx1000Sqmm)Aluminium cable from transformers to 11KV Switchgear.
c) 11KV XLPE cable, 240Sq. mm. Aluminium cable 3 Core to be run from 11KV Switchgear to 11kV take off DP Structure. | Mtr | 84.96 | 84.96 | 400.0 | False | None | None | False | None | False | 33984.0 | 0 | 2845039 | 92191 | None | SE27 | d) Heat Shrinkable type Cable Termination kits suitable for following sizes as per Technical Specification.
i) 95 Sq mm 3 core
ia) Indoor
ib) Outdoor | Nos | 3136.44 | 3136.44 | 2.0 | False | None | None | False | None | False | 6272.88 | 0 | 2845040 | 92191 | None | SE28 | ii) 1000Sq mm Single core
iia) Indoor
iib) Outdoor | Nos | 4427.36 | 4427.36 | 8.0 | False | None | None | False | None | False | 35418.88 | 0 | 2845041 | 92191 | None | SE29 | ii) 240Sq mm 3 core
iia) Indoor
iib) Outdoor | Nos | 3136.44 | 3136.44 | 12.0 | False | None | None | False | None | False | 37637.28 | 0 | 2845042 | 92191 | None | SE30 | Equipment required for establishing SCADA Communication as per KPTCL specification
Note: 1. Satellite communication required will be arranged by SLDC
2. The detailed BOM & specification of SCADA equipment shall be obtained from SEE-SCADA
a) Remote Terminal Unit (RTU) | No | 30195.02 | 30195.02 | 1.0 | False | None | None | False | None | False | 30195.02 | 0 | 2845043 | 92191 | None | SE31 | b) Data Concentrator Unit (DCU) | No | 14278.0 | 14278.0 | 1.0 | False | None | None | False | None | False | 14278.0 | 0 | 2845044 | 92191 | None | SE32 | c) 2kVA online UPS (230V AC 1Phase 50Hz) | No | 7651.12 | 7651.12 | 1.0 | False | None | None | False | None | False | 7651.12 | 0 | 2845045 | 92191 | None | SE33 | 4)Integration of RTU,DCU and UPS with field equipments
Note:Bidder has to quote only for erection charges | No | 31872.98 | 31872.98 | 1.0 | False | None | None | False | None | False | 31872.98 | 0 | 2845046 | 92191 | None | SE34 | Supply & Laying of following Power cables for SCADA.
i) Current Cables - copper core with c/s 4.0sqmm multistrand 4 core
ii) Voltage Cables-Copper core with c/s 2.5sqmm multistrand 4core
iii) Signal cables- armoured copper core with c/s 0.5sqmm multistrand 10core
iv) Control cables - copper core with c/s 1.5sqmm multistrand 10core
v) Control cables-copper core with c/s 4.0sqmm multistrand 3core for AC input to UPS & UPS to RTU, confirming to KPTCL specifications.
vi) Control cables-copper core with c/s 32.0sqmm multistrand for Battery conforming to KPTCL specifications. | m | 17.7 | 17.7 | 765.0 | False | None | None | False | None | False | 13540.5 | 0 | 2845047 | 92191 | None | SE35 | Materials for new bay integration to existing SCADA panel
i)RJ-45 cable for Energy meter integration to DCU | m | 17.7 | 17.7 | 5.0 | False | None | None | False | None | False | 88.5 | 0 | 2845048 | 92191 | None | SE36 | Earth mat formation:
Supplying, Laying and welding of M.S.Flats 50x6mm, applying ACB paint to welded portion as per approved drawing,/standard specification & consolidation and directions of engineer incharge of work. | m | 236.0 | 236.0 | 2660.0 | False | None | None | False | None | False | 627760.0 | 0 | 2845049 | 92191 | None | SE37 | b) Supplying and Grounding of equipment with
50 x 6 mm G.I. Flat and connecting equipment to the earthmat/ground pit. Each point of earthing with all formation works like bending, twisting, drilling of holes and connecting by welding (inclusive of all T&P and consumables) to the earthmat/ground pit/point of earth connection, all the materials supplied by the contractor | m | 395.3 | 395.3 | 1300.0 | False | None | None | False | None | False | 513890.0 | 0 | 2845050 | 92191 | None | SE38 | c) Supplying and Providing 25mm dia M.S.Rod 1.05m long earthmat spikes including heating, bending top 50mm overlap flattening and making spike edge at one end driving into the earth below the ground level and welding the rod with ground mat flat with necessary earth work. | Each | 534.54 | 534.54 | 62.0 | False | None | None | False | None | False | 33141.48 | 0 | 2845051 | 92191 | None | SE39 | d) Grounding of equipments by providing cast iron pipe of 100mm ID 13mm thickness, 2.75mtrs long with 2 part clamp out of G.I.Flat 50x6mm continuously welded around the pipe using cast iron welding electrodes as per drawing including the cost of excavation, providing & laying homogeneous mixture of charcoal lumps, salt & sand all round the pipe as per specification. | No | 19213.94 | 19213.94 | 35.0 | False | None | None | False | None | False | 672487.9 | 0 | 2845052 | 92191 | None | SE40 | e) Supplying & providing 450 mm dia 450 mm height 1.5" to 2" thick hume pipe collar (nonpressure type) for earth pits including all lead and lifts etc., | No | 1768.82 | 1768.82 | 35.0 | False | None | None | False | None | False | 61908.7 | 0 |
| 1709119905000 | 1 | None | None | Sub-Station | Line Erection portion | 3758666.8 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
2845053 | 92192 | None | LE1 | SURVEY : Check survey & tower spotting. for all types of terrain Check survey using their own equipment for Plain terrain | Km | 3426.72 | 3426.72 | 13.081 | False | None | None | False | None | False | 44824.92432 | 0 | 2845054 | 92192 | None | LE2 | Installing insulator strings complete with necessary Hardwares, Installing and stringing of ACSR Lynx conductor including fixing of conductor accessories etc., Note :- The tenderers are required to quote the rates taking in to consideration the charges for loading and unloading of ACSR conductor, Insulators and Hardwares. | Km | 9440.0 | 9440.0 | 39.243 | False | None | None | False | None | False | 370453.92 | 0 | 2845055 | 92192 | None | LE3 | b) Installing and stringing of 7/3.15 mm earthwire including fixing of earth wire accessories and hardwares. Note :- The tenderers are required to quote the rates taking in to consideration the charges for loading and unloading of ACSR conductor / Ground Wire, Insulators and Hardwares. | Km | 12980.0 | 12980.0 | 13.081 | False | None | None | False | None | False | 169791.38 | 0 | 2845056 | 92192 | None | LE4 | Erection of Towers including tack welding, fixing of tower accessories , Anti Climbing Devices, earthing & technical specifications (The weight includes the wt. of std., tower & stubs, including bolts nuts and washers and supplying & fixing of Barbed wire as per drawings & technical specifications ) Note :- 1. The tenders are required to quote the rates taking in to consideration the charges for sorting of towers, loading, unloading, fixing of accessories, grounding, stub setting and tack welding and supplying & fixing of Barbed wire as per drawings & technical specifications. Rate to be quoted on per MT basis. 2. For split up details refer techno commercial sheet | t | 13041.74 | 13041.74 | 243.3415 | False | None | None | False | None | False | 3173596.57421 | 0 |
| 1709119905000 | 0 | None | None | Sub-Station | CIVIL PORTION | 40235345.87 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
2845057 | 92193 | None | CVL1 | Earth work in surface excavation by mechanical means for lowering & leveling the ground for all works other than foundation in all kinds of soils & upto depth not exceeding 300mm as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenances required to complete the work.
In all kinds of soils upto 300 mm depth | Cum | 95.0 | 95.0 | 780.4 | False | None | None | False | None | False | 74138.0 | 0 | 2845058 | 92193 | None | CVL2 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work.
In all kinds of soils Depth upto 3 m | Cum | 102.0 | 102.0 | 13003.88 | False | None | None | False | None | False | 1326395.76 | 0 | 2845059 | 92193 | None | CVL3 | Construction of Embankment by excavating the available approved Gravel/Murrum deposited at a place or borrow pits during or prior excavation with all lifts and lead, transportation to site, spreading, grading to required slope and compacting to meet the requirement complete as per specifications, including cost of labour,rolling, water,all materials,usage& all other appurtenaces required to complete the work. | Cum | 474.0 | 474.0 | 1312.0 | False | None | None | False | None | False | 621888.0 | 0 | 2845060 | 92193 | None | CVL4 | Construction of Embankment by excavating the available approved Gravel/Murrum deposited at a place or borrow pits during or prior excavation with all lifts and lead, transportation to site, spreading, grading to required slope and compacting to meet the requirement complete as per specifications, including cost of labour,rolling, water,all materials,usage& all other appurtenaces required to complete the work with 3% Cement to foundation in case of BC Soil. | Cum | 488.22 | 488.22 | 800.0 | False | None | None | False | None | False | 390576.0 | 0 | 2845061 | 92193 | None | CVL5 | Refilling available earth around trenches/pipelines, cables in layers not exceeding 20 cms in depth, compacting each deposited layer by ramming after watering with a lead upto 50 m, and lift upto 1.5 m. Including cost of all labour complete as per specifications | Cum | 160.0 | 160.0 | 555.0 | False | None | None | False | None | False | 88800.0 | 0 | 2845062 | 92193 | None | CVL6 | Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, and all the other appurtenances required to complete the work as per technical specifications. Mix 1:4:8 Using 40 mm nominal size graded crushed coarse aggregates | Cum | 5664.0 | 5664.0 | 186.44 | False | None | None | False | None | False | 1055996.16 | 0 | 2845063 | 92193 | None | CVL7 | Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to complete the work as per technical specifications M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates For foundation (Raft of Columns,Retaining walls, Cable Ducts, Sump Tank) | Cum | 6475.61 | 6475.61 | 997.01 | False | None | None | False | None | False | 6456247.9261 | 0 | 2845064 | 92193 | None | CVL8 | Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to complete the work as per technical specifications M20 Design (1:1.5:3) Mix Using 20 mm nominal size graded crushed coarse aggregates- For Columns Upto plinth beam bottom. | Cum | 10687.9 | 10687.9 | 51.22 | False | None | None | False | None | False | 547434.238 | 0 | 2845065 | 92193 | None | CVL9 | Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M20 Design (1:1.5:3) Mix Using 20 mm nominal size graded crushed coarse aggregates-For Plinth beam. | Cum | 9484.5 | 9484.5 | 8.1 | False | None | None | False | None | False | 76824.45 | 0 | 2845066 | 92193 | None | CVL10 | Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to complete the work as per technical specifications M20 Design (1:1.5:3) Mix Using 20 mm nominal size graded crushed coarse aggregates-For Retaining wall alround below CR building plinth beam bottom and cable ducts , raft below retaining wall/toe wall, RCC drains, Culverts. | Cum | 6915.7 | 6915.7 | 1075.0 | False | None | None | False | None | False | 7434377.5 | 0 | 2845067 | 92193 | None | CVL11 | Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to complete the work as per technical specifications. M20 Design (1:1.5:3) Mix Using 20 mm nominal size graded crushed coarse aggregates-For RCC drains | Cum | 8487.45 | 8487.45 | 91.16 | False | None | None | False | None | False | 773715.942 | 0 | 2845068 | 92193 | None | CVL12 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M20 Design (1:1.5:3) Mix Using 20 mm nominal size graded crushed coarse aggregates - For Columns. | Cum | 11271.0 | 11271.0 | 9.64 | False | None | None | False | None | False | 108652.44 | 0 | 2845069 | 92193 | None | CVL13 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M20 Design (1:1.5:3) Mix Using 20 mm nominal size graded crushed coarse aggregates - For Lintels and Roof beams | Cum | 10608.0 | 10608.0 | 9.53 | False | None | None | False | None | False | 101094.24 | 0 | 2845070 | 92193 | None | CVL14 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M20 Design (1:1.5:3) Mix Using 20 mm nominal size graded crushed coarse aggregates - For Roof Slab,Canopy and chejja's | Cum | 9945.0 | 9945.0 | 38.08 | False | None | None | False | None | False | 378705.6 | 0 | 2845071 | 92193 | None | CVL15 | Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification Buildings | Kgs | 89.46 | 89.46 | 6000.0 | False | None | None | False | None | False | 536760.0 | 0 | 2845072 | 92193 | None | CVL16 | Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification All other type of structures | Kgs | 79.01 | 79.01 | 66575.0 | False | None | None | False | None | False | 5260090.75 | 0 | 2845073 | 92193 | None | CVL17 | Providing and fixing Structural Steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. (For Switchgear Shelter). | Kgs | 113.0 | 113.0 | 15500.0 | False | None | None | False | None | False | 1751500.0 | 0 | 2845074 | 92193 | None | CVL18 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M 40 Design Mix Using 20 mm nominal size graded crushed coarse aggregates | Cum | 7898.1 | 7898.1 | 100.0 | False | None | None | False | None | False | 789810.0 | 0 | 2845075 | 92193 | None | CVL19 | Constructing brick masonry chamber of internal dimension 600x600mm and depth of 600mm (inner dimensions) with modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plastering 12 mm thick with cement mortar 1:4, CC 1:2:4 coping 75mm thk for fixing CI cover & frame etc. And Providing & fixing cast iron cover with frame and necessary locking arrangements with M.S flats 32x6 mm etc & painting with two or more coats with black Japan paint etc. complete as directed by the engineer-in-charge. | Nos. | 7416.0 | 7416.0 | 15.0 | False | None | None | False | None | False | 111240.0 | 0 | 2845076 | 92193 | None | CVL20 | Constructing brick masonry chamber of internal dimension 450x450mm and depth of 600mm (inner dimensions) with modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plastering 12 mm thick with cement mortar 1:4, CC 1:2:4 coping 75mm thk for fixing CI cover & frame etc. And Providing & fixing cast iron cover with frame and necessary locking arrangements with M.S flats 32x6 mm etc & painting with two or more coats with black Japan paint etc. complete as directed by the engineer-in-charge. | Nos. | 6198.0 | 6198.0 | 12.0 | False | None | None | False | None | False | 74376.0 | 0 | 2845077 | 92193 | None | CVL21 | Providing Size Stone masonry with hard stone in foundation & plinth with Cement mortar 1:6 (1 cement : 6 coarse sand). | Cum | 6389.0 | 6389.0 | 500.0 | False | None | None | False | None | False | 3194500.0 | 0 | 2845078 | 92193 | None | CVL22 | Providing 20 mm cement plaster of mix :1:6 (1 cement: 6 fine sand) to brick/stone masonary including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge | Sqm | 333.0 | 333.0 | 2100.0 | False | None | None | False | None | False | 699300.0 | 0 | 2845079 | 92193 | None | CVL23 | Providing Flush/ Ruled pointing: Pointing on stone work with cement
mortar 1:3 (1 cement : 3 fine sand) after raking joints to depth nicely lining, including cost of materials, labour, curing as per specifications and as
per directions of Engineer-in-charge. | Sqm | 255.0 | 255.0 | 350.0 | False | None | None | False | None | False | 89250.0 | 0 | 2845080 | 92193 | None | CVL24 | Providing & fixing corrugated G.S. sheet roofing including vertical /curved surface fixed with polymer coated J or L hooks, bolts and nuts 8 mm diameter with bitumen and G.I. limpet washers or with G.I. limpet washers filled with white lead, including a coat of approved steel primer and two coats of pproved paint on overlapping of sheets complete as per design drawings (up to any pitch in horizontal/ vertical or curved surfaces), excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required as per the direction of Engineer in charge. | Sqm | 879.0 | 879.0 | 150.0 | False | None | None | False | None | False | 131850.0 | 0 | 2845081 | 92193 | None | CVL25 | Providing & fixing ridges or hips of width 60 cm overall width plain G.S. sheet fixed with polymer coated J or L hooks, bolts and nuts 8 mm dia G.I. limpet and bitumen washers complete as per design drawings. 0.63 mm thick with zinc coating not less than 275 g/m² | m | 639.0 | 639.0 | 15.0 | False | None | None | False | None | False | 9585.0 | 0 | 2845082 | 92193 | None | CVL26 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 167.0 | 167.0 | 75.0 | False | None | None | False | None | False | 12525.0 | 0 | 2845083 | 92193 | None | CVL27 | Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for:PVC pipes 110mm dia., 6 kg/sqcm & class 3 | m | 411.0 | 411.0 | 30.0 | False | None | None | False | None | False | 12330.0 | 0 | 2845084 | 92193 | None | CVL28 | Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for:PVC pipes 160mm dia., 6 kg/sqcm & class 3 | m | 618.0 | 618.0 | 150.0 | False | None | None | False | None | False | 92700.0 | 0 | 2845085 | 92193 | None | CVL29 | Supplying S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with latest amentments using ordinary portland cement, for sanitary works and conveying to work site, rolling and lowering into trenches, laying true to line and level including loading and unloading at both destinations and jointing of pipes and specials, perfect linking of joints with jack to correct position including cost of jointing materials, i.e, rubber rings conforming to IS: 5382 for S&S RCC pipes, with all leads and lifts as directed and giving necessary hydraulic test as per ISS to the required pressure and commissioning etc. complete. (Contractor will make his own arrangements for procuring water for testing). Before the execution of the work, the contractor shall carry out the survey. 600mm dia | m | 3140.0 | 3140.0 | 12.5 | False | None | None | False | None | False | 39250.0 | 0 | 2845086 | 92193 | None | CVL30 | Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work. | Cum | 7969.0 | 7969.0 | 60.0 | False | None | None | False | None | False | 478140.0 | 0 | 2845087 | 92193 | None | CVL31 | Providing and laying water proofing treatment to the Roof with PU based single component elastomeric pure polyurethane based coating on New terrace/Chajjas/Sunken portion of WC:Bathroom, cold applied PU waterproofing membrane that is highly elastic with elongation greater than 400% and tensile strength greater than 2MPa as per ASTM D412. The waterproofing membrane to be applied in 2coats @ 1.6 kg/m2 to achieve final DFT (Dry Film Thickness) of 1mm including prime coat of epoxy primer @150 g/m2 and protection with 120gsm Geo-textile over the waterproofing membrane. The finished cost to include surface preparation, making coving at Junction, Bore Packing, treatment of construction joints completely as per specification. | Sqm | 817.0 | 817.0 | 150.0 | False | None | None | False | None | False | 122550.0 | 0 | 2845088 | 92193 | None | CVL32 | Providing 12 mm cement plaster with cement mortar 1:4 (1 cement:4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 255.0 | 255.0 | 135.0 | False | None | None | False | None | False | 34425.0 | 0 | 2845089 | 92193 | None | CVL33 | Providing 18 mm cement plaster in two coats under layer 12 mm thick cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster with cement mortar 1:6 (1 cement : 6 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 371.0 | 371.0 | 550.0 | False | None | None | False | None | False | 204050.0 | 0 | 2845090 | 92193 | None | CVL34 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing ,curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.** Polished Granite stone slab Black, Cherry Red, Brown, Cat Eye, River Pink or equivalent. | Sqm | 2852.0 | 2852.0 | 115.0 | False | None | None | False | None | False | 327980.0 | 0 | 2845091 | 92193 | None | CVL35 | Providing and laying Polished Glazed Vitrified tiles in floor with different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS : 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). | Sqm | 1251.0 | 1251.0 | 45.0 | False | None | None | False | None | False | 56295.0 | 0 | 2845092 | 92193 | None | CVL36 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of Engineer incharge. | Sqm | 100.0 | 100.0 | 375.0 | False | None | None | False | None | False | 37500.0 | 0 | 2845093 | 92193 | None | CVL37 | Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives, New work (Two coats applied @ 1.43 litre/ 10 m². Over and including priming coat of exterior primer applied @ 0.90 litre/10 m² with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 156.0 | 156.0 | 35.0 | False | None | None | False | None | False | 5460.0 | 0 | 2845094 | 92193 | None | CVL38 | Finishing walls with water proofing cement paint of required shade :New work (Two coats applied @ 4.84 kg/10 m²) to give an even shade after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. complete. | Sqm | 89.0 | 89.0 | 360.0 | False | None | None | False | None | False | 32040.0 | 0 | 2845095 | 92193 | None | CVL39 | Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, toppers, handles, including applying a priming coat of approved steel primer including cost of materials ,labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. complete including necessary bolts and nuts. | Sqm | 8276.0 | 8276.0 | 6.0 | False | None | None | False | None | False | 49656.0 | 0 | 2845096 | 92193 | None | CVL40 | Providing & fixing 30mm thick factory made rigid foam Prelam Panelled Door Shutters made from M.S. tube of 19x19mm, 19 gauge for stiles and 15x15mm for top & bottom rails, covered with heat moulded Prelaminated PVC C Channel of 5mm thick sheet & 30x50mm wide to form stiles & 5mm thick & 75mm wide Prelaminated PVC Sheets for top rail, lock rail & bottom rail on either side & 5mm thick, 20mm wide cross PVC sheet as gap insert for top rail & bottom rail, Panelling of 5mm thick PVC sheetPrelaminated on either side fitted in the M.S. frame, Sealed to the stiles & rails with PVC Designer beading on either side & joined together with solvent cement adhesive etc., Complete as per manufacturers specification & direction of Engineer-in-charge fixed to frames with 3 nos of 75mm Aluminium hinges. | Sqm | 2366.0 | 2366.0 | 5.0 | False | None | None | False | None | False | 11830.0 | 0 | 2845097 | 92193 | None | CVL41 | Providing & fixing factory made PVC Door frame of size 50x47mm with a wall thickness of 5mm, made out of extruded 5mm rigid PVC foam sheet metered cut at corners & jointed 2 No.s of 150mm long brackets of 15x15mm M.S Square tube, the entire door frame to be reinforced with 19x19mm M.S Square tube of 19 gauge. the door frame to be fixed to the wall using M.S.Screws of 65/80mm size complete as per manufactures specification & direction of Engineer-in-charge. | Sqm | 318.0 | 318.0 | 12.6 | False | None | None | False | None | False | 4006.8 | 0 | 2845098 | 92193 | None | CVL42 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests. | Each | 4884.0 | 4884.0 | 2.0 | False | None | None | False | None | False | 9768.0 | 0 | 2845099 | 92193 | None | CVL43 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : Range of two urinal basins with 5 litre white P.V.C. automatic flushing cistern. | Each | 6784.0 | 6784.0 | 2.0 | False | None | None | False | None | False | 13568.0 | 0 | 2845100 | 92193 | None | CVL44 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required: using White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer. | Each | 2866.0 | 2866.0 | 2.0 | False | None | None | False | None | False | 5732.0 | 0 | 2845101 | 92193 | None | CVL45 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete . | Each | 1220.0 | 1220.0 | 2.0 | False | None | None | False | None | False | 2440.0 | 0 | 2845102 | 92193 | None | CVL46 | Providing and placing on terrace (at all fllor levels) polyethylene water storage tank, IS: 12701 marked, with cover and suitable locking arrangment and making necessary holes for inlet, outlet and overflow pipes but without fitting and the base support for tank. | l | 9.0 | 9.0 | 2000.0 | False | None | None | False | None | False | 18000.0 | 0 | 2845103 | 92193 | None | CVL47 | Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm including the cost of materials, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer in-charge of works as per the standard procedure | Sqm | 177.3 | 177.3 | 3690.0 | False | None | None | False | None | False | 654237.0 | 0 | 2845104 | 92193 | None | CVL48 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/appropriate sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Powder coated aluminium (minimum thickness of powder coating 50 micron) including cost of materials, labour, usage charges of machinery complete as per specifications. | Kg | 571.0 | 571.0 | 450.0 | False | None | None | False | None | False | 256950.0 | 0 | 2845105 | 92193 | None | CVL49 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50 kg/m²) including cost of materials, labour, usage charges of machinery complete as per specifications. | Sqm | 1171.0 | 1171.0 | 50.0 | False | None | None | False | None | False | 58550.0 | 0 | 2845106 | 92193 | None | CVL50 | Filling the gap in between aluminium/ stone/ wood frame and adjacent RCC/ Brick/ Stone/ wood/ Ceramic/ Gypsum work by providing weather/structural non sag elastomeric PU sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete, complying to ASTM C920, DIN 18540- F & ISO 11600 Upto 20 mm depth and 20 mm width including cost of materials, labour, usage charges of machinery complete as per specifications. | m | 296.0 | 296.0 | 200.0 | False | None | None | False | None | False | 59200.0 | 0 | 2845107 | 92193 | None | CVL51 | Providing and fixing Brass 100mm mortice latch and lock with 6 levers without pair of handles (best make of approved quality) for aluminium doors including necessary cutting and making good etc. complete including cost of materials, labour, usage charges of machinery complete as per specifications. | No | 437.0 | 437.0 | 10.0 | False | None | None | False | None | False | 4370.0 | 0 | 2845108 | 92193 | None | CVL52 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete. | No | 130.0 | 130.0 | 15.0 | False | None | None | False | None | False | 1950.0 | 0 | 2845109 | 92193 | None | CVL53 | Providing and fixing bright finished brass butt hinges with necessary screws etc. complete : 125x85x5.5 mm (heavy type). | No | 275.0 | 275.0 | 20.0 | False | None | None | False | None | False | 5500.0 | 0 | 2845110 | 92193 | None | CVL54 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in- charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts bolts, fasteners etc.) including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge | Kgs | 565.0 | 565.0 | 200.0 | False | None | None | False | None | False | 113000.0 | 0 | 2845111 | 92193 | None | CVL55 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (Made of G.I. wire of dia 4 mm) | Sqm | 803.0 | 803.0 | 530.0 | False | None | None | False | None | False | 425590.0 | 0 | 2845112 | 92193 | None | CVL56 | Fencing with G.I. barbed wire Angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 kg per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Cost of posts, struts, earth work and concrete work to be paid for separately). Payment to be made per metre cost of total length of barbed wire used. | m | 18.0 | 18.0 | 2800.0 | False | None | None | False | None | False | 50400.0 | 0 | 2845113 | 92193 | None | CVL57 | Providing and constructing load bearing wall with Solid Concrete blocks of size 400 x 200 x 200 mm having block density more than 1800kg/m3 and minimum compressive strength of 4.00 N/mm2 conforming to IS 2185 (Part - I) - 2005 and constructed with CM 1:4 as per IS 2572:2005 including cost of all materials, labour, scaffolding and curing, usage charges of machinery etc complete as per specifications. | Sqm | 1310.0 | 1310.0 | 800.0 | False | None | None | False | None | False | 1048000.0 | 0 | 2845114 | 92193 | None | CVL58 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in charge. Internal work - Exposed on wall
Provding and fixing CPVC pipes 50mm dia | m | 721.0 | 721.0 | 200.0 | False | None | None | False | None | False | 144200.0 | 0 | 2845115 | 92193 | None | CVL59 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in charge. Internal work - Exposed on wall
Provding and fixing CPVC pipes 40mm dia | m | 477.0 | 477.0 | 100.0 | False | None | None | False | None | False | 47700.0 | 0 | 2845116 | 92193 | None | CVL60 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in charge. Internal work - Exposed on wall
Provding and fixing CPVC pipes 25mm dia | m | 296.0 | 296.0 | 75.0 | False | None | None | False | None | False | 22200.0 | 0 | 2845117 | 92193 | None | CVL61 | Sinking borewell of 150mm dia. clear, using super fast hydraulic rig of capacity 250 PSIG & above 900 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc. For 2no's borewells Drilling of 150mm dia Borewell. Borewell depth of 0 to 50 m | m | 370.0 | 370.0 | 50.0 | False | None | None | False | None | False | 18500.0 | 0 | 2845118 | 92193 | None | CVL62 | Sinking borewell of 150mm dia. clear, using super fast hydraulic rig of capacity 250 PSIG & above 900 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc. For 2no's borewells Drilling of 150mm dia Borewell. Borewell depth of 50 to 100 m | m | 464.0 | 464.0 | 50.0 | False | None | None | False | None | False | 23200.0 | 0 | 2845119 | 92193 | None | CVL63 | Sinking borewell of 150mm dia. clear, using super fast hydraulic rig of capacity 250 PSIG & above 900 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc.For 2no's borewells Drilling of 150mm dia Borewell. Borewell depth of 100 to 150 m | m | 493.0 | 493.0 | 50.0 | False | None | None | False | None | False | 24650.0 | 0 | 2845120 | 92193 | None | CVL64 | Sinking borewell of 150mm dia. clear, using super fast hydraulic rig of capacity 250 PSIG & above 900 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc.For 2no's borewells Drilling of 150mm dia Borewell. Borewell depth of 150 to 200 m | m | 572.0 | 572.0 | 50.0 | False | None | None | False | None | False | 28600.0 | 0 | 2845121 | 92193 | None | CVL65 | Sinking borewell of 150mm dia. clear, using super fast hydraulic rig of capacity 250 PSIG & above 900 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc. For 2no's borewells Drilling of 150mm dia Borewell. Borewell depth of 200 to 250m | m | 671.0 | 671.0 | 50.0 | False | None | None | False | None | False | 33550.0 | 0 | 2845122 | 92193 | None | CVL66 | Supply of ISI mark 175mm nominal bore,plain and steel casing pipe grade of steel Fe 410 of wall thickness conforming to IS 4270-2001 andlatest ammendments, electrical resistance welded steel tubes, material and conforming to IS 1387-1993 and manufactured by basic open hearth electric or basic oxygen process in random length of 5-7m bothends.threaded conforming to IS 554-1985 one end fixed with socket conforming to IS 4270-2001 and the other end with screwed pipes all shall be responsibaly free from defects. The tubes shall be responsible straight end should be with ISI marking weighing 25.10kg/m.prices include Collar-Medium duty. | m | 1933.0 | 1933.0 | 100.0 | False | None | None | False | None | False | 193300.0 | 0 | 2845123 | 92193 | None | CVL67 | Providing and laying at site of work MS casing caps as per IS 1239 (partII) 1982 with all latest amendments if any for any dia. The thickness of plate used for covering one end shall be 3mm (minimum). The dimensions of caps and colars shall be strictly as per IS 1239 (Part-II) 1982 with all amendments including cost of material and labour charges for fixing, if any etc. complete with all lead and lifts and as directed by the Engineer in charge. | Each | 164.0 | 164.0 | 1.0 | False | None | None | False | None | False | 164.0 | 0 | 2845124 | 92193 | None | CVL68 | Geophysical investigation at site for sinking borewells for supplying drinking water to the habitation either through the Hand Pump MWS or P.W.S.S, by vertical electrical sounding by adopting Venner or Schlumbergers’s method, including reconnaissance survey of geological formation. Geophysical investigation of existing ground water in the vicinity, its quality, quantity and acceptability of the users, indicating the location of the site, recommended depth of casing pipe required to seal the top unconsolidated formation including an extra depth of 1.0 metre in consolidated formation for proper seating of casing pipe, depth of drilling required to cover full depth of aquifer proposed to be tapped, probable yield and other information required including transportation of instruments and accessories to work site, engaging technical personal and labour required etc. | Each | 5288.0 | 5288.0 | 1.0 | False | None | None | False | None | False | 5288.0 | 0 | 2845125 | 92193 | None | CVL69 | PUMPSET :
Providing,supplying to work site, Submersible Pump Set of 150mm dia suitable for bore well and confirming to IS 8034-2000;3Phase, SS Bowl & Impeller with Low volt Motor as per specifications,as per necessary ammendments and instructions of engineer incharge of work. For HP For 6.50 HP
6.50 HP - 90 LPM @ 132 m = 12 STG Outlet Dia - 2.00” | Each | 36719.0 | 36719.0 | 1.0 | False | None | None | False | None | False | 36719.0 | 0 | 2845126 | 92193 | None | CVL70 | Supply and delivery at site Brand new best make PVC insulated cable of Flat 3 core (sheathed) of nominal cross sectional area as per IS 694-1990 with ISI Mark and as per its latest amendments. 3C X 4.0 Sq mm | m | 135.0 | 135.0 | 175.0 | False | None | None | False | None | False | 23625.0 | 0 | 2845127 | 92193 | None | CVL71 | PRESSURE GAUGE :
Supply & delivery of brand new best make Pressure gauge burden type of size 100 mm as per IS-3624 -87 with its latest amendments with ISI mark. | Each | 654.0 | 654.0 | 1.0 | False | None | None | False | None | False | 654.0 | 0 | 2845128 | 92193 | None | CVL72 | GATE VALVE :
Supply and delivery at site of brand new best make gate valve as per IS 778/1984 with ISI Mark and as per its latest amendments. | Each | 1250.0 | 1250.0 | 1.0 | False | None | None | False | None | False | 1250.0 | 0 | 2845129 | 92193 | None | CVL73 | NON - RETURN VALVE :
Providing and fixing in position 50mm dia nominal bore gun metal non-return valve horizontal type of approved make mark including cost of all materials, lab our and HOM of equipments with all leads complete as per secificationns. | Each | 1250.0 | 1250.0 | 1.0 | False | None | None | False | None | False | 1250.0 | 0 | 2845130 | 92193 | None | CVL74 | Control Panel BOARD-A:
Supply, installing,testing and commissioning COMMON control panel consisting of the following INCOMING:1 No set of Phase indicating lamps with SFU of suitable rating 1 No, Analog Ammeter, 1 No Analog Voltmeter 1ni with Phase selector switch, Isolating switch OUTGOING for Main Electrical Pump: 1 No. MCB 1 No. DOL of S/D Starter suitable for respective HP 1 No. Electrcal Protection Like single Phase preventor, under voltage over Volage, under current over current & dry run protection suitable for the pump described above 1 no Indoor typ e NOTE: 1) DOLDirect Online Starter 2) S-D- Star Delta Starter for outdoor Upto 6 HP pumps. | Each | 15900.0 | 15900.0 | 1.0 | False | None | None | False | None | False | 15900.0 | 0 | 2845131 | 92193 | None | CVL75 | POWER CAPACITOR :
Supply and delivery at site best indigenous brand new power capacitor as per IS 2834/1986 with latest amendments with KPTCL authorities and erection, electrification and commissioning of the same at the location of respective pump sets. | Kvar | 550.0 | 550.0 | 2.0 | False | None | None | False | None | False | 1100.0 | 0 | 2845132 | 92193 | None | CVL76 | MCB :
Supply and delivery at site delivery of best ndigenous brand new MCB (Miniature Circuit Breakers) of required capacity as per IS 8228/1978 and its latest amendments and with ISI Mark of 6/10/16/20/25/40 Amps with scalable box. | Each | 1150.0 | 1150.0 | 1.0 | False | None | None | False | None | False | 1150.0 | 0 | 2845133 | 92193 | None | CVL77 | GALVANISED MILD STEEL TUBES:
Supply and delivery of galvanized mild steel tubes of 6mtr standard length heavy duty (C Class) as per IS 1239 (Part-I) 1990 with latest amendments with ISI Mark (one end fitted with Heavy Duty collar and other end fitted with protective cover) | Each | 3050.0 | 3050.0 | 15.0 | False | None | None | False | None | False | 45750.0 | 0 | 2845134 | 92193 | None | CVL78 | Erection elctrification & Commissioning works of pumpsets :
Labour charges for Erection, Electrification and commissioning of Pump sets, including aligning and balancing of all items including supply and erection of two pair of supporting clamps, bore well caps, cable clips and water tight gland cable protectors, bolts, nuts, valve and gauges,tools and equipments etc., involved in the job as per specifications, with necessary tests as per specifications, with testing of as per instructions of engineer incharge of work. | Set | 6500.0 | 6500.0 | 1.0 | False | None | None | False | None | False | 6500.0 | 0 | 2845135 | 92193 | None | CVL79 | Ercerion of panel board & meter board Unit :
Labour charges for erection of outdoor type panel board and meter board units with all necessary materials and labour, tools and equipments including providing cement concrete foundation bed etc., complete as per specification, with testing of as per instructions of engineer incharge of work. | Set | 1450.0 | 1450.0 | 1.0 | False | None | None | False | None | False | 1450.0 | 0 | 2845136 | 92193 | None | CVL80 | Main connections:
Providing main connection from pole PVC insulated sheathed steel wire cable in new trench as per IS 1554/ 1988 with latest amendments with ISI mark from KPTCL pole to meter board unit. | m | 135.0 | 135.0 | 50.0 | False | None | None | False | None | False | 6750.0 | 0 | 2845137 | 92193 | None | CVL81 | Pot Heads :
Providing and fixing suitable for 1.1 KV class UG cable filled with necessary bitumen/insulating compound complete with terminals, lamps, bolts,nuts and washers etc. with necessary materials and labour tools and equipments as per instructions of engineer incharge of work. etc 10 Sqmm. | Each | 450.0 | 450.0 | 1.0 | False | None | None | False | None | False | 450.0 | 0 | 2845138 | 92193 | None | CVL82 | Labour charges for providing connection using insulated sheathed steel wire cable as per IS 1554/ 1988 with latest amendments from KPTCL pole to meter board unit, with all necessary materials ,tools and equipments,as per specificationswith testing of as per instructions of engineer incharge of work 3.5 x 10 sqmm | m | 195.0 | 195.0 | 50.0 | False | None | None | False | None | False | 9750.0 | 0 | 2845139 | 92193 | None | CVL83 | Earthing :
suplying, fixing & wiring earth electordes for grouding conduits, I.C cutouts and other equipments on the meter board using 40mm dia 2.90mm thick GI pipe 2.5 mtr long buried in a pit.. The pit should be filled with equal proportion of salt and charcoal 150mm all-round the pipe to complete depth. The connection from the pipe to the conduit etc., is to be established through GI wire of size as per ISI specification 7.3.3 of IS 732 using 12mm dia bolts, nuts, washers and check nuts., the pipe shall have 16 through holes of 122 mm dia. | Job | 3750.0 | 3750.0 | 1.0 | False | None | None | False | None | False | 3750.0 | 0 | 2845140 | 92193 | None | CVL84 | Supplying of TPST with reqirable porcelain channels in SM enclosure, made out of 14 SWG powder coated paint of approved colour. 32 AMPS. | Each | 1701.0 | 1701.0 | 6.0 | False | None | None | False | None | False | 10206.0 | 0 | 2845141 | 92193 | None | CVL85 | Supplying and fixing of Porcelain fuse channel with cut out on existing wooden/panel using necessary nuts, bolts and washers 32 AMPS | Each | 241.0 | 241.0 | 6.0 | False | None | None | False | None | False | 1446.0 | 0 | 2845142 | 92193 | None | CVL86 | Concealed Conduit System Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509 with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary 19/20mm dia 2mm thick | m | 66.0 | 66.0 | 50.0 | False | None | None | False | None | False | 3300.0 | 0 | 2845143 | 92193 | None | CVL87 | Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering upto the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary 25mm dia 2mm thick | m | 79.0 | 79.0 | 150.0 | False | None | None | False | None | False | 11850.0 | 0 | 2845144 | 92193 | None | CVL88 | Supplying and fixing sheet metal box made out of 18 SWG sheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc. 100x75x65mm. | Each | 118.0 | 118.0 | 6.0 | False | None | None | False | None | False | 708.0 | 0 | 2845145 | 92193 | None | CVL89 | Supplying and fixing sheet metal box made out of 18 SWG sheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc. 135x75x65mm. | Each | 139.0 | 139.0 | 5.0 | False | None | None | False | None | False | 695.0 | 0 | 2845146 | 92193 | None | CVL90 | Supplying PVC/GI flexible conduit pipe…mm dia fixing on surface over inverted tapered wooden plugs or phill plugs or rawl plugs and clamped using heavy gauge saddles at an interval of 300mm using NF screws and on either end of the pipe terminated completely. 25mm | m | 22.0 | 22.0 | 85.0 | False | None | None | False | None | False | 1870.0 | 0 | 2845147 | 92193 | None | CVL91 | Supplying And Fixing Metal Fan Box with Round Hook. | No | 117.0 | 117.0 | 10.0 | False | None | None | False | None | False | 1170.0 | 0 | 2845148 | 92193 | None | CVL92 | SupplyingandwiringadoptingloopsysteminexistingPVCConduit/casingcappingusing2x1.5Sqmm(Phase&Neutral) &1x1.0sqmm (Earthwire)FRLS multistrand PVC insulated copperwire (confirming toIS-694:and latest amendments) with a 6Amps flushtype SPcontrol switch shall be fixed on the existing plasticsheet /gangbox, the other end of the wires shall be terminated with sufficient loose length in a wood /PVC roundblock. complete for each outlet.. Short point upto 3Mtr from tapping point to out let via switch box | Point | 285.0 | 285.0 | 6.0 | False | None | None | False | None | False | 1710.0 | 0 | 2845149 | 92193 | None | CVL93 | SupplyingandwiringadoptingloopsysteminexistingPVCConduit/casingcappingusing2x1.5Sqmm(Phase&Neutral) &1x1.0sqmm (Earthwire)FRLS multistrand PVC insulated copperwire (confirming toIS-694:and latest amendments) with a 6Amps flushtype SPcontrol switch shall be fixed on the existing plasticsheet /gangbox, the other end of the wires shall be terminated with sufficient loose length in a wood /PVC roundblock. complete for each outlet.. Short point upto 3Mtr from tapping point to out let via switch box | Point | 394.0 | 394.0 | 10.0 | False | None | None | False | None | False | 3940.0 | 0 | 2845150 | 92193 | None | CVL94 | SupplyingandwiringadoptingloopsysteminexistingPVCConduit/casingcappingusing2x1.5Sqmm(Phase&Neutral) &1x1.0sqmm (Earthwire)FRLS multistrand PVC insulated copperwire (confirming toIS-694:and latest amendments) with a 6Amps flushtype SPcontrol switch shall be fixed on the existing plasticsheet /gangbox, the other end of the wires shall be terminated with sufficient loose length in a wood /PVC roundblock. complete for each outlet.. Short point upto 3Mtr from tapping point to out let via switch box | Point | 570.0 | 570.0 | 10.0 | False | None | None | False | None | False | 5700.0 | 0 | 2845151 | 92193 | None | CVL95 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 1.5 Sqmm | m | 26.0 | 26.0 | 250.0 | False | None | None | False | None | False | 6500.0 | 0 | 2845152 | 92193 | None | CVL96 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 2.5 Sqmm | m | 42.0 | 42.0 | 400.0 | False | None | None | False | None | False | 16800.0 | 0 | 2845153 | 92193 | None | CVL97 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 4 Sqmm | m | 63.0 | 63.0 | 550.0 | False | None | None | False | None | False | 34650.0 | 0 | 2845154 | 92193 | None | CVL98 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 6 Sqmm | m | 92.0 | 92.0 | 150.0 | False | None | None | False | None | False | 13800.0 | 0 | 2845155 | 92193 | None | CVL99 | Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall. 1-2way | Each | 138.0 | 138.0 | 5.0 | False | None | None | False | None | False | 690.0 | 0 | 2845156 | 92193 | None | CVL100 | Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall. 6Way. | Each | 220.0 | 220.0 | 2.0 | False | None | None | False | None | False | 440.0 | 0 | 2845157 | 92193 | None | CVL101 | Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall. 8Way. | Each | 261.0 | 261.0 | 4.0 | False | None | None | False | None | False | 1044.0 | 0 | 2845158 | 92193 | None | CVL102 | Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 10-12 way | Each | 319.0 | 319.0 | 8.0 | False | None | None | False | None | False | 2552.0 | 0 | 2845159 | 92193 | None | CVL103 | Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 16Way | Each | 363.0 | 363.0 | 10.0 | False | None | None | False | None | False | 3630.0 | 0 | 2845160 | 92193 | None | CVL104 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 1 to 3 Module | Each | 137.0 | 137.0 | 5.0 | False | None | None | False | None | False | 685.0 | 0 | 2845161 | 92193 | None | CVL105 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 6 Module | Each | 234.0 | 234.0 | 2.0 | False | None | None | False | None | False | 468.0 | 0 | 2845162 | 92193 | None | CVL106 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 8 Module | Each | 284.0 | 284.0 | 4.0 | False | None | None | False | None | False | 1136.0 | 0 | 2845163 | 92193 | None | CVL107 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 10-12 Module | Each | 344.0 | 344.0 | 8.0 | False | None | None | False | None | False | 2752.0 | 0 | 2845164 | 92193 | None | CVL108 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box. 16 Module | Each | 397.0 | 397.0 | 10.0 | False | None | None | False | None | False | 3970.0 | 0 | 2845165 | 92193 | None | CVL109 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A One Way Switch | Each | 102.0 | 102.0 | 10.0 | False | None | None | False | None | False | 1020.0 | 0 | 2845166 | 92193 | None | CVL110 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A Two Way Switch | Each | 166.0 | 166.0 | 5.0 | False | None | None | False | None | False | 830.0 | 0 | 2845167 | 92193 | None | CVL111 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A Three Way socket | Each | 171.0 | 171.0 | 5.0 | False | None | None | False | None | False | 855.0 | 0 | 2845168 | 92193 | None | CVL112 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.Stepped Fan Regulator Two Module | Each | 357.0 | 357.0 | 10.0 | False | None | None | False | None | False | 3570.0 | 0 | 2845169 | 92193 | None | CVL113 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.16A One Way Switch. | Each | 180.0 | 180.0 | 2.0 | False | None | None | False | None | False | 360.0 | 0 | 2845170 | 92193 | None | CVL114 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A Bell Push. | Each | 177.0 | 177.0 | 1.0 | False | None | None | False | None | False | 177.0 | 0 | 2845171 | 92193 | None | CVL115 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293 32A DP Switch. | Each | 326.0 | 326.0 | 2.0 | False | None | None | False | None | False | 652.0 | 0 | 2845172 | 92193 | None | CVL116 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 12933 6/16A Universal Socket. | Each | 236.0 | 236.0 | 2.0 | False | None | None | False | None | False | 472.0 | 0 | 2845173 | 92193 | None | CVL117 | Supplying and fixing hylum plastic sheet 3mm thick with necessary nitches for fixing switches, regulators etc., and fixing on existing wood or metal box using N. F. screws. | Sq CM | 0.35 | 0.35 | 600.0 | False | None | None | False | None | False | 210.0 | 0 | 2845174 | 92193 | None | CVL118 | Extra for supplying 4 mm thick white plastic plate andcovering for junction boxes of size ...... mm conduit using necessary machine screws.80 mm. | No | 15.0 | 15.0 | 10.0 | False | None | None | False | None | False | 150.0 | 0 | 2845175 | 92193 | None | CVL119 | Extra for supplying 4 mm thick white plastic plate andcovering for junction boxes of size ...... mm conduit using necessary machine screws.110 mm. | No | 21.0 | 21.0 | 10.0 | False | None | None | False | None | False | 210.0 | 0 | 2845176 | 92193 | None | CVL120 | Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws,bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuit in Thermal Magnetic Release. Micro processor release shall have Earth Fault as per IS-13947. (Icu=100% lcs). In 4P MCCB, all Poles should have protection for Short-Cicrcuit/Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open). Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.FOUR Pole.100 A 25 kA | Each | 8487.0 | 8487.0 | 2.0 | False | None | None | False | None | False | 16974.0 | 0 | 2845177 | 92193 | None | CVL121 | Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.6-32 A SP | Each | 415.0 | 415.0 | 4.0 | False | None | None | False | None | False | 1660.0 | 0 | 2845178 | 92193 | None | CVL122 | Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.50-63 A SP | Each | 811.0 | 811.0 | 5.0 | False | None | None | False | None | False | 4055.0 | 0 | 2845179 | 92193 | None | CVL123 | Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.6-32 A TPN | Each | 1717.0 | 1717.0 | 2.0 | False | None | None | False | None | False | 3434.0 | 0 | 2845180 | 92193 | None | CVL124 | Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.50-63 A TPN | Each | 3088.0 | 3088.0 | 1.0 | False | None | None | False | None | False | 3088.0 | 0 | 2845181 | 92193 | None | CVL125 | Supplying and fixing regular MCB distribution boards on wall/ood board / flush mounting using required clA, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase/3 phase/single door with powder coated painting Made out of 14 SWG MS enclosure.II - Double Door.12 Way SP & N | Each | 2329.0 | 2329.0 | 1.0 | False | None | None | False | None | False | 2329.0 | 0 | 2845182 | 92193 | None | CVL126 | Supplying, fixing and wiring Residual current circuit breaker (RCCB) 240/450V up to 300mA sensitivity on existing wood/ panel board.16-25 A 2 pole | Each | 4277.0 | 4277.0 | 1.0 | False | None | None | False | None | False | 4277.0 | 0 | 2845183 | 92193 | None | CVL127 | Supplying, fixing and wiring Residual current circuit breaker (RCCB)240/450V upto 300mA sensitivity on existing wood/ panel board.32 -40A 2 pole | Each | 4559.0 | 4559.0 | 1.0 | False | None | None | False | None | False | 4559.0 | 0 | 2845184 | 92193 | None | CVL128 | Supplying, fixing and wiring earth leakage relay with core balanced current transformer suitable for single phase 50 Hz AC with latest microcontroller based, digital readout of percentage leakage current, programmable delay/auto/manual reset facility suitable to mount on DIN rail/ flush mounting on panel board. | Each | 9255.0 | 9255.0 | 1.0 | False | None | None | False | None | False | 9255.0 | 0 | 2845185 | 92193 | None | CVL129 | Supplying, fixing and wiring 0 to 1500A CT operated AC analog type Ammeter without CT | Each | 480.0 | 480.0 | 3.0 | False | None | None | False | None | False | 1440.0 | 0 | 2845186 | 92193 | None | CVL130 | Supplying, fixing and wiring 3 Phase Digital Ammeter / Voltmeter | Each | 1425.0 | 1425.0 | 2.0 | False | None | None | False | None | False | 2850.0 | 0 | 2845187 | 92193 | None | CVL131 | Supplying, fixing and wiring Electronic Trivector Meter (ETV) 5 to 32/63A three phase 4 wire whole current class-1 Accuracy Energy Meter. | Each | 5705.0 | 5705.0 | 1.0 | False | None | None | False | None | False | 5705.0 | 0 | 2845188 | 92193 | None | CVL132 | Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 230/440VAC. 50 Hz 12/24V D.C. | Each | 515.0 | 515.0 | 3.0 | False | None | None | False | None | False | 1545.0 | 0 | 2845189 | 92193 | None | CVL133 | Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. Flat......with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint.40 x 40 x 6 mm | m | 305.0 | 305.0 | 12.0 | False | None | None | False | None | False | 3660.0 | 0 | 2845190 | 92193 | None | CVL134 | Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. Flat......with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint.50 x 50 x 6 mm | m | 395.0 | 395.0 | 8.0 | False | None | None | False | None | False | 3160.0 | 0 | 2845191 | 92193 | None | CVL135 | Fabricating supplying and mounting MS box made out 18 SWG suitable for floor /wall mounting, fully weather proof with provision for better heat dissipation, provided with hinged front cover, equipped with tamper proof locking arrangements, with suitable size clA with necessary cable entry pipe with gland and box should be finished with 7tanks treatment with powder coated paint and finally finished with approved colour etc., complete. | Sq CM | 0.43 | 0.43 | 25000.0 | False | None | None | False | None | False | 10750.0 | 0 | 2845192 | 92193 | None | CVL136 | Supplying exhaust fan of 1440 RPM of 300 mm (12") size with bracket blades complete for light duty suitable to operate on 230V 50Hz, AC Supply. | Each | 2969.0 | 2969.0 | 2.0 | False | None | None | False | None | False | 5938.0 | 0 | 2845193 | 92193 | None | CVL137 | Supplying of 1440 rpm heavy duty exhaust fan with bracket blades suitable to operate on 230V 50Hz, AC Supply complete.15" Sweep (450 mm) | Each | 4446.0 | 4446.0 | 2.0 | False | None | None | False | None | False | 8892.0 | 0 | 2845194 | 92193 | None | CVL138 | Supplying capacitor type ceiling fan complete with down rod blades, shackle, canopies etc., for operation on 230 volts, 50 cycles. Single phase AC supply conforming to ISS-374-1979 and with double ball bearing system 48" Sweep (1200mm) Regular model | Each | 2984.0 | 2984.0 | 10.0 | False | None | None | False | None | False | 29840.0 | 0 | 2845195 | 92193 | None | CVL139 | Supplying wall mounting fan suitable to operate at singlephase 230v AC. supply.400 mm Sweep | Each | 3212.0 | 3212.0 | 2.0 | False | None | None | False | None | False | 6424.0 | 0 | 2845196 | 92193 | None | CVL140 | Supplying of .....feet -PVC Batten with integrated LED tube ....W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI greater than 80. Power Input: 220-240V@ 50/60Hz & Power factor greater than0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition.LED light fitting 1 x 4' - 20/22 W | Each | 690.0 | 690.0 | 10.0 | False | None | None | False | None | False | 6900.0 | 0 | 2845197 | 92193 | None | CVL141 | Supplying of recess mounting non integral type ........ LED w luminaire comprising of pressure decast/extruded aluminium housing, with spring loaded false ceiling clA, Power LEDs with CCT 6500 degree K, CRIgreater than 70%. efficacy greater than 100 lumen per W, 120degree beam spread, lifegreater than 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level LEDs are driven by HF electronic driver integrated in a separate control gear assembly., with PF greater than 0.95, power loss should less than 5% of lamp Wage., short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition.LED modular down light 2'x2' /1'x4' 34-36 W | Each | 5898.0 | 5898.0 | 10.0 | False | None | None | False | None | False | 58980.0 | 0 | 2845198 | 92193 | None | CVL142 | Supply of LED Streetlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate material, delivering superior light output Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, maximum light intensity should be between 60 degrees to 70 degrees. CCT greater than 5500K, IP66 optical and electrical compartment & impact resistance of complete luminaire greater than IK08. Power Factor greater than0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole mounting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with ........W System Power consumption. LED Efficiencygreater than1301m/w, nominal CRI greater than75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001 :2008. Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing/ Body part. Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned.LED Streetlight 90 W | Each | 8860.0 | 8860.0 | 11.0 | False | None | None | False | None | False | 97460.0 | 0 | 2845199 | 92193 | None | CVL143 | Supplying & fixing of retrofit type - LED bulb ...... W with OPAL acrylic diffuser comprising of LED source with CCT 6500 degree K, CRIgreater than 70%. efficacy greater than80 lumen per W, lifegreater than 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The LED are driven by HF electronic driver integrated in the system, with PF greater than 0.95, power loss should less than 5% of lamp Wage., short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition.15W, 6500K. | Each | 326.0 | 326.0 | 10.0 | False | None | None | False | None | False | 3260.0 | 0 | 2845200 | 92193 | None | CVL144 | Supplying and Fixing of........mm dia class A GI pipe bracket upto 2 ms long bent at suitable angle and fixing to this bracket 1x40/2x40 W fluorescent tube street light fitting of all capacities to GI or GI or rail or RCC pole / wall using suitable clA, bolts, and nuts and wiring using suitable capacity wires. Using 25mm dia G.I.Pipe. | Each | 978.0 | 978.0 | 11.0 | False | None | None | False | None | False | 10758.0 | 0 | 2845201 | 92193 | None | CVL145 | Fixing all types and all capacities of fluorescent /false ceiling / spot light / CFL / LED fittings indoor on the wall/ ceiling / rafters / girders using 23/0.0076" twin twisted PVC insulated wires, required Nos of round blocks and clA.On wall/ ceiling / Rafter / Girders. | Each | 122.0 | 122.0 | 30.0 | False | None | None | False | None | False | 3660.0 | 0 | 2845202 | 92193 | None | CVL146 | Fixing a ceiling / Wall mounting fan of all capacities and all types to the existing 'S'' hook with fan regulator to the existing board together with supplying and fixing 5 A. ceiling rose, necessary length of 23 / 0.0076 inch PVC insulated twin twisted copper wire and wiring. | Each | 171.0 | 171.0 | 16.0 | False | None | None | False | None | False | 2736.0 | 0 | 2845203 | 92193 | None | CVL147 | Fixing one exhaust fan after making a suitable notch in the wall and finishing with cement mortar and colouring to match the existing wall or brackets, with bolts and nuts and a 5 A, ceiling rose with sufficient length of 23 / 0.0076 inch PVC insulated twin core wire of approved make with wire mesh and wooden frame. | Each | 707.0 | 707.0 | 4.0 | False | None | None | False | None | False | 2828.0 | 0 | 2845204 | 92193 | None | CVL148 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights,including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. In ordinary/soft rock without blasting upto 1.5 m depth. | Cum | 363.0 | 363.0 | 240.4 | False | None | None | False | None | False | 87265.2 | 0 | 2845205 | 92193 | None | CVL149 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights,including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. In ordinary/soft rock without blasting Depth exceeding 1.5 m but not exceeding 3 m depth | Cum | 425.0 | 425.0 | 240.4 | False | None | None | False | None | False | 102170.0 | 0 | 2845206 | 92193 | None | CVL150 | Earth work excavation for Foundation by Mechanical means depth upto 1.50m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including cost of explosives, dressing of excavated surfaces, disposing off or levelling the excavated stuff or sorting & stacking the selected stuff for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, blasting materials, tools, usage of Machinery & all other appurtenaces required to complete the work.
In Hard Rock (requiring blasting) Depth upto 1.50m | Cum | 554.0 | 554.0 | 12.66 | False | None | None | False | None | False | 7013.64 | 0 | 2845207 | 92193 | None | CVL151 | Earth work excavation for Foundation by Mechanical means depth upto 1.50m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including cost of explosives, dressing of excavated surfaces, disposing off or levelling the excavated stuff or sorting & stacking the selected stuff for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, blasting materials, tools, usage of Machinery & all other appurtenaces required to complete the work.
In Hard Rock ( requiring blasting) Depth exceeding 1.5 m, but not exceeding 3 m | Cum | 623.0 | 623.0 | 12.66 | False | None | None | False | None | False | 7887.18 | 0 | 2845208 | 92193 | None | CVL152 | Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite /trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. Mix 1:3:6 (M10) Using 20 mm nominal size graded crushed coarse aggregates | Cum | 6217.0 | 6217.0 | 121.46 | False | None | None | False | None | False | 755116.82 | 0 | 2845209 | 92193 | None | CVL153 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. | Cum | 266.0 | 266.0 | 6732.17 | False | None | None | False | None | False | 1790757.22 | 0 |
|
|
---|