3311313 | 115632 | None | code01 | Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material to the appropriate disposal area as per direction of Engineer-in-charge. | Cum | 2498.78 | 2498.78 | 8.38 | False | None | None | False | None | False | 20939.7764 | 0 |
3311314 | 115632 | None | code02 | Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material to the appropriate disposal area as per direction of Engineer-in-charge.In cement mortar | Cum | 1059.87 | 1059.87 | 195.79 | False | None | None | False | None | False | 207511.9473 | 0 |
3311315 | 115632 | None | code03 | Dismantling weather proof course and removing and conveying the debris to a distance to the appropriate disposal area as per direction of Engineer-in-charge. | Cum | 374.92 | 374.92 | 55.84 | False | None | None | False | None | False | 20935.5328 | 0 |
3311316 | 115632 | None | code04 | Dismantling roofing including ridges, hips, valleys and gutters etc., and stacking the material to the appropriate disposal area as per direction of Engineer-in-charge. Asbestos cement sheet | Sqm | 52.53 | 52.53 | 27.36 | False | None | None | False | None | False | 1437.2208 | 0 |
3311317 | 115632 | None | code05 | Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transport- ing, unloading to approved municipal dumping ground or as approved by Engineer-in-charge to the appropriate disposal area. | Sqm | 2419.47 | 2419.47 | 64.22 | False | None | None | False | None | False | 155378.3634 | 0 |
3311318 | 115632 | None | code06 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work In all kinds of soils Depth upto 3 m | Cum | 105.06 | 105.06 | 16.77 | False | None | None | False | None | False | 1761.8562 | 0 |
3311319 | 115632 | None | code07 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work In all kinds of soils Depth upto 3 m- In ordinary/soft rock without blasting upto 1.5 m depth Soft rock 10% OF THE TOTAL QUANTITY | Cum | 373.89 | 373.89 | 0.04 | False | None | None | False | None | False | 14.9556 | 0 |
3311320 | 115632 | None | code08 | PCC BED Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork shall be paid separately)-Mix 1:4:8( M5) Using 40 mm nominal size graded crushed coarse
aggregates | Cum | 5833.92 | 5833.92 | 18.66 | False | None | None | False | None | False | 108860.9472 | 0 |
3311321 | 115632 | None | code09 | FOOTING CONCRETING Providing and laying in position Reinforced cement concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork to be paid separately)-M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates
(RATE INCLUDING CENTERING 8% ON CONCRETE ITEM)
Basic rate: 6248 | Cum | 6435.44 | 6435.44 | 2.74 | False | None | None | False | None | False | 17633.1056 | 0 |
3311322 | 115632 | None | code10 | PLINTH BEAM-Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other M25 Design Mix Using 20 mm nominal size graded
crushed coarse aggregates
(RATE INCLUDING CENTERING 50% ON CONCRETE ITEM)
Basic rate:6336 | Cum | 9789.12 | 9789.12 | 0.86 | False | None | None | False | None | False | 8418.6432 | 0 |
3311323 | 115632 | None | code11 | EARTH FILLING-Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. | Cum | 273.98 | 273.98 | 65.78 | False | None | None | False | None | False | 18022.4044 | 0 |
3311324 | 115632 | None | code12 | RCC COLUMN-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse
aggregates
(RATE INCLUDING CENTERING 70% ON CONCRETE ITEM)
Up to Plinth Bottom | Cum | 10831.69 | 10831.69 | 0.54 | False | None | None | False | None | False | 5849.1126 | 0 |
3311325 | 115632 | None | code13 | RCC COLUMN-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse
aggregates
(RATE INCLUDING CENTERING 70% ON CONCRETE ITEM)
Up to Plinth Bottom Ground Floor | Cum | 10831.69 | 10831.69 | 1.3 | False | None | None | False | None | False | 14081.197 | 0 |
3311326 | 115632 | None | code14 | RCC COLUMN-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse
aggregates
(RATE INCLUDING CENTERING 70% ON CONCRETE ITEM)
Up to Plinth Bottom First Floor | Cum | 10940.0 | 10940.0 | 31.59 | False | None | None | False | None | False | 345594.6 | 0 |
3311327 | 115632 | None | code15 | RCC COLUMN-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse
aggregates
(RATE INCLUDING CENTERING 70% ON CONCRETE ITEM)
Up to Plinth Bottom Second Floor Dummi column | Cum | 11048.32 | 11048.32 | 10.79 | False | None | None | False | None | False | 119211.3728 | 0 |
3311328 | 115632 | None | code16 | RCC BEAM-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse
aggregates (RATE INCLUDING CENTERING 60% ON CONCRETE ITEM)
-Ground Floor | Cum | 11277.26 | 11277.26 | 8.81 | False | None | None | False | None | False | 99352.6606 | 0 |
3311329 | 115632 | None | code17 | RCC BEAM-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse
aggregates (RATE INCLUDING CENTERING 60% ON CONCRETE ITEM)
-First Floor | Cum | 11390.04 | 11390.04 | 51.17 | False | None | None | False | None | False | 582828.3468 | 0 |
3311330 | 115632 | None | code18 | RCC LINTEL-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates (RATE INCLUDING CENTERING 60% ON CONCRETE ITEM)
0-First Floor | Cum | 11390.04 | 11390.04 | 11.5 | False | None | None | False | None | False | 130985.46 | 0 |
3311331 | 115632 | None | code19 | SILL CONCRETE-Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork shall be paid separately)-- Mix 1:3:6 (M10) Using 20 mm nominal size graded crushed coarse aggregates (RATE INCLUDING CENTERING 60% ON CONCRETE ITEM)
First floor | Cum | 10309.65 | 10309.65 | 0.79 | False | None | None | False | None | False | 8144.6235 | 0 |
3311332 | 115632 | None | code20 | RCC STAIRCASE-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates (RATE INCLUDING CENTERING 50% ON CONCRETE ITEM) -FIRST FLOOR TO SECOND FLOOR-BRICK MASONRY 230 mm thick | Cum | 10642.92 | 10642.92 | 4.15 | False | None | None | False | None | False | 44168.118 | 0 |
3311333 | 115632 | None | code21 | Providing Brick work with common burnt clay machine moulded perforated bricks of class designation 5.0 conforming to IS: 2222 in superstructure above plinth level in cement mortar 1:6 (1 cement : 6 coarse sand) With Modular bricks including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work.-First Floor | Sqm | 12092.45 | 12092.45 | 179.54 | False | None | None | False | None | False | 2171078.473 | 0 |
3311334 | 115632 | None | code22 | Providing Brick work with common burnt clay machine moulded perforated bricks of class designation 5.0 conforming to IS: 2222 in superstructure above plinth level in cement mortar 1:6 (1 cement : 6 coarse sand) With Modular bricks including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work.-Second Floor | Sqm | 12212.17 | 12212.17 | 38.35 | False | None | None | False | None | False | 468336.7195 | 0 |
3311335 | 115632 | None | code23 | RCC SLAB-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates
(RATE INCLUDING CENTERING 50% ON CONCRETE ITEM) Basic rate: 6843.00 Ground Floor | Cum | 10572.44 | 10572.44 | 16.3 | False | None | None | False | None | False | 172330.772 | 0 |
3311336 | 115632 | None | code24 | RCC SLAB-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates
(RATE INCLUDING CENTERING 50% ON CONCRETE ITEM) Basic rate: 6843.00 First Floor | Cum | 10678.16 | 10678.16 | 92.46 | False | None | None | False | None | False | 987302.6736 | 0 |
3311337 | 115632 | None | code25 | RCC CHAJJA-Providing and laying in position Reinforced cement concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/ trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement, dowel bars & formwork to be paid separately)-- M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates
(RATE INCLUDING CENTERING 45% ON CONCRETE ITEM) | Cum | 10290.5 | 10290.5 | 4.6 | False | None | None | False | None | False | 47336.3 | 0 |
3311338 | 115632 | None | code26 | Providing Thermo-Mechanically Treated bars of grade Fe-550 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position, binding and anchoring to adjacent members whereever necessary complete as per Design including cost of material, labour, usage charges complete as per specifications. (The laps and wastages shall not be measured separately) | Kg | 90.64 | 90.64 | 34499.05 | False | None | None | False | None | False | 3126993.892 | 0 |
3311339 | 115632 | None | code27 | Providing and fixing Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. In stringers, treads, landings etc. of stair cases, including use of chequered plate wherever required, all complete including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. | Kg | 116.39 | 116.39 | 7365.05 | False | None | None | False | None | False | 857218.1695 | 0 |
3311340 | 115632 | None | code28 | Providing Red Salwood frames of doors, windows, clerestory windows, ventilators and other frames, wrought, framed or assembled including making plaster groves (excluding cost of cement concrete and side clamps), but including cost of materials, labour, usage charges complete as per specifications. -First Floor | Cum | 103613.88 | 103613.88 | 1.16 | False | None | None | False | None | False | 120192.1008 | 0 |
3311341 | 115632 | None | code29 | Providing Red Salwood frames of doors, windows, clerestory windows, ventilators and other frames, wrought, framed or assembled including making plaster groves (excluding cost of cement concrete and side clamps), but including cost of materials, labour, usage charges complete as per specifications. Second Floor | Cum | 105686.16 | 105686.16 | 0.09 | False | None | None | False | None | False | 9511.7544 | 0 |
3311342 | 115632 | None | code30 | Providing Red Salwood frames of doors, windows, clerestory windows, ventilators and other frames, wrought, framed or assembled including making plaster groves (excluding cost of cement concrete and side clamps), but including cost of materials, labour, usage charges complete as per specifications. | Cum | 102588.0 | 102588.0 | 0.14 | False | None | None | False | None | False | 14362.32 | 0 |
3311343 | 115632 | None | code31 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass kg 463.00 / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Polyester powder coated aluminium (minimum thickness of polyester powder coating 50 micron) including cost of materials, labour, usage charges of machinery complete as per specifications. FF | Kg | 476.89 | 476.89 | 679.6863 | False | None | None | False | None | False | 324135.599607 | 0 |
3311344 | 115632 | None | code32 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50 kg/m²) including cost of materials, labour, usage charges of machinery complete as per specifications.-FF | Sqm | 1206.13 | 1206.13 | 85.14 | False | None | None | False | None | False | 102689.9082 | 0 |
3311345 | 115632 | None | code33 | Providing and fixing flush door shutter made out of solid core block board type, well seasoned , chemicaly treated hard wood battens and internal frame with minimum 45 mm wide wooden frame alround door shutters covered with cross bonded wooden sheets (core veneer) hot pressed and fastened on both sides of the door useing liquid phenol formaldehyde resin as per IS specifications 2202 (part-I) 1991. from manufacturer complete as per spcification.-35 mm thick both side commercial First Floor | Sqm | 3455.88 | 3455.88 | 39.99 | False | None | None | False | None | False | 138200.6412 | 0 |
3311346 | 115632 | None | code34 | Providing and fixing flush door shutter made out of solid core block board type, well seasoned , chemicaly treated hard wood battens and internal frame with minimum 45 mm wide wooden frame alround door shutters covered with cross bonded wooden sheets (core veneer) hot pressed and fastened on both sides of the door useing liquid phenol formaldehyde resin as per IS specifications 2202 (part-I) 1991. from manufacturer complete as per spcification.-35 mm thick both side commercial Second Floor | Sqm | 3524.99 | 3524.99 | 2.4 | False | None | None | False | None | False | 8459.976 | 0 |
3311347 | 115632 | None | code35 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to steel windows by welding-FF | Kgs | 174.77 | 174.77 | 1787.94 | False | None | None | False | None | False | 312478.2738 | 0 |
3311348 | 115632 | None | code36 | Providing 12 mm cement plaster with Cement mortar 1:3 (1cement: 3 coarse sand) finished with a floating coat of neat cement to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete Ground Floor | Sqm | 332.69 | 332.69 | 108.96 | False | None | None | False | None | False | 36249.9024 | 0 |
3311349 | 115632 | None | code37 | Providing 12 mm cement plaster with Cement mortar 1:3 (1cement: 3 coarse sand) finished with a floating coat of neat cement to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete First Floor | Sqm | 336.02 | 336.02 | 676.37 | False | None | None | False | None | False | 227273.8474 | 0 |
3311350 | 115632 | None | code38 | Providing 15 mm cement plaster with cement mortar 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement on the rough side of single or half brick wall including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per
directions of Engineer-in-charge.-Ground Floor | Sqm | 376.98 | 376.98 | 11.45 | False | None | None | False | None | False | 4316.421 | 0 |
3311351 | 115632 | None | code39 | Providing 15 mm cement plaster with cement mortar 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement on the rough side of single or half brick wall including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per
directions of Engineer-in-charge.-First Floor | Sqm | 380.75 | 380.75 | 1558.06 | False | None | None | False | None | False | 593231.345 | 0 |
3311352 | 115632 | None | code40 | Providing 15 mm cement plaster with cement mortar 1:3 (1 cement: 3 coarse sand) finished with a floating coat of neat cement on the rough side of single or half brick wall including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per
directions of Engineer-in-charge.-Second Floor | Sqm | 384.52 | 384.52 | 67.32 | False | None | None | False | None | False | 25885.8864 | 0 |
3311353 | 115632 | None | code41 | Providing 18 mm cement plaster in two coats under layer 12 mm thick cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster with cement mortar 1:3 (1 cement : 3 coarse sand) finished rough with sponge to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in- charge.-First Floor | Sqm | 400.52 | 400.52 | 783.29 | False | None | None | False | None | False | 313723.3108 | 0 |
3311354 | 115632 | None | code42 | Providing 18 mm cement plaster in two coats under layer 12 mm thick cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster with cement mortar 1:3 (1 cement : 3 coarse sand) finished rough with sponge to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in- charge.-Second Floor | Sqm | 408.53 | 408.53 | 69.72 | False | None | None | False | None | False | 28482.7116 | 0 |
3311355 | 115632 | None | code43 | Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork shall be paid separately)-- Mix 1:3:6 (M10) Using 40 mm nominal size graded crushed coarse
aggregates-Ground Floor | Cum | 6168.67 | 6168.67 | 16.57 | False | None | None | False | None | False | 102214.8619 | 0 |
3311356 | 115632 | None | code44 | Providing and laying water proofing treatment to the Roof with PU based single component elastomeric pure polyurethane based coating on New terrace/Chajjas/Sunken portion of WC:Bathroom, cold applied PU waterproofing membrane that is highly elastic with elongation greater than 400% and tensile strength greater than 2MPa as per ASTM D412. The waterproofing membrane to be applied in 2coats @ 1.6kg per m2 to achieve final DFT (dry film thickness) of 1mm including prime coat of epoxy primer @150 g per m2 and protection with 120gsm Geo-textile over the waterproofing membrane. The finished cost to include surface preparation, making coving at Junction, Bore Packing, treatment of construction joints completely as per specification & with a 10 years warranty on product & work from certified manufacturers as per the direction of the Engineer In charge.-Terrace Floor | Sqm | 841.51 | 841.51 | 744.47 | False | None | None | False | None | False | 626478.9497 | 0 |
3311357 | 115632 | None | code45 | Providing and laying cinder concrete in cement 1:15 ( 1 cement : 15 cinder of 12.5mm nominal gauge) on terraced roof or sunken slabs, laid to slope compacting, including cost of materials, labour, curing complete as per specifications.-FF | Sqm | 2098.29 | 2098.29 | 1.02 | False | None | None | False | None | False | 2140.2558 | 0 |
3311358 | 115632 | None | code46 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. ** Polished Granite stone slab Black, Cherry Red, Brown, Cat Eye, River Pink or equivalent.-Ground Floor | Sqm | 2937.56 | 2937.56 | 110.44 | False | None | None | False | None | False | 324424.1264 | 0 |
3311359 | 115632 | None | code47 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. ** Polished Granite stone slab Black, Cherry Red, Brown, Cat Eye, River Pink or equivalent.-First Floor | Sqm | 2966.94 | 2966.94 | 211.03 | False | None | None | False | None | False | 626113.3482 | 0 |
3311360 | 115632 | None | code48 | Providing edge moulding to 18mm thick Granite stone counters, vanities etc including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-charge. -First Floor | m | 337.84 | 337.84 | 183.77 | False | None | None | False | None | False | 62084.8568 | 0 |
3311361 | 115632 | None | code49 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ m2 including grouting the joints with white cement and matching pigments etc., complete.-- Size of Tile 800x800 mm-FF | Sqm | 1294.71 | 1294.71 | 500.58 | False | None | None | False | None | False | 648105.9318 | 0 |
3311362 | 115632 | None | code50 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ m2 including pointing the joints with white cement and matching pigments etc., complete -FF | Sqm | 924.83 | 924.83 | 3.45 | False | None | None | False | None | False | 3190.6635 | 0 |
3311363 | 115632 | None | code51 | Providing and fixing 1st quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer- in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per m2, including pointing in white cement mixed with pigment of matching shade complete.-FF | Sqm | 1150.57 | 1150.57 | 14.1 | False | None | None | False | None | False | 16223.037 | 0 |
3311364 | 115632 | None | code52 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of Engineer in charge.-Ground Floor | Sqm | 103.0 | 103.0 | 120.41 | False | None | None | False | None | False | 12402.23 | 0 |
3311365 | 115632 | None | code53 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of Engineer in charge.-First Floor | Sqm | 104.03 | 104.03 | 2234.43 | False | None | None | False | None | False | 232447.7529 | 0 |
3311366 | 115632 | None | code54 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of Engineer in charge.-Second Floor | Sqm | 105.06 | 105.06 | 69.72 | False | None | None | False | None | False | 7324.7832 | 0 |
3311367 | 115632 | None | code55 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications: Two coats applied on walls @ 1.25 ltr/10 m² over and including one coat of Specialprimer applied @ 0.75 ltr /10 m² with paint of approved quality to givean even shade, after thoroughly brooming the surface to remove all dirt,dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per
specifications and as per directions of Engineer-in-charge.-Ground Floor | Sqm | 162.74 | 162.74 | 108.96 | False | None | None | False | None | False | 17732.1504 | 0 |
3311368 | 115632 | None | code56 | Finishing with Deluxe Multi surface paint system for interiors and exteriors using Primer as per manufacturers specifications: Two coats applied on walls @ 1.25 ltr/10 m² over and including one coat of Specialprimer applied @ 0.75 ltr /10 m² with paint of approved quality to givean even shade, after thoroughly brooming the surface to remove all dirt,dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per
specifications and as per directions of Engineer-in-charge.-First Floor | Sqm | 164.37 | 164.37 | 676.37 | False | None | None | False | None | False | 111174.9369 | 0 |
3311369 | 115632 | None | code57 | Finishing with Deluxe Multi surface paint system for interiors andexteriors using Primer as per manufacturers specifications: Two coats applied on walls @ 1.25 ltr/10 m² over and including one coat of Specialprimer applied @ 0.75 ltr /10 m² with paint of approved quality to givean even shade, after thoroughly brooming the surface to remove all dirt,dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. Ground Floor | Sqm | 162.74 | 162.74 | 1558.06 | False | None | None | False | None | False | 253558.6844 | 0 |
3311370 | 115632 | None | code58 | Finishing with Deluxe Multi surface paint system for interiors andexteriors using Primer as per manufacturers specifications: Two coats applied on walls @ 1.25 ltr/10 m² over and including one coat of Specialprimer applied @ 0.75 ltr /10 m² with paint of approved quality to givean even shade, after thoroughly brooming the surface to remove all dirt,dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.-First Floor | Sqm | 164.37 | 164.37 | 1558.06 | False | None | None | False | None | False | 256098.3222 | 0 |
3311371 | 115632 | None | code59 | Finishing with Deluxe Multi surface paint system for interiors andexteriors using Primer as per manufacturers specifications: Two coats applied on walls @ 1.25 ltr/10 m² over and including one coat of Specialprimer applied @ 0.75 ltr /10 m² with paint of approved quality to givean even shade, after thoroughly brooming the surface to remove all dirt,dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.-Second Floor | Sqm | 165.99 | 165.99 | 69.72 | False | None | None | False | None | False | 11572.8228 | 0 |
3311372 | 115632 | None | code60 | Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two coat applied @ 1.67 ltr/10 m² over and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as
per specifications and as per directions of Engineer-in-charge.-First Floor | Sqm | 179.22 | 179.22 | 1054.61 | False | None | None | False | None | False | 189007.2042 | 0 |
3311373 | 115632 | None | code61 | Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two coat applied @ 1.67 ltr/10 m² over and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as
per specifications and as per directions of Engineer-in-charge.-Second Floor | Sqm | 182.8 | 182.8 | 69.72 | False | None | None | False | None | False | 12744.816 | 0 |
3311374 | 115632 | None | code62 | Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. First Floor-Window Grills | Sqm | 172.01 | 172.01 | 85.14 | False | None | None | False | None | False | 14644.9314 | 0 |
3311375 | 115632 | None | code63 | Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content. With ready mixed pink or grey primer on wood work (hard and soft wood) having VOC content less than 50 grams/ litre as per specifications and as per directions of Engineer in charge.-First Floor | Sqm | 58.26 | 58.26 | 99.98 | False | None | None | False | None | False | 5824.8348 | 0 |
3311376 | 115632 | None | code64 | Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content. With ready mixed pink or grey primer on wood work (hard and soft wood) having VOC content less than 50 grams/ litre as per specifications and as per directions of Engineer in charge.-Second Floor | Sqm | 58.83 | 58.83 | 6.0 | False | None | None | False | None | False | 352.98 | 0 |
3311377 | 115632 | None | code65 | Polishing on wood work with ready mixed wax polish of approved brand and manufacture : New work to give an even surface including preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, sand papering smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.-First Floor | Sqm | 140.44 | 140.44 | 99.98 | False | None | None | False | None | False | 14041.1912 | 0 |
3311378 | 115632 | None | code66 | Polishing on wood work with ready mixed wax polish of approved brand and manufacture : New work to give an even surface including preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, sand papering smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge.-Second Floor | Sqm | 141.83 | 141.83 | 6.0 | False | None | None | False | None | False | 850.98 | 0 |
3311379 | 115632 | None | code67 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in- charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts,bolts, fasteners etc.) including cost of materials, labour, usage charges
of machinery complete as per specifications and as per directions of the Engineer-in-Charge.-FF | Kg | 587.77 | 587.77 | 126.25 | False | None | None | False | None | False | 74205.9625 | 0 |
3311380 | 115632 | None | code68 | Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for:-PVC pipes 110mm dia., 6 kg/sqcm | m | 413.94 | 413.94 | 88.33 | False | None | None | False | None | False | 36563.3202 | 0 |
3311381 | 115632 | None | code69 | Providing and fixing Over deck insulation with cast insitu polyurethane foam (PUF) spray 50mm thick average with PU foam spray including necessary fasteners etc., complete covered with two layers of 40mm thick cement concrete screed with mix proportion 1:1.5:3 (M20grade) smooth finished with floating coat of neat cement, including necessary polymerized plaster reinforced with glass fibre mesh for PUF slab, epoxy bases bonding adhesive etc., complete-FF | Sqm | 1391.53 | 1391.53 | 6.8 | False | None | None | False | None | False | 9462.404 | 0 |
3311382 | 115632 | None | code70 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete | Nos | 133.9 | 133.9 | 28.0 | False | None | None | False | None | False | 3749.2 | 0 |
3311383 | 115632 | None | code71 | Providing and fixing magnetic catcher of approved quality in cupboard / ward robe shutters, including fixing with necessary screws etc. complete. | Nos | 60.77 | 60.77 | 10.0 | False | None | None | False | None | False | 607.7 | 0 |
3311384 | 115632 | None | code72 | Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete : | Nos | 93.73 | 93.73 | 112.0 | False | None | None | False | None | False | 10497.76 | 0 |
3311385 | 115632 | None | code73 | Providing and fixing bright finished brass handles with screws etc.complete: Brass handles 100 mm with plate 150x32 mm | Nos | 237.93 | 237.93 | 28.0 | False | None | None | False | None | False | 6662.04 | 0 |
3311386 | 115632 | None | code74 | Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete. | Nos | 1083.56 | 1083.56 | 8.0 | False | None | None | False | None | False | 8668.48 | 0 |
3311387 | 115632 | None | code75 | EUROPEAN TYPE WATER CLOSET Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings &
C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : W.C. pan with ISI marked white solid plastic seat and lid | Nos | 6176.91 | 6176.91 | 1.0 | False | None | None | False | None | False | 6176.91 | 0 |
3311388 | 115632 | None | code76 | WASH BASIN Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass single hole basin mixer of approved quality and make, including painting of fittings and brackets, cutting and making good the walls wherever required: using White Vitreous China Wash basin size 550x400 mm with a 15 mm CP Brass single hole basin mixer | Nos | 4244.63 | 4244.63 | 1.0 | False | None | None | False | None | False | 4244.63 | 0 |
3311389 | 115632 | None | code77 | Providing and fixing 100 mm sand cast Iron grating for gully
trap. | Nos | 48.41 | 48.41 | 5.0 | False | None | None | False | None | False | 242.05 | 0 |
3311390 | 115632 | None | code78 | Providing and fixing C.P. brass stop cock (concealed) of
standard design and of approved make conforming to IS:8931. | Nos | 746.75 | 746.75 | 1.0 | False | None | None | False | None | False | 746.75 | 0 |
3311391 | 115632 | None | code79 | Providing and fixing C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than
810 g. | Nos | 871.38 | 871.38 | 1.0 | False | None | None | False | None | False | 871.38 | 0 |
3311392 | 115632 | None | code80 | Providing and fixing Brass full way valve gate with C.I. wheel of
approved quality (screwed end) 25 mm nominal bore | m | 565.47 | 565.47 | 5.0 | False | None | None | False | None | False | 2827.35 | 0 |
3311393 | 115632 | None | code81 | 32 mm nominal bore | m | 615.94 | 615.94 | 5.0 | False | None | None | False | None | False | 3079.7 | 0 |
3311394 | 115632 | None | code82 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass
screws and washers complete. | Nos | 1256.6 | 1256.6 | 1.0 | False | None | None | False | None | False | 1256.6 | 0 |
3311395 | 115632 | None | code83 | 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190g. | Nos | 510.88 | 510.88 | 1.0 | False | None | None | False | None | False | 510.88 | 0 |
3311396 | 115632 | None | code84 | Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for:-PVC pipes 160mm dia., 6 kg/sqcm & class 3-(basic rate 599) | m | 616.97 | 616.97 | 200.0 | False | None | None | False | None | False | 123394.0 | 0 |
3311397 | 115632 | None | code85 | Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for:-PVC pipes 110mm dia., 6 kg/sqcm & class 3-(basic rate 394) | m | 405.82 | 405.82 | 30.0 | False | None | None | False | None | False | 12174.6 | 0 |
3311398 | 115632 | None | code86 | Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for:-PVC pipes 90mm dia., 6 kg/sqcm & class 3 (basic rate 281) | m | 289.43 | 289.43 | 20.0 | False | None | None | False | None | False | 5788.6 | 0 |
3311399 | 115632 | None | code87 | Providing and fixing Chorinated Poly Venly Cloride (CPVC) pipes conforming to IS15778, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipe with clamp at 1.00 mtr. spacing. This includes jointing of pipes and fitting with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete. (concealed work including cutting chases and good the walls
etc), For 50 mm dia | Mtr | 790.01 | 790.01 | 150.0 | False | None | None | False | None | False | 118501.5 | 0 |
3311400 | 115632 | None | code88 | Providing and fixing Chorinated Poly Venly Cloride (CPVC) pipes conforming to IS15778, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipe with clamp at 1.00 mtr. spacing. This includes jointing of pipes and fitting with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete. (concealed work including cutting chases and good the walls etc), For 25 mm dia | m | 325.48 | 325.48 | 100.0 | False | None | None | False | None | False | 32548.0 | 0 |
3311401 | 115632 | None | code89 | Providing and fixing Chorinated Poly Venly Cloride (CPVC) pipes conforming to IS15778, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipe with clamp at 1.00 mtr. spacing. This includes jointing of pipes and fitting with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete. (concealed work including cutting chases and good the walls etc), For 20 mm dia | Nos | 246.17 | 246.17 | 5.0 | False | None | None | False | None | False | 1230.85 | 0 |
3311402 | 115632 | None | code90 | INSPECTION CHAMBER (450x450mm) Providing PVC-U INDIVIDUAL U.G.D House service connection (which shall be laid from inside the customer property ) which includes: a) Supply of PVC-U pipe (b) providing and fixing of 315 mm dia the PE Inspection chambres with lid consisting of inlet & outlet arrangements with base, riser of min. 0.42 m depth which includes earth work, fixing in CC- 1:2:4 with appurtenances., complete. (c) civil works like Earthwork excavation for the pipeline trenches for laying of PVC-U pipes for the house connections in all types of soils , disintegrated rock,soft rock, hard rock, including cutting of any road using , crossing drains, compound, Dismantling of existing structures like culverts, bridges, retaining walls and other structure comprising of masonry, c.c. wood work, steel work, including T & P and scaffolding wherever necessary sorting the dismantled material, disposal of unserviceable and stacking the serviceable material with all lifts and lead , restoring the damaged portions inside or outside the property premises, refilling the portions of trenches that are dug open including linking to existing sewer network with appurtenances. complete.Supply and fixing of SFRC machinhole cover (Medium Duty) made as per IS to suit existing damaged machinhole cover after removing the debries from inside and outside the existing machinhole etc. with all lead
and lifts. 110 mm dia | Nos | 8057.69 | 8057.69 | 5.0 | False | None | None | False | None | False | 40288.45 | 0 |
3311403 | 115632 | None | code91 | KSRB 13-11 : Providing and placing on terrace, polyethylene water storage tanks as per IS 12701 : 1996 with manhole lid and suitable locking arrangements, making holes of suitable diameter for inlet, outlet and over flow pipes, including cost of all materials, labour, transport charges, HOM and testing complete as per specifications.
Specification No.KBS 13.22 | Ltr | 9.27 | 9.27 | 1000.0 | False | None | None | False | None | False | 9270.0 | 0 |
3311404 | 115632 | None | code92 | PVC Conduit and its Accessories Concealed Conduit System Supplying heavy gauge PVC conduit pipe … mm dia confirming to IS 2509 with suitable size bends, metal / PVC junction boxes adhesive paste etc. and running before Concreting the Slab. The Conduit should be tied to the reenforcement Rods by using binding wires and the unused ways of Junction boxes should be covered using PVC End enclosures .run with 18 SWG GI finish wire wherever it is necessory 19/20mm Dia 2mm Thick | Mtr | 66.0 | 66.0 | 1166.0 | False | None | None | False | None | False | 76956.0 | 0 |
3311405 | 115632 | None | code93 | 25mm dia 2mm Thick | Mtr | 78.0 | 78.0 | 1155.0 | False | None | None | False | None | False | 90090.0 | 0 |
3311406 | 115632 | None | code94 | 32mm dia 2.5mm thick | Mtr | 103.0 | 103.0 | 25.0 | False | None | None | False | None | False | 2575.0 | 0 |
3311407 | 115632 | None | code95 | Supplying heavy gauge PVC conduit pipe … mm dia confirming to IS 2509 with suitable size bends, metal / PVC junction boxes adhesive paste etc. by groove cutting in the wall and fixing by bracing U or J hooks and plastering upto wall surface and .run with 18 SWG GI finish wire wherever it is necessory 19/20mm Dia 2mm Thick | Mtr | 75.0 | 75.0 | 385.0 | False | None | None | False | None | False | 28875.0 | 0 |
3311408 | 115632 | None | code96 | 25mm dia 2mm Thick | Mtr | 80.0 | 80.0 | 330.0 | False | None | None | False | None | False | 26400.0 | 0 |
3311409 | 115632 | None | code97 | 32mm dia 2.5mm thick | Mtr | 105.0 | 105.0 | 50.0 | False | None | None | False | None | False | 5250.0 | 0 |
3311410 | 115632 | None | code98 | Supplying and fixing PVC/ Metal Conduit Deep Junction Boxes 19/20 mm Deep Junction Box | Each | 49.0 | 49.0 | 92.0 | False | None | None | False | None | False | 4508.0 | 0 |
3311411 | 115632 | None | code99 | 25 mm Deep Junction Box | Each | 51.0 | 51.0 | 10.0 | False | None | None | False | None | False | 510.0 | 0 |
3311412 | 115632 | None | code100 | Supplying and fixing PVC Casing and capping on the wall or ceiling using materials like bend , screws at an interval 0f 300 mm etc 20 mm | Mtr | 28.0 | 28.0 | 20.0 | False | None | None | False | None | False | 560.0 | 0 |
3311413 | 115632 | None | code101 | 25 mm | Mtr | 35.0 | 35.0 | 15.0 | False | None | None | False | None | False | 525.0 | 0 |
3311414 | 115632 | None | code102 | 32 mm | Mtr | 43.0 | 43.0 | 15.0 | False | None | None | False | None | False | 645.0 | 0 |
3311415 | 115632 | None | code103 | Supplying PVC /GI flexible conduit pipe …. Mm dia fixing on surface cover inverted tapared wodden plugs or phill plugs or rawl plugs and clamped using heavy guage saddles in an interval of 300 mm using NF screws and on the eaiter end of the pipe terminated properly 20 mm | Mtr | 19.0 | 19.0 | 25.0 | False | None | None | False | None | False | 475.0 | 0 |
3311416 | 115632 | None | code104 | 25 mm | Mtr | 22.0 | 22.0 | 25.0 | False | None | None | False | None | False | 550.0 | 0 |
3311417 | 115632 | None | code105 | Supply & Fixing of Metal fan box with round Hook | Each | 117.0 | 117.0 | 53.0 | False | None | None | False | None | False | 6201.0 | 0 |
3311418 | 115632 | None | code106 | Point wiring using copper wire without Switch Supplying and wiring adopting loop system in existing PVC conduit/casing capping, using copper FRLS PVC insulated multi strand 2 x 1.5 sq.mm copper wire without switch, the other end of the wires shall be terminated with sufficient loose length in a wood/pvc round block complete for each outlet. Short point upto 3 Mtd. From Tapping point to outlet via switch box. | Point | 269.0 | 269.0 | 46.0 | False | None | None | False | None | False | 12374.0 | 0 |
3311419 | 115632 | None | code107 | Medium point above 3 Mts upto 6 Mts. From tapping point to outlet via switch box. | Point | 379.0 | 379.0 | 86.0 | False | None | None | False | None | False | 32594.0 | 0 |
3311420 | 115632 | None | code108 | Long point above 6 Mts. Upto 10 Mts. From tapping of point to outlet via switch box. | Point | 555.0 | 555.0 | 35.0 | False | None | None | False | None | False | 19425.0 | 0 |
3311421 | 115632 | None | code109 | Two outlet in a row above 3 Mts upto 6 Mts, from tapping point to outlet via switch box. | Point | 677.0 | 677.0 | 10.0 | False | None | None | False | None | False | 6770.0 | 0 |
3311422 | 115632 | None | code110 | Three outlet in a row, above 6 Mts. Upto 10 Mts. From tapping point to outlet via switch box. | Point | 989.0 | 989.0 | 7.0 | False | None | None | False | None | False | 6923.0 | 0 |
3311423 | 115632 | None | code111 | Wiring for Lighting/ Power Circuit using one of PVC insulated 1100V grade, multistrand Copper conductor 1C cable in open or Concealed system of Wiring 1.5 Sqmm | Mtr | 26.0 | 26.0 | 1056.0 | False | None | None | False | None | False | 27456.0 | 0 |
3311424 | 115632 | None | code112 | 2.5Sqmm | Mtr | 42.0 | 42.0 | 1155.0 | False | None | None | False | None | False | 48510.0 | 0 |
3311425 | 115632 | None | code113 | 4Sqmm | Mtr | 63.0 | 63.0 | 240.0 | False | None | None | False | None | False | 15120.0 | 0 |
3311426 | 115632 | None | code114 | 6 sqmm | Mtr | 92.0 | 92.0 | 120.0 | False | None | None | False | None | False | 11040.0 | 0 |
3311427 | 115632 | None | code115 | 10Sqmm | Mtr | 167.0 | 167.0 | 50.0 | False | None | None | False | None | False | 8350.0 | 0 |
3311428 | 115632 | None | code116 | Supplying and Flush mounting Powder coated / galvanised metal box suitable for mounting modular switch plates . The Box should be firmly flush mounted after due groove cutting in brick / Stone / C.C wall Make : Anchor / Schneider / Legrand 1-3 way | Each | 138.0 | 138.0 | 45.0 | False | None | None | False | None | False | 6210.0 | 0 |
3311429 | 115632 | None | code117 | 6 way | Each | 177.0 | 177.0 | 7.0 | False | None | None | False | None | False | 1239.0 | 0 |
3311430 | 115632 | None | code118 | 12 way | Each | 261.0 | 261.0 | 11.0 | False | None | None | False | None | False | 2871.0 | 0 |
3311431 | 115632 | None | code119 | Supplying and fixing Superior Quality modular switch mounting poly carbonate plate with necessory supporting back plate with required no. of machine screws , bolts nuts etc. complte on existing metal / PVC box 1-3 way | Each | 137.0 | 137.0 | 45.0 | False | None | None | False | None | False | 6165.0 | 0 |
3311432 | 115632 | None | code120 | 6 way | Each | 175.0 | 175.0 | 7.0 | False | None | None | False | None | False | 1225.0 | 0 |
3311433 | 115632 | None | code121 | 10-12 way | Each | 284.0 | 284.0 | 11.0 | False | None | None | False | None | False | 3124.0 | 0 |
3311434 | 115632 | None | code122 | Supply and fixing of modular switch /socket /stepped electronic fan regulator/ dimmer telephone socket etc on existing modular switch plate 6 Amp one way | Each | 102.0 | 102.0 | 182.0 | False | None | None | False | None | False | 18564.0 | 0 |
3311435 | 115632 | None | code123 | 6 Amps 2 way | Each | 166.0 | 166.0 | 12.0 | False | None | None | False | None | False | 1992.0 | 0 |
3311436 | 115632 | None | code124 | 6 Amps socket | Each | 171.0 | 171.0 | 225.0 | False | None | None | False | None | False | 38475.0 | 0 |
3311437 | 115632 | None | code125 | Stepped Fan Regulator | Each | 357.0 | 357.0 | 110.0 | False | None | None | False | None | False | 39270.0 | 0 |
3311438 | 115632 | None | code126 | 16 Amps 1 way switch | Each | 180.0 | 180.0 | 22.0 | False | None | None | False | None | False | 3960.0 | 0 |
3311439 | 115632 | None | code127 | 6 Amps Bell Push | Each | 177.0 | 177.0 | 2.0 | False | None | None | False | None | False | 354.0 | 0 |
3311440 | 115632 | None | code128 | 32 Amps DP Switch | Each | 326.0 | 326.0 | 10.0 | False | None | None | False | None | False | 3260.0 | 0 |
3311441 | 115632 | None | code129 | 6/16 Amps universal socket | Each | 236.0 | 236.0 | 22.0 | False | None | None | False | None | False | 5192.0 | 0 |
3311442 | 115632 | None | code130 | LUMINERIES & LIGHT FIXTURES & ACCESSORIESMake : Panasonic/Phillips / Crompton Led Light Fixture 4 feet - 20/22 W | Each | 690.0 | 690.0 | 104.0 | False | None | None | False | None | False | 71760.0 | 0 |
3311443 | 115632 | None | code131 | Led Street Light70 watts | Each | 5992.0 | 5992.0 | 6.0 | False | None | None | False | None | False | 35952.0 | 0 |
3311444 | 115632 | None | code132 | Supplying and fixing regular MCB distribution Boards on Wall / wood board /flush mounting using required clamps bolts nuts etc with provision for fixing suitable type capacity MCB single phase / 3 phase / single door with powder coated paiting Double Door 8Way SP &N | Nos | 1854.0 | 1854.0 | 1.0 | False | None | None | False | None | False | 1854.0 | 0 |
3311445 | 115632 | None | code133 | 6Way TP &N | Nos | 4940.0 | 4940.0 | 1.0 | False | None | None | False | None | False | 4940.0 | 0 |
3311446 | 115632 | None | code134 | 8Way TP &N | Nos | 6091.0 | 6091.0 | 1.0 | False | None | None | False | None | False | 6091.0 | 0 |
3311447 | 115632 | None | code135 | Supplying fixing & wiring earth leakage miniature circuit breaker (ELMCB) 240 / 450 V up to 300mA sensitivity on Existing / panel Board 16 - 25 Amps 2 pole | Nos | 4277.0 | 4277.0 | 3.0 | False | None | None | False | None | False | 12831.0 | 0 |
3311448 | 115632 | None | code136 | 32 - 40 Amps 2 pole | Nos | 4559.0 | 4559.0 | 4.0 | False | None | None | False | None | False | 18236.0 | 0 |
3311449 | 115632 | None | code137 | 32 - 40 Amps 4 pole | Nos | 5147.0 | 5147.0 | 2.0 | False | None | None | False | None | False | 10294.0 | 0 |
3311450 | 115632 | None | code138 | Supplying and Fixing miniature circuit breakers on existing MCB distribution boards using necessory fixing materials & C type curve indicator ON OFF energy cross 3 with short circuit breaking capacity of 10 K and complete wiring as required confirming to IEC 60898 5 - 32 Amp SP | Nos | 210.0 | 210.0 | 60.0 | False | None | None | False | None | False | 12600.0 | 0 |
3311451 | 115632 | None | code139 | Supplying Fixing and Wiring earth electrode for grounding of lifts,Xmer, DG Sets etc using 40mm dia 2.9mm thick, 2.5mtr long GI pipe with GI funnel with mesh & suitable size reducer fixed on the top of Electrode. The funnel should be enclosed in a cc chamber of 400x400x400 with a cast iron cover. The Earth electrode shall have staggered holes of 12mm dia & electrode shoulde be covered 150mm around with alternate layers of salt & charcoal from the bottom of the CC Chamber. The connection from the electrode is to be established throgh GI strip using GI bolts & nuts. | Nos | 4150.0 | 4150.0 | 2.0 | False | None | None | False | None | False | 8300.0 | 0 |
3311452 | 115632 | None | code140 | Supplying & running of GI/Cu. Strips for grounding connections using necessary fixing material as required…..GI Strip 25 x 3 mm G.I strip. | m | 75.0 | 75.0 | 60.0 | False | None | None | False | None | False | 4500.0 | 0 |
3311453 | 115632 | None | code141 | GI wire 12 SWG GI wire | m | 14.0 | 14.0 | 200.0 | False | None | None | False | None | False | 2800.0 | 0 |
3311454 | 115632 | None | code142 | 2C x 10sq.mm. Al. Alum. Cable | Mtr | 95.0 | 95.0 | 30.0 | False | None | None | False | None | False | 2850.0 | 0 |
3311455 | 115632 | None | code143 | 4C x 10sq.mm. Al. Alum. Cable | Mtr | 130.0 | 130.0 | 40.0 | False | None | None | False | None | False | 5200.0 | 0 |
3311456 | 115632 | None | code144 | 4C x 16sq.mm. Al. Alum. Cable | Mtr | 150.0 | 150.0 | 20.0 | False | None | None | False | None | False | 3000.0 | 0 |
3311457 | 115632 | None | code145 | 48 INCHES Sweep Economy model | Each | 2085.0 | 2085.0 | 48.0 | False | None | None | False | None | False | 100080.0 | 0 |