3379529 | 119010 | None | code01 | Earth work excavation for Foundation by mechanical means for all kinds of soil & depth as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work with all leads & lift complete as per specification and as directed by the engineer of the work. | Cum | 107.1 | 107.1 | 1535.3625 | False | None | None | False | None | False | 164437.32375 | 0 |
3379530 | 119010 | None | code02 | Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, and all the other appurtenances required to complete the work as per technical specifications Mix 1:4:8 Using 40 mm nominal size graded crushed coarse aggregates with all leads & lift complete as per specification and as directed by the engineer of the work. | Cum | 5947.2 | 5947.2 | 72.1925 | False | None | None | False | None | False | 429343.236 | 0 |
3379531 | 119010 | None | code03 | Providing and laying in position Cement Concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates with all leads & lift complete as per specification and as directed by the engineer of the work. this rate is inclusive of formwork. | Cum | 6971.1 | 6971.1 | 78.9 | False | None | None | False | None | False | 550019.79 | 0 |
3379532 | 119010 | None | code04 | Providing and laying in position Cement Concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates with all leads & lift complete as per specification and as directed by the engineer of the work. his rate is inclusive of formwork. | Cum | 8962.85 | 8962.85 | 157.81 | False | None | None | False | None | False | 1414427.3585 | 0 |
3379533 | 119010 | None | code05 | Providing and laying in position Cement Concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, confirming to therequirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates with all leads & lift complete as per specification and as directed by the engineer of the work. this rate is inclusive of formwork. | Cum | 6985.44 | 6985.44 | 6.72 | False | None | None | False | None | False | 46942.1568 | 0 |
3379534 | 119010 | None | code06 | Providing and laying in position Cement Concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates this rate is inclusive of formwork. | Cum | 7983.36 | 7983.36 | 22.9125 | False | None | None | False | None | False | 182918.736 | 0 |
3379535 | 119010 | None | code07 | Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification. with all leads & lift complete as per specification and as directed by the engineer of the work. | Tonne | 82961.55 | 82961.55 | 13.48 | False | None | None | False | None | False | 1118321.694 | 0 |
3379536 | 119010 | None | code08 | Construction of Embankment by excavating the available approved Gravel/Murrum deposited at a place or borrow pits during or prior excavation with all lifts and lead, transportation to site, spreading, grading to required slope and compacting to meet the requirement complete as per specifications, including cost of labour,rolling,water,all materials,usage& all other appurtenaces required to complete the work. | Cum | 497.7 | 497.7 | 788.53 | False | None | None | False | None | False | 392451.381 | 0 |
3379537 | 119010 | None | code09 | Construction of sub-grade and earthen shoulders with approved material obtained from borrow pits with all lifts & leads, transporting to site, spreading, grading to required slope and compacted to meet requirement of table No. 300-2 | Cum | 517.65 | 517.65 | 374.22 | False | None | None | False | None | False | 193714.983 | 0 |
3379538 | 119010 | None | code10 | Construction of Granular Sub-Base of required grading as per design mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401 For Grading -V Material with all leads & lift complete as per specification and as directed by the engineer of the work. | Cum | 2611.35 | 2611.35 | 414.31 | False | None | None | False | None | False | 1081908.4185 | 0 |
3379539 | 119010 | None | code11 | Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 14:1, aggregate gradation after blending to be as per table 600-1, cement content not to be less than 140 kg/ m3 , optimum moisture content to be determined during trial length construction, concrete strength not to be less than 7 Mpa at 7 days, mixed in a batching plant, transported to site, laid with a paver with electronic sensor, compacting with 8-10 t vibratory roller, finishing and curing with all leads & lift complete as per specification and as directed by the engineer of the work. | Cum | 5166.0 | 5166.0 | 276.21 | False | None | None | False | None | False | 1426900.86 | 0 |
3379540 | 119010 | None | code12 | Providing and constructing un-reinforced plain cement concrete pavement, thickness as per design, over a prepare sub base, with 43 grade cement or any other type as per Clause 1501.2.2 M30 (Grade), coarse and fine aggregates conforming to IS:383:2016:, maximum size of coarse aggregate not exceeding 25 mm, mixed in a concrete mixer of not less than 0.2 cum capacity and appropriate weigh batcher using approved mix design, laid in approved fixed side formwork (steel channel, laying and fixing of 125 micron thick polythene film, wedges, steel plates including levelling the formwork as per drawing), spreading the concrete with shovels, rakes, compacted using needle, screed and plate vibrators and finished in continuous operation including construction joints, primer, sealant, curing of concrete slabs for 14-days, and water finishing to lines and grade as per drawing and technical specification clause 1501 with all lead, lifts, loading & unloading charges, cost and conveyance of all materials, labour, equipments etc., with all leads & lift complete as per specification and as directed by the engineer of the work. | Cum | 7091.7 | 7091.7 | 614.79 | False | None | None | False | None | False | 4359906.243 | 0 |
3379541 | 119010 | None | code13 | Providing and fixing in position 25mm dia dowel bars precoated with anticorrosive epoxy paint of required Dia. 600 mm. Long and at 300 mm. C/C and wherever directed including handling, straightening, necessary cutting supported by TMT, chairs with proper alignment by using properly designed assembly of Bulkheads lubricating half length with bituminous paint as directed etc. with all leads & lift complete as per specification and as directed by the engineer of the work. | Nos | 399.0 | 399.0 | 150.0 | False | None | None | False | None | False | 59850.0 | 0 |
3379542 | 119010 | None | code14 | Providing and fixing in position, tie bars precoated with anticorrosive epoxy paint of 12 mm dia. 700 mm. long and at 300 mm. C/C and wherever directed including handling, straightening wrapping with paper of approved quality for half length, necessary cutting, handling, straightening , supported by assembly of TMT FE 500, chairs with proper alignment etc. complete | Nos | 283.5 | 283.5 | 990.0 | False | None | None | False | None | False | 280665.0 | 0 |
3379543 | 119010 | None | code15 | Providing and laying of a reinforced cement concrete pipe duct, 300 mm dia, across the road (new construction), extending from drain to drain in cuts and toe of slope to toe of slope in fills, constructing head walls at both ends, providing a minimum fill of granular material over top and sides of RCC pipe as per IRC:98-1997, bedded on a 0.3 m thick layer of granular material free of rock pieces, outer to outer distance of pipe at least half dia of pipe subject to minimum 450 mm in case of double and triple row ducts, joints to be made leak proof, invert level of duct to be above higher than ground level to prevent entry of water and dirt, all as per IRC: 98 - 1997 and approved drawings. Single row for one utility service with all leads & lift complete as per specification and as directed by the engineer of the work. | Rmtr | 2322.6 | 2322.6 | 128.0 | False | None | None | False | None | False | 297292.8 | 0 |
3379544 | 119010 | None | code16 | Constructing brick masonry chamber for underground C.I. inspection chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg), R.C.C. top slab with 1:1.5:3 mix (1 cement : 1.5 fine sand : 3 graded stone aggregate 20 mm nominal size), foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand), finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design: Inside dimensions 455x610 mm and 45 cm deep for single pipe line : With common burnt clay (non modular) bricks of class designation 3.5 Extra for depth beyond 45 cm of brick masonry chamber : For 455x610 mm size With common burnt clay (non modular) bricks of class designation 3.5 with all leads & lift complete as per specification and as directed by the engineer of the work. | Each | 6764.1 | 6764.1 | 20.0 | False | None | None | False | None | False | 135282.0 | 0 |
3379545 | 119010 | None | code17 | Open Conduit System Supplying heavy gauge PVC conduit pipe …….dia .......mm thick confirming to IS 2509 with suitable size bends, junction boxes, adhesive paste etc., and fixing using inverted wood plugs in case of RCC ceiling and RCC wall / stone structure or rawl plugs in case of brick walls and cement plastering the damaged portion using heavy gauge saddles at an interval of 700mm using NF screws.40 mm dia 2.5 mm thick .with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 156.45 | 156.45 | 110.0 | False | None | None | False | None | False | 17209.5 | 0 |
3379546 | 119010 | None | code18 | Supplying and drawing Flexible Multicore Cable manufactured with electrolytic grade flexible copper with low conductor confirming to IS 8130-1984 and (Virgin) PVC insulation sheathed suitable for working voltage upto 1100V as per IS- 694:2010 3C x 2.5 mm2 with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 118.65 | 118.65 | 420.0 | False | None | None | False | None | False | 49833.0 | 0 |
3379547 | 119010 | None | code19 | Fabricating, supplying and erecting swaged tubular pole of height …Mtr having three sections, and providing twocoats of red oxide paint and finished with two coats of enamelled paint of approved quality and colour and M.S. base plate of suitable size welded at the bottom of the pole(as per IS) and 40mm dia GI / flexible PVC pipe of 1 mtr length fitted to the heavy gauge polycarbonate control box including 5way connector of size 167x125x82mm for 7.5M pole/200x160x98mm for remaining length of pole with front opening cover, with locking arrangements and suitable capacity MCB / DP switch, The pole shall be erected in cement concrete work (1:2:4) including excavation and refilling of planting depth of the pole to the ground level and the coping CC shall be up to 0.6M above ground level as per IS 2713 - 7.Erection of heavy duty pole on Footpath / median 10Mt (5Mt Hb,165.1mm dia 4.85mm thick x3M Hm, 139.7mm dia 4.50mm thick x 2M. Ht,114.3mm dia 3.65mm thick) as per IS 410 SP 47. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 20055.0 | 20055.0 | 55.0 | False | None | None | False | None | False | 1103025.0 | 0 |
3379548 | 119010 | None | code20 | Supplying and fixing telescopic M.S.bracket fabricated by using 0.5m length 4"dia telescopic M.S.pipe,with2"dia1.5m longM.S.Bracket and are welded with suitable angle,using 6mm thick M.S.sheet,grip bolts&nuts,a srequired,suitable for 9to12ms.M.S.tubular pole,with necessary two coats of painting,with all other accessories.Single bracket 1.5 m. Length with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 1534.05 | 1534.05 | 55.0 | False | None | None | False | None | False | 84372.75 | 0 |
3379549 | 119010 | None | code21 | Supplying and fixing of 4 pole power contactor with NO/NC contacts on existing wood/panel boaard using necessary bolts,nuts, washers and wiring etc., completee with ac-3 rating and as per IS-13947 40 Amps. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 6424.95 | 6424.95 | 2.0 | False | None | None | False | None | False | 12849.9 | 0 |
3379550 | 119010 | None | code22 | Supply and Installation / Fixing / Provision of Outdoor type Thermoplastic Modular Panel enclosure with transparent Polycarbonate Lid, shock proof, IP65 (Weather Proof), rust proof, dust proof, water proof, corrosion proof having internally Embedded gasket on both lid and flap suitable to fix Single Phase / Three Phase Energy Meter in suitable base plate and having a provision for Fuse / MCB cutout with suitable transparent hinged flap opening for operating MCB along with complete tamper proof SEALING facility.600mmx600mmx170mm | No | 15246.0 | 15246.0 | 2.0 | False | None | None | False | None | False | 30492.0 | 0 |
3379551 | 119010 | None | code23 | Supplying and fixing Microprocessor Based Astronomical timer Switch with using necessary bolts, nuts and washers. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 5085.15 | 5085.15 | 2.0 | False | None | None | False | None | False | 10170.3 | 0 |
3379552 | 119010 | None | code24 | Supply of LED Streetlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation.Lamp compartment comprising of anti glare clear diffuse with Injection molded poly carbonate material, delivering superior light output. Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, maximum light intensity should be between 60 degrees to 70 degrees. CCT 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminary IK08. Power Factor 0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole muting with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100V to 270V 50/60Hz application. Compliance to IS 10322/IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with ........W System Power consumption. LED Efficiency 130lm/w, nominal CRI 75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008 . Housing with supplier word mark /name shall be Engraved / Embossing on the die cast housing/ Body part. Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer & Cree/Nichia/ Lumileds/Osram make LED Source. LED Streetlight 90 W with all leads & lift complete as per specification and as directed by the engineer of the work.MAKE PHILIPS, BAJAJ, CREE, LUMI LEDS, OS RAM EQUIVALENT. | No | 9303.0 | 9303.0 | 86.0 | False | None | None | False | None | False | 800058.0 | 0 |
3379553 | 119010 | None | code25 | Fixing halogen/metal halide / SVL / IL / LED floodlight fitting over existing pole / wall ceiling including clamps, bolts, nuts and wiring using suitable capacity wires with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 170.1 | 170.1 | 86.0 | False | None | None | False | None | False | 14628.6 | 0 |
3379554 | 119010 | None | code26 | Supplying and fixing Moulded Case Circuit Breaker(MCCB) over theexisting wood/panel board using necessary screws,bolts,nuts,necessary phase separators,handle and wiring complete.Protection of Over load and Short circuit with adjustable thermal magnetic release,Microprocessor release shall have Earth Fault as per IS/IEC60947 2.(Icu=100%lcs).In 4P MCCB,all Poles should have protection for Short Cicrcuit / Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non Priority loads must be available in the MCCB.MCCB shall be provided with double insulation(insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open)Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.100 A 25 kA with all leads & lift complete as per specification and as directed by the engineer of the work.MAKE LEGRAND, GM, PM CONA, ANCHOR, HAVELLS, LISHA OR EQUIVALENT | No | 8911.35 | 8911.35 | 6.0 | False | None | None | False | None | False | 53468.1 | 0 |
3379555 | 119010 | None | code27 | Supplying and fixing Moulded Case Circuit Breaker(MCCB) over theexisting wood/panel board using necessary screws,bolts,nuts,necessary phase separators,handle and wiring complete.Protection of Over load and Short circuit with adjustable thermal magnetic release,Microprocessor release shall have Earth Fault as per IS/IEC60947 2.(Icu=100%lcs).In 4P MCCB,all Poles should have protection for Short Cicrcuit / Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non Priority loads must be available in the MCCB.MCCB shall be provided with double insulation(insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open)Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.200 A 36 kA with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE LEGRAND, GM, PM CONA, ANCHOR, HAVELLS, LISHA OR EQUIVALENT | No | 22495.2 | 22495.2 | 4.0 | False | None | None | False | None | False | 89980.8 | 0 |
3379556 | 119010 | None | code28 | Supplying and fixing of Shunt trip suitable for MCCB.CBCT with all leads & lift complete as per specification and as directed by the engineer of the work | No | 1788.15 | 1788.15 | 4.0 | False | None | None | False | None | False | 7152.6 | 0 |
3379557 | 119010 | None | code29 | Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.6-32 Amps SP with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE LEGRAND, GM, PM CONA, ANCHOR, HAVELLS, LISHA OR EQUIVALENT | No | 435.75 | 435.75 | 42.0 | False | None | None | False | None | False | 18301.5 | 0 |
3379558 | 119010 | None | code30 | Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.6-32 Amps DP. with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE LEGRAND, GM, PM CONA, ANCHOR, HAVELLS, LISHA OR EQUIVALENT | No | 775.95 | 775.95 | 4.0 | False | None | None | False | None | False | 3103.8 | 0 |
3379559 | 119010 | None | code31 | Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898.50-63 Amps TPN. with all leads & lift complete as per specification and as directed by the engineer of the work. LEGRAND, GM, PM CONA, ANCHOR, HAVELLS, LISHA OR EQUIVALENT | No | 3242.4 | 3242.4 | 6.0 | False | None | None | False | None | False | 19454.4 | 0 |
3379560 | 119010 | None | code32 | Supplying, fixing and wiring earth leakage relay with core balanced current transformer suitable for single phase 50 Hz AC with latest microcontroller based, digital readout of percentage leakage current, programmable delay/auto/ manual reset facility suitable to mount on DIN rail/ flush mounting on panel board. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 9717.75 | 9717.75 | 2.0 | False | None | None | False | None | False | 19435.5 | 0 |
3379561 | 119010 | None | code33 | Supplying of multi function digital meter with three line back light LCD type display for voltage, Current, frequency, Power, power factor, KVA, KWH,KVAR suitable for 3 phase, 4 wire LT network with IP 54 degree of protection and completely wired as required with communication Port and Class 0.5s accuracy.with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 9780.75 | 9780.75 | 4.0 | False | None | None | False | None | False | 39123.0 | 0 |
3379562 | 119010 | None | code34 | Supplying, fixing and wiring 50/5 to 400/5Amps 5VA burden Current Transformer. Class 0.5 accuracy with Tape Wound. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 590.1 | 590.1 | 12.0 | False | None | None | False | None | False | 7081.2 | 0 |
3379563 | 119010 | None | code35 | Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 220v A.C. 50 Hz 12/24v D.C. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 540.75 | 540.75 | 42.0 | False | None | None | False | None | False | 22711.5 | 0 |
3379564 | 119010 | None | code36 | Supplying ......... amps rated 3phase with neutral bus bar using required capacity electrolytic aluminum strips covered with heat shrinkable coloured PVC sleeve, mounted on phenolic/FRP/DMC insulator which are mounted on powder coated 40x6mm M.S.flat frame work in existing panel board. The bus bar shall have suitable holes for termination of incoming and outgoing cables as per IS specification with necessary bolts, nuts and washers etc., complete.250Amps 4x30x10mm Aluminium Strips with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 3606.75 | 3606.75 | 24.0 | False | None | None | False | None | False | 86562.0 | 0 |
3379565 | 119010 | None | code37 | Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. flat … with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint.40*40*6mm with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 320.25 | 320.25 | 20.0 | False | None | None | False | None | False | 6405.0 | 0 |
3379566 | 119010 | None | code38 | Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. flat … with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint.50x50x6mm with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 414.75 | 414.75 | 20.0 | False | None | None | False | None | False | 8295.0 | 0 |
3379567 | 119010 | None | code39 | Supplying and fixing angle iron frame work fabricated out of M.S. angle iron.. and M.S. flat … with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint.50X100X50X6mm C channel with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 793.8 | 793.8 | 20.0 | False | None | None | False | None | False | 15876.0 | 0 |
3379568 | 119010 | None | code40 | Fabricating supplying and mounting MS box made out … SWG suitable for floor / wall mounting, fully weather proof with provision for better heat dissipation, provided with hinged front cover, equipped with tamper proof locking arrangements, with suitable size clamps with necessary cable entry pipe with gland and box should be finished with 2 coats of red oxide primer paint and finally finished with approved colour enameled metal paint etc., complete.14SWG with all leads & lift complete as per specification and as directed by the engineer of the work. | Sq CM | 0.52 | 0.52 | 520000.0 | False | None | None | False | None | False | 270400.0 | 0 |
3379569 | 119010 | None | code41 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.6 sqmm with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE HAVELLS, POLYCAB, FINOLEX, KEI, V-GUARD | Mtr | 96.6 | 96.6 | 120.0 | False | None | None | False | None | False | 11592.0 | 0 |
3379570 | 119010 | None | code42 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.10 sqmm with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE HAVELLS, POLYCAB, FINOLEX, KEI, V-GUARD | Mtr | 175.35 | 175.35 | 100.0 | False | None | None | False | None | False | 17535.0 | 0 |
3379571 | 119010 | None | code43 | Supply of 11 kV [6.35/11 kV(E)], HT Aerial Bunched Cable XLPE insulation confirming to IS-14255: 1995 3x95 + 1x70 Sqmm (Insulated Messenger Wire). with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE HAVELLS, POLYCAB, FINOLEX, KEI, UNIVERSAL CABLES | Km | 1007716.5 | 1007716.5 | 0.6 | False | None | None | False | None | False | 604629.9 | 0 |
3379572 | 119010 | None | code44 | Stringing of 11 kV grade Aerial Bunched 3 Core cable of XLPE insulation of size 3x95 Sqmm + 1x70 Sqmm with Insulated Messenger Wire. with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE HAVELLS, POLYCAB, FINOLEX, KEI, UNIVERSAL CABLES | Km | 36503.25 | 36503.25 | 0.6 | False | None | None | False | None | False | 21901.95 | 0 |
3379573 | 119010 | None | code45 | Supply of 11 kV, AB Cable Straight thru' joint kit suitable for 95 Sqmm. with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 8069.25 | 8069.25 | 4.0 | False | None | None | False | None | False | 32277.0 | 0 |
3379574 | 119010 | None | code46 | Laying of 11 kV AB Cable Straight thru' joint installation for 3 Core with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 1495.2 | 1495.2 | 4.0 | False | None | None | False | None | False | 5980.8 | 0 |
3379575 | 119010 | None | code47 | Supply of 11 kV, ABC Termination kit 95 -120 Sqmm. with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 2998.8 | 2998.8 | 4.0 | False | None | None | False | None | False | 11995.2 | 0 |
3379576 | 119010 | None | code48 | Laying of 11 kV AB Cable Termination installation for 3 Core. with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 1195.95 | 1195.95 | 4.0 | False | None | None | False | None | False | 4783.8 | 0 |
3379577 | 119010 | None | code49 | Supply of Suspension Clamp Assembly 16 to 70 Sqmm Bare Messenger (Exclusive of Pole Clamp and Eye Hook).with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 232.05 | 232.05 | 19.0 | False | None | None | False | None | False | 4408.95 | 0 |
3379578 | 119010 | None | code50 | Laying of Erection of Suspension Clamp - 25 to 95 Sqmm bare/Insulated messenger. with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 100.8 | 100.8 | 19.0 | False | None | None | False | None | False | 1915.2 | 0 |
3379579 | 119010 | None | code51 | Supply of Pole Clamp for HT/LT AB cable.. with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 114.45 | 114.45 | 19.0 | False | None | None | False | None | False | 2174.55 | 0 |
3379580 | 119010 | None | code52 | Fixing of Pole Clamp-145 mm x 95 with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 168.0 | 168.0 | 19.0 | False | None | None | False | None | False | 3192.0 | 0 |
3379581 | 119010 | None | code53 | Supply of 1.1 kV, 3 Phase Aerial Bunched Cable of size3x95+1x16+1x70 Sqmm.with all leads & lift complete as per specification and as directed by the engineer of the work. | Km | 518795.55 | 518795.55 | 1.85 | False | None | None | False | None | False | 959771.7675 | 0 |
3379582 | 119010 | None | code54 | Stringing of 1.1 kV grade Aerial Bunched 3 Core cable of XLPE insulation of size (3x95) (Phase Conductor) + (1x70) (Insulated Messenger Neutral) + (1x16) (Street Light Control). with all leads & lift complete as per specification and as directed by the engineer of the work. | Km | 34764.45 | 34764.45 | 1.85 | False | None | None | False | None | False | 64314.2325 | 0 |
3379583 | 119010 | None | code55 | Supply of Piercing connector suitable for 16 Sqmm - 95Sqmm AB Cable - Service Connections.with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 278.25 | 278.25 | 240.0 | False | None | None | False | None | False | 66780.0 | 0 |
3379584 | 119010 | None | code56 | Installation of Insulation piercing connector for Main to Service Line Main : 16-95 Sqmm, Tap: 4-35 Sqmm (P2X95) with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 134.4 | 134.4 | 240.0 | False | None | None | False | None | False | 32256.0 | 0 |
3379585 | 119010 | None | code57 | Supply of Piercing connector suitable for 16 Sqmm - 95 Sqmm AB Cable - Street Light Connections. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 195.3 | 195.3 | 80.0 | False | None | None | False | None | False | 15624.0 | 0 |
3379586 | 119010 | None | code58 | Installation of Insulation piercing connector for Main to Street Light Main : 16-95 Sqmm, Tap: 1.5-10 Sqmm (EP95).with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 94.5 | 94.5 | 80.0 | False | None | None | False | None | False | 7560.0 | 0 |
3379587 | 119010 | None | code59 | Suspension Clamp Assembly 16 to 70 Sqmm Bare Messenger (Exclusive of Pole Clamp and Eye Hook) with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 232.05 | 232.05 | 60.0 | False | None | None | False | None | False | 13923.0 | 0 |
3379588 | 119010 | None | code60 | Erection of Anchor Clamp -25 to 95 Sqmm bare/Insulated messenger with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 151.2 | 151.2 | 60.0 | False | None | None | False | None | False | 9072.0 | 0 |
3379589 | 119010 | None | code61 | Supply of Pole Clamp for HT/LT AB cable.(ESCOM SR 2023-24,PART-2,P.NO-19,It no-43.35) with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 114.45 | 114.45 | 60.0 | False | None | None | False | None | False | 6867.0 | 0 |
3379590 | 119010 | None | code62 | Fixing of Pole Clamp-145 mm x 95 with all leads & lift complete as per specification and as directed by the engineer of the work. | Set | 168.0 | 168.0 | 60.0 | False | None | None | False | None | False | 10080.0 | 0 |
3379591 | 119010 | None | code63 | Straight Joint Suitable for 95 Sqmm, LT ABC - MJPT Type. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 442.05 | 442.05 | 20.0 | False | None | None | False | None | False | 8841.0 | 0 |
3379592 | 119010 | None | code64 | Laying of 11 kV AB Cable Straight thru' joint installation for 3 Core. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 1495.2 | 1495.2 | 20.0 | False | None | None | False | None | False | 29904.0 | 0 |
3379593 | 119010 | None | code65 | Supply of Pre - Insulated Lug - CPTAU for 95 Sqmm. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 411.6 | 411.6 | 300.0 | False | None | None | False | None | False | 123480.0 | 0 |
3379594 | 119010 | None | code66 | Installation of Pre-Insulated Lug - CPTAU for 95 Sqmm..with all leads & lift complete as per specification and as directed by the engineer of the work.. | No | 168.0 | 168.0 | 300.0 | False | None | None | False | None | False | 50400.0 | 0 |
3379595 | 119010 | None | code67 | Supply of PVC Wire - 10 Sqmm Weight per 100 Mtr Coil: 5.3 Kg with all leads & lift complete as per specification and as directed by the engineer of the work. | Coil | 2811.9 | 2811.9 | 4.5 | False | None | None | False | None | False | 12653.55 | 0 |
3379596 | 119010 | None | code68 | Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff.2.5 to 25 Sqmm with all leads & lift complete as per specification and as directed by the engineer of the work. | Km | 21930.3 | 21930.3 | 0.44 | False | None | None | False | None | False | 9649.332 | 0 |
3379597 | 119010 | None | code69 | 1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part 1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975. 150 Sqmm, 3.5 Core, (25 GI Strips - 4 x 0.8 mm with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE HAVELLS, POLYCAB, FINOLEX, KEI, UNIVERSAL CABLES | Km | 582387.75 | 582387.75 | 0.1 | False | None | None | False | None | False | 58238.775 | 0 |
3379598 | 119010 | None | code70 | Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff.120 to 240 Sqmm with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE HAVELLS, POLYCAB, FINOLEX, KEI, UNIVERSAL CABLES | Km | 33891.9 | 33891.9 | 0.1 | False | None | None | False | None | False | 3389.19 | 0 |
3379599 | 119010 | None | code71 | 1.1 kV, XLPE or Heat resistant PVC insulated, PVC exutruted Inner Seath Armoured LTUG Cable as per IS-1554 (Part 1) or IS-7098 Part-1, Armouring strip thickness and resistivity as per IS-3975. 135 Sqmm, 4 Core, (15 GI Strips - 4 x 0.8 mm with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE HAVELLS, POLYCAB, FINOLEX, KEI, UNIVERSAL CABLES | Km | 184873.5 | 184873.5 | 0.2 | False | None | None | False | None | False | 36974.7 | 0 |
3379600 | 119010 | None | code72 | Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff.35 to 95 Sqmm with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE HAVELLS, POLYCAB, FINOLEX, KEI, UNIVERSAL CABLES | Km | 32695.95 | 32695.95 | 0.2 | False | None | None | False | None | False | 6539.19 | 0 |
3379601 | 119010 | None | code73 | Brass Cable Gland 25mm. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 82.95 | 82.95 | 8.0 | False | None | None | False | None | False | 663.6 | 0 |
3379602 | 119010 | None | code74 | Brass Cable Gland 32 mm. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 99.75 | 99.75 | 8.0 | False | None | None | False | None | False | 798.0 | 0 |
3379603 | 119010 | None | code75 | Brass Cable Gland 40 mm. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 155.4 | 155.4 | 8.0 | False | None | None | False | None | False | 1243.2 | 0 |
3379604 | 119010 | None | code76 | Brass Cable Gland 45 mm. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 206.85 | 206.85 | 4.0 | False | None | None | False | None | False | 827.4 | 0 |
3379605 | 119010 | None | code77 | Earth work excavation for cable trench of 0.5 to 0.75 Mtr. Width and Depth upto 1 Mtr (BESCOM SR PART-4,P.NO.8, IT No-29.02) -Earth work excavation for pipelines/cables by Manual means upto 600 mm trench width, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter, including dressing of excavated surfaces, disposing off or leveling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m. Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering and lift upto 1.5 m including cost of labour, tools, usage& other appurtenances required to complete the work. with all leads & lift complete as per specification and as directed by the engineer of the work. | cm | 508.2 | 508.2 | 180.0 | False | None | None | False | None | False | 91476.0 | 0 |
3379606 | 119010 | None | code78 | Refilling the cable trenches with selected available earth from trench excavation including watering, consolidation in layers of 15 cm. Thickness including depositing of the surplus earth with a lead of 200 Mtr with all leads & lift complete as per specification and as directed by the engineer of the work. | cm | 60.9 | 60.9 | 180.0 | False | None | None | False | None | False | 10962.0 | 0 |
3379607 | 119010 | None | code79 | Supplying,fixing,wiring,earth electrode for grounding conduits,I.C.cutouts and other equipment's on the mete rboard using 40mm dia 2.90 mm thick GI pipe 2.5m long buried in a pit.The pit should be filled with equal proportion of salt and char coal150mm all-round the pipe to complete depth.The connection from the pipe to the conduit etc.,is to be established through GI wire of size as per lSI specification7.3.3.of IS732 using 12 mm dia bolts,nuts,washers and check nuts etc., the pipe shall have 16 through holes of 12 mm dia. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 3685.5 | 3685.5 | 12.0 | False | None | None | False | None | False | 44226.0 | 0 |
3379608 | 119010 | None | code80 | Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. GI strip GI Strip. 25x3mm with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 86.1 | 86.1 | 60.0 | False | None | None | False | None | False | 5166.0 | 0 |
3379609 | 119010 | None | code81 | Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. GI strip Copper strip. 25x3mm. with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 598.5 | 598.5 | 20.0 | False | None | None | False | None | False | 11970.0 | 0 |
3379610 | 119010 | None | code82 | Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. 600x600x3mm Copper plate. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 7792.05 | 7792.05 | 4.0 | False | None | None | False | None | False | 31168.2 | 0 |
3379611 | 119010 | None | code83 | Supply of 11 kV, 3 Core, XPLE HTUG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975. 95 Sqmm, (54 GI Wires - 2.5 mm Dia). with all leads & lift complete as per specification and as directed by the engineer of the work. MAKE HAVELLS, POLYCAB, FINOLEX, KEI, UNIVERSAL CABLES | Km | 934149.3 | 934149.3 | 0.1 | False | None | None | False | None | False | 93414.93 | 0 |
3379612 | 119010 | None | code84 | Supply of Heat Shrinkable Indoor Type Cable Termination Kit for XLPE Cable.3Cx95sqmm indoor. with all leads & lift complete as per specification and as directed by the engineer of the work. | Kit | 3931.2 | 3931.2 | 4.0 | False | None | None | False | None | False | 15724.8 | 0 |
3379613 | 119010 | None | code85 | Supply of Heat Shrinkable Outdoor Type Cable Termination Kit for XLPE Cable 3Cx95sqmm outdoor. with all leads & lift complete as per specification and as directed by the engineer of the work. | Kit | 4270.35 | 4270.35 | 4.0 | False | None | None | False | None | False | 17081.4 | 0 |
3379614 | 119010 | None | code86 | Supply of Cable covering tiles 250x125x40mm.. ) with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 10.76 | 10.76 | 100.0 | False | None | None | False | None | False | 1076.0 | 0 |
3379615 | 119010 | None | code87 | Supply of River sand. with all leads & lift complete as per specification and as directed by the engineer of the work. | cm | 1852.2 | 1852.2 | 6.0 | False | None | None | False | None | False | 11113.2 | 0 |
3379616 | 119010 | None | code88 | Supply of RCC humepipes 2000mm long 150mm dia. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 322.35 | 322.35 | 4.0 | False | None | None | False | None | False | 1289.4 | 0 |
3379617 | 119010 | None | code89 | Supply of Collars for RCC hume pipes. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 86.1 | 86.1 | 4.0 | False | None | None | False | None | False | 344.4 | 0 |
3379618 | 119010 | None | code90 | Supply of GI pipe 150mm dia. 100MM DIA VOL V SlNo 177 P-A30 with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 1072.05 | 1072.05 | 4.0 | False | None | None | False | None | False | 4288.2 | 0 |
3379619 | 119010 | None | code91 | Supply of Route and Joint indicating stones with MS Anchor rod. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 139.65 | 139.65 | 10.0 | False | None | None | False | None | False | 1396.5 | 0 |
3379620 | 119010 | None | code92 | Earth work excavation for cable treanch of 0.5 to 0.75Mtr Width and Depth up to 1Mtr . Earth work excavation for pipelines/cables by Manual means upto 600 mm trench width, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter, including dressing of excavated surfaces, disposing off or leveling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m. Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering and lift upto 1.5 m including cost of labour, tools, usage& other appurtenances required to complete the work with all leads & lift complete as per specification and as directed by the engineer of the work. | cm | 508.2 | 508.2 | 60.0 | False | None | None | False | None | False | 30492.0 | 0 |
3379621 | 119010 | None | code93 | Laying of cable in Existing Trench/GI pipe/Stone Ware/RCC Hume pipe using Wooden/Aluminum Rollers as directed by the departmental staff.3x95 to 150 Sqmm with all leads & lift complete as per specification and as directed by the engineer of the work. | Km | 64388.1 | 64388.1 | 0.1 | False | None | None | False | None | False | 6438.81 | 0 |
3379622 | 119010 | None | code94 | Retailing the cable trenches with selected availble earth from trench excavation including watering,Consolidation in layers of 15Cm thickness including depositing of the surplus earth with a lead of 200Mtrs. with all leads & lift complete as per specification and as directed by the engineer of the work. | cm | 60.9 | 60.9 | 14.0 | False | None | None | False | None | False | 852.6 | 0 |
3379623 | 119010 | None | code95 | Making and Fixing pot head for HT Cable only.Heat shrinkable Type Terminations.3x95 to 3x150 Sqmm. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 2790.9 | 2790.9 | 8.0 | False | None | None | False | None | False | 22327.2 | 0 |
3379624 | 119010 | None | code96 | Covering the cables with tiles.with all leads & lift complete as per specification and as directed by the engineer of the work. | Km | 4585.35 | 4585.35 | 0.06 | False | None | None | False | None | False | 275.121 | 0 |
3379625 | 119010 | None | code97 | Spreading and forming with sand alround the cable to a depth of 75mm and width of 500mm with all leads & lift complete as per specification and as directed by the engineer of the work. | Km | 15550.5 | 15550.5 | 0.06 | False | None | None | False | None | False | 933.03 | 0 |
3379626 | 119010 | None | code98 | Laying and Jointing the pipes (100-150 mm Dia) including lowering in Position: Fixing Collars etc., Joining with mud mortor complete.RCC Pipe..with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 72.45 | 72.45 | 4.0 | False | None | None | False | None | False | 289.8 | 0 |
3379627 | 119010 | None | code99 | Laying the GI Pipe 80 mm to 150 mm dia at Drainage Water Supply Crossing including fixing collars elbows, bends, Tees and other fitting with Cuts and Threads wherever necessary complete..with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 97.65 | 97.65 | 4.0 | False | None | None | False | None | False | 390.6 | 0 |
3379628 | 119010 | None | code100 | Fixing of Route Joint Indicating Slab..with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 121.8 | 121.8 | 6.0 | False | None | None | False | None | False | 730.8 | 0 |
3379629 | 119010 | None | code101 | CT PT Operated ETV Meter 0.2s Accuracy Class with ABT feature and DLMS protocal with ToD with RS 232 Port UNIDIRACTIONAL (Used for HT Installation, LT Metering Cubicle 50-150 KW with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 20595.75 | 20595.75 | 2.0 | False | None | None | False | None | False | 41191.5 | 0 |
3379630 | 119010 | None | code102 | Supply of Load Break switches with Panel with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 76900.95 | 76900.95 | 2.0 | False | None | None | False | None | False | 153801.9 | 0 |
3379631 | 119010 | None | code103 | Erection of LT metering Cubicle on Platform. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 1741.95 | 1741.95 | 2.0 | False | None | None | False | None | False | 3483.9 | 0 |
3379632 | 119010 | None | code104 | Erection,Alignment and fixing of Load break switch on the platform. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 2181.9 | 2181.9 | 2.0 | False | None | None | False | None | False | 4363.8 | 0 |
3379633 | 119010 | None | code105 | Construction of platform (1.5x1.5x1.2) mtr in size stone,cement concrete for erection of Metering cubical,Transformer and Load break switch: Excavation of (1.5x1.5x1) mt pit for foundation providing and laying cement concrete 1:4:8 for foundation laid in 10cm thick layers, well compacted curing etc., complete providing and construction of stone masonary 0.9m below ground level and 1.2m above ground level neatly hammer dressed in cement morter 1:6. Providing cement concrete Slab(1.5x1.5x0.10)Mtr with cement concrete 1:2:4 mix forming and cutting complete providing pointing to stone masonary in cement morter 1:3 after racking joint & nisely lining curing etc., plastering the concrete surfaces in cement morter 1:4 including smooth randering curing etc., curing at every stages completely this Estimate is prepared using CSR 2023-24 rates with all leads & lift complete as per specification and as directed by the engineer of the work. | Each | 24702.3 | 24702.3 | 8.0 | False | None | None | False | None | False | 197618.4 | 0 |
3379634 | 119010 | None | code106 | supply of Distribution Transformer - 3 Phase, 11kV/433V - Stacked CRGO Core with Oil as per IS-1180 Part-1 2014.21. 100 kVA, Aluminium Wdg, Star 2 5 Star with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 236854.8 | 236854.8 | 2.0 | False | None | None | False | None | False | 473709.6 | 0 |
3379635 | 119010 | None | code107 | Erection of 100 kVA Transformer. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 1669.5 | 1669.5 | 2.0 | False | None | None | False | None | False | 3339.0 | 0 |
3379636 | 119010 | None | code108 | Supply and instalation of DAS Specification Compact RMU (VCB/SF6 Type) as per IEC-62271 The DAS RMUs shall have the following in addition to the Standards: DC motors, Numerical Relays, Multifunctional meters, fault passage indicator (FPI), Metering CTs, Protection CTs, Auxiliary transformers, Potential transformer, Batteries, Battery chargers (12V & 24 V), AC power socket and light for illumination of Control panel. Control cable from each panel shall be wired and terminated to suitable 24 pin connector in the control panel. Suitable space for fixing the Remote Terminal Unit (RTU) and Radio Modem in Control panel. Suitable Clamps for fixing Antenna Pipe 3 Way RMU, 2OD + 1VL (One Incomer + One Breakers + One Outgoing) 630 Amps with Copper Busbar..with all leads & lift complete as per specification and as directed by the engineer of the work. | Each | 827661.45 | 827661.45 | 2.0 | False | None | None | False | None | False | 1655322.9 | 0 |
3379637 | 119010 | None | code109 | Providing chain link fencing 50mm size of 8 guage properly stretched between rectangular poles and fixed with suitable bolts & nuts, the free ends shall be welded to the pole and block pipe at top and bottom as required including cost of all materials, labour, lead and lifts, cutting, bending wherever necessary, wastage and lapping etc., complete as per the direction of the engineer incharge for work including two coats of approved quality paint over one coat of primer paint.this Estimate is prepared using CSR 2023-24 rates Area 9mx5m with all leads & lift complete as per specification and as directed by the engineer of the work. | Each | 274627.5 | 274627.5 | 2.0 | False | None | None | False | None | False | 549255.0 | 0 |
3379638 | 119010 | None | code110 | Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc. using 40mm dia 2.9mm thick 2.5 mtr long GI pipe with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode. The funnel should be enclosed in a CC chamber of 400x400x400mm with a cast iron cover. The earth electrode shall have staggered holes of 12mm dia and the electrode should be covered 150mm all-round with alternate layers of salt and charcoal from the bottom of the CC chamber. The connection from the electrode is to be established through GI strip using GI bolts and nuts.. with all leads & lift complete as per specification and as directed by the engineer of the work. | No | 4468.8 | 4468.8 | 20.0 | False | None | None | False | None | False | 89376.0 | 0 |
3379639 | 119010 | None | code111 | Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. GI strip GI Strip. 25x3mm with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 86.1 | 86.1 | 40.0 | False | None | None | False | None | False | 3444.0 | 0 |
3379640 | 119010 | None | code112 | Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. GI strip 50x6mm GI strip with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 228.9 | 228.9 | 40.0 | False | None | None | False | None | False | 9156.0 | 0 |
3379641 | 119010 | None | code113 | Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. 25 x 3 mm Copper strip with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 598.5 | 598.5 | 40.0 | False | None | None | False | None | False | 23940.0 | 0 |
3379642 | 119010 | None | code114 | Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required. 25 x 6 mm Copper strip with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 1155.0 | 1155.0 | 40.0 | False | None | None | False | None | False | 46200.0 | 0 |
3379643 | 119010 | None | code115 | Supplying and running of GI/Copper strips for grounding connections, using necessary fixing materials as required.600 x 600 x 3 mm Copper plate with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 7792.05 | 7792.05 | 8.0 | False | None | None | False | None | False | 62336.4 | 0 |
3379644 | 119010 | None | code116 | Supplying and running GI/Copper conductor for grounding and (along with other wires in conduit system of wiring) using necessary suitable size clamps, nails, guttas/spacers etc. 8 SWG. Copper Wire with all leads & lift complete as per specification and as directed by the engineer of the work. | Mtr | 60.9 | 60.9 | 100.0 | False | None | None | False | None | False | 6090.0 | 0 |