tenderSubEstimateList | createdTs | version | createdDate | modifiedDate | workCategoryName | subEstimateName | estimateTotal | itemList |
---|
1726893212000 | 0 | None | None | Sub-Station | Cable Supply | 1378083431.0 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
4044080 | 156939 | None | CS1 | 220 kV (Earthed) 1C X 1200 Sq mm stranded, annealed, copper conductor, segmental compacted, circular (Milliken), conductor screen, cross linked polyethylene (XLPE) insulation, core screen, semiconducting water swellable layer, lead alloy 'E' sheathed, semi-conducting bedding tapes, helically applied plain round copper wire screen, plain copper tape in open helix, water swellable tape with overall extruded high density polyethylene sheath coated with graphite/ extruded semi conducting layer and anti-termite treated as per technical specification. | Kms | 30694000.0 | 30694000.0 | 29.334 | False | None | None | False | None | False | 900377796.0 | 0 | 4044081 | 156939 | None | CS2 | Joints suitable for 220 kV, 1C X 1200 Sq mm, copper conductor, XLPE insulated, lead sheathed cable complete with all accessories as per technical specification.
(UNISR Vol-6 Page No.80, Sl No. 61.1.7)
a. Insulated joints/sheath sectionalizing joints - 12 Nos. for Work-A, 24 Nos. for Work-B b. Normal straight through joints - 3 Nos. for Work-A,
c. Earthing joints-2 nos/phase - 6 Nos. for Work-A, 9 Nos. for Work-B | Nos | 756250.0 | 756250.0 | 54.0 | False | None | None | False | None | False | 40837500.0 | 0 | 4044082 | 156939 | None | CS3 | Out door type cable end termination suitable for 127/220 kV (E) class 1C X 1200 Sq mm copper conductor lead sheathed XLPE insulated cable as per technical specification.
(UNISR Vol-6 Page No.79, Sl No. 61.1.1) | Nos | 1102310.0 | 1102310.0 | 3.0 | False | None | None | False | None | False | 3306930.0 | 0 | 4044083 | 156939 | None | CS4 | Indoor type cable termination (plug in dry type) suitable for GIS modules confirming to IEC 62271-209 for 220 kV, 1200 Sq mm, copper conductor XLPE insulated cable as per technical specification. | Nos | 730840.0 | 730840.0 | 9.0 | False | None | None | False | None | False | 6577560.0 | 0 | 4044084 | 156939 | None | CS5 | Single phase Link box outdoor structure mounting type, with SVL suitable for 220 kV, 1200 Sq mm UG cable including 400 Sq mm sheath bonding cable as per the technical specification. | Nos | 78650.0 | 78650.0 | 3.0 | False | None | None | False | None | False | 235950.0 | 0 | 4044085 | 156939 | None | CS6 | Three phase cross bonding Link box with SVL including 400 Sq mm sheath bonding cable and 400 Sq mm co-axial cable as per technical specification suitable for 220 kV, 1200/1000 Sq mmUG Cable.
Note: The rate of 220 kV : Cross Bonding, Link Boxes, Single phase out door structure mounting type, with Temperature Transducers, Thermocouplers, SVL/CCPU and PVC earthing cable including 1C x 1000 Sq mm cable as per the technical specifictions is considered
The Link box shall be burried type, water proof (capable of immerssion in water), weather proof, rust & dust proof (IP: 68) | Nos | 105270.0 | 105270.0 | 13.0 | False | None | None | False | None | False | 1368510.0 | 0 | 4044086 | 156939 | None | CS7 | Three phase Link box without SVL including 400 Sq mm sheath bonding cable and 400 Sq mm co-axial cable as per technical specification suitable for 220 kV, 1200/1000 Sq mm UG Cable. The Link box shall be burried type, water proof (capable of immerssion in water), weather proof, rust & dust proof (IP: 68) | Nos | 65340.0 | 65340.0 | 8.0 | False | None | None | False | None | False | 522720.0 | 0 | 4044087 | 156939 | None | CS8 | Terminal Connector for SF6 / Air Bushing suitable to receive Twin Bersimis/Moose ACSR Conductor is considered for estimation pupose. | Nos | 2191.0 | 2191.0 | 9.0 | False | None | None | False | None | False | 19719.0 | 0 | 4044088 | 156939 | None | CS9 | Power Connectors, Expansion Type Terminal Connectors suitable for Aluminium pipes 63 mm nominal diameter x 73.03 mm | No. | 2117.0 | 2117.0 | 3.0 | False | None | None | False | None | False | 6351.0 | 0 | 4044089 | 156939 | None | CS10 | 66 kV (Earthed), 1C X 1000 Sq mm stranded, annealed, copper conductor, segmental, compact, circular, (Milliken), conductor screen, cross linked polyethylene (XLPE) insulation, core screen, semiconducting water swellable layer, lead alloy 'E' sheathed, semi-conducting bedding tapes, helically applied plain round copper wire screen, plain copper tape in open helix, water swellable tape with overall extruded high density polyethylene sheath coated with graphite and anti-termite treated as per technical specification. | Kms | 16606000.0 | 16606000.0 | 23.75 | False | None | None | False | None | False | 394392500.0 | 0 | 4044090 | 156939 | None | CS11 | Outdoor type cable end termination suitable for 66 kV, 1C X 1000 Sq mm segmental compact type miliken copper conductor, XLPE, lead sheathed cable as per technical specification | No. | 274670.0 | 274670.0 | 6.0 | False | None | None | False | None | False | 1648020.0 | 0 | 4044091 | 156939 | None | CS12 | Indoor type cable termination (plug in dry type) suitable for GIS modules confirming to IEC 62271-209 for 66 kV, 1000 Sq mm, copper conductor, XLPE insulated lead sheathed cable as per technical
specification. | Nos | 381150.0 | 381150.0 | 12.0 | False | None | None | False | None | False | 4573800.0 | 0 | 4044092 | 156939 | None | CS13 | Single phase Link box outdoor structure mounting type, with SVL suitable for 66 kV,1000 Sq mm UG cable including 240 Sq mm sheath bonding cable as per the technical specification. (UNISR Vol-6, Page No. 83, SL No. 61.4.5) | Nos | 43560.0 | 43560.0 | 6.0 | False | None | None | False | None | False | 261360.0 | 0 | 4044093 | 156939 | None | CS14 | Three phase Link box without SVL including 240 Sq mm sheath bonding cable and 240/240 Sq mm co-axial cable as per technical specification suitable for 66 kV,1000 Sq mm UG Cable. The Link box shall be burried type, water proof(capable of immerssion in water), weather proof, rust & dust proof (IP: 68) | Nos | 65340.0 | 65340.0 | 5.0 | False | None | None | False | None | False | 326700.0 | 0 | 4044094 | 156939 | None | CS15 | Three phase cross bonding Link box with SVL including 240 Sq mm sheath bonding cable and 240/240 Sq mm co-axial cable as per technical specification suitable for 66 kV,1000 Sq mm UG Cable. The Link box shall be burried type, water proof (capable of immerssion in water), weather proof, rust & dust proof (IP: 68) | Nos | 105270.0 | 105270.0 | 11.0 | False | None | None | False | None | False | 1157970.0 | 0 | 4044095 | 156939 | None | CS16 | Normal Straight through Joint suitable for 66 kV, 1C X 1000 Sq mm, copper conductor, XLPE insulated, lead sheathed cable complete with all accessories as per technical specification.
a.Insulated/sheath sectionalizing joints- 24 for work-C , 2 for work-D b.Normal straight through joints-3 for work-C , 2 for work-D c. earthing joints- 9 for work-C , 2 for work-D | Nos | 169400.0 | 169400.0 | 42.0 | False | None | None | False | None | False | 7114800.0 | 0 | 4044096 | 156939 | None | CS17 | Sheath cable of 1C x 240 sqmm for earthing from terminal bay to CTT as per specifications. Including erection | Kms | 5283000.0 | 5283000.0 | 1.33 | False | None | None | False | None | False | 7026390.0 | 0 | 4044097 | 156939 | None | CS18 | INSULATOR STRINGS :66kV lines
A. Single Tension insulator strings consisting of any one of the following:
a. Insulator string consisting of 1X5nos. of 90kN Disc insulators
Or
b. Porcelain long rod insulator string equivalent to 1x5nos. of 90kN/120KN Disc insulators
Or
c. Silicon rubber composite insulator equivalent to 1X5nos. of 90kN Disc insulators
Strings=Nos | Nos | 2955.0 | 2955.0 | 12.0 | False | None | None | False | None | False | 35460.0 | 0 | 4044098 | 156939 | None | CS19 | B. Double Tension insulator strings consisting of any one of the following:
a. Insulator string consisting of 2X5nos. of 90kN Disc insulators
Or
b. Porcelain long rod insulator string equivalent to 2x5nos. of 90kN/120KN Disc insulators
Or
c. Silicon rubber composite insulator equivalent to 2X5nos. of 90kN Disc insulators
Strings=Nos | Nos | 5910.0 | 5910.0 | 12.0 | False | None | None | False | None | False | 70920.0 | 0 | 4044099 | 156939 | None | CS20 | Insulator Hardware:
A.Single Tension Clamp with hardware and arcing horn suitable for 1x5nos. of 90kN insulator to suit Drake ACSR | Nos | 3865.0 | 3865.0 | 12.0 | False | None | None | False | None | False | 46380.0 | 0 | 4044100 | 156939 | None | CS21 | B.Double Tension Clamp with hardware and arcing horn suitable for 2x5nos. of 90kN insulator to suit Drake ACSR | Nos | 6884.0 | 6884.0 | 12.0 | False | None | None | False | None | False | 82608.0 | 0 | 4044101 | 156939 | None | CS22 | ii. C type wedge connector suitable for Coyote-Drake ACSR | No | 2334.0 | 2334.0 | 24.0 | False | None | None | False | None | False | 56016.0 | 0 | 4044102 | 156939 | None | CS23 | iii. C type wedge connector suitable for Drake-Drake ACSR | No | 2462.0 | 2462.0 | 12.0 | False | None | None | False | None | False | 29544.0 | 0 | 4044103 | 156939 | None | CS24 | iv. Vibration damper for Coyote conductor | No | 942.0 | 942.0 | 6.0 | False | None | None | False | None | False | 5652.0 | 0 | 4044104 | 156939 | None | CS25 | v. Vibration damper for Drake conductor | No | 1587.0 | 1587.0 | 12.0 | False | None | None | False | None | False | 19044.0 | 0 | 4044105 | 156939 | None | CS26 | Tower Accessories
1.Number Plates | Nos | 318.0 | 318.0 | 2.0 | False | None | None | False | None | False | 636.0 | 0 | 4044106 | 156939 | None | CS27 | 2.Danger Boards | Nos | 318.0 | 318.0 | 2.0 | False | None | None | False | None | False | 636.0 | 0 | 4044107 | 156939 | None | CS28 | 3.Circuit plate | Nos | 318.0 | 318.0 | 4.0 | False | None | None | False | None | False | 1272.0 | 0 | 4044108 | 156939 | None | CS29 | 4.Phase plate (Set of 3 per tower) | Nos | 264.0 | 264.0 | 4.0 | False | None | None | False | None | False | 1056.0 | 0 | 4044109 | 156939 | None | CS30 | 5. Earth bond 450mm long | Nos | 538.0 | 538.0 | 2.0 | False | None | None | False | None | False | 1076.0 | 0 | 4044110 | 156939 | None | CS31 | Optical fibre and its accessories as per Specifications:
1.Unarmored Under Ground Fiber Optic Cable (48F DWSM) as per technical specifications. | Kms | 109000.0 | 109000.0 | 16.25 | False | None | None | False | None | False | 1771250.0 | 0 | 4044111 | 156939 | None | CS32 | 2.Poly Vinyl Lubricated Bond (PLB) HDPE OD 40mm with accessories. | Kms | 98000.0 | 98000.0 | 16.25 | False | None | None | False | None | False | 1592500.0 | 0 | 4044112 | 156939 | None | CS33 | 3.Joint box suitable for OFC(48F) (Kit=Nos) | Nos | 7923.0 | 7923.0 | 13.0 | False | None | None | False | None | False | 102999.0 | 0 | 4044113 | 156939 | None | CS34 | 4.OFC end terminal (Line Interface unit LIU suitable for 48F) | Nos | 20570.0 | 20570.0 | 10.0 | False | None | None | False | None | False | 205700.0 | 0 | 4044114 | 156939 | None | CS35 | 5.Collars for PLB Pipe | Nos | 157.0 | 157.0 | 70.0 | False | None | None | False | None | False | 10990.0 | 0 | 4044115 | 156939 | None | CS36 | 6. Digital protection coupler of direct fiber-in type, working with universal power supply | Nos | 353320.0 | 353320.0 | 4.0 | False | None | None | False | None | False | 1413280.0 | 0 | 4044116 | 156939 | None | CS37 | 7.Media convertor | Nos | 4840.0 | 4840.0 | 8.0 | False | None | None | False | None | False | 38720.0 | 0 | 4044117 | 156939 | None | CS38 | 8.UG OFC to OPGW joint box | Nos | 8470.0 | 8470.0 | 2.0 | False | None | None | False | None | False | 16940.0 | 0 | 4044118 | 156939 | None | CS39 | OPGW and Accessories
1.48 Fibre Dual Window Single Mode (DWSM) OPGW | Kms | 193000.0 | 193000.0 | 12.0 | False | None | None | False | None | False | 2316000.0 | 0 | 4044119 | 156939 | None | CS40 | 2.Suspension Clamp Assembly for 48 Fibre OPGW | Nos | 2118.0 | 2118.0 | 11.0 | False | None | None | False | None | False | 23298.0 | 0 | 4044120 | 156939 | None | CS41 | 3. Tension assembly for dead end for 48 Fibre OPGW | Nos | 2345.0 | 2345.0 | 2.0 | False | None | None | False | None | False | 4690.0 | 0 | 4044121 | 156939 | None | CS42 | 4.Tension fitting assembly for 48 Fibre OPGW including all accessories for joint box (Splicing Location) | Nos | 4690.0 | 4690.0 | 7.0 | False | None | None | False | None | False | 32830.0 | 0 | 4044122 | 156939 | None | CS43 | 5.Tension assembly - Double Tension pass through for 48 Fibre OPGW | Nos | 4320.0 | 4320.0 | 11.0 | False | None | None | False | None | False | 47520.0 | 0 | 4044123 | 156939 | None | CS44 | 6.Tension fitting assembly on suspension Tower for 48 Fibre OPGW including all accessories for joint box (splicing) location | Nos | 5677.0 | 5677.0 | 2.0 | False | None | None | False | None | False | 11354.0 | 0 | 4044124 | 156939 | None | CS45 | 7.Vibration Damper for 48 Fibre OPGW | Nos | 490.0 | 490.0 | 58.0 | False | None | None | False | None | False | 28420.0 | 0 | 4044125 | 156939 | None | CS46 | 8.Down lead clamp assembly for fibre OPGW | Nos | 225.0 | 225.0 | 21.0 | False | None | None | False | None | False | 4725.0 | 0 | 4044126 | 156939 | None | CS47 | 9Joint Box | Nos | 7923.0 | 7923.0 | 11.0 | False | None | None | False | None | False | 87153.0 | 0 | 4044127 | 156939 | None | CS48 | 10.FODP 48F : Indoor type consisting of 2 nos. of rack
mounted LIU (to be housed in FODP) with 24 ports
each with FCPC coupling & pigtails | Nos | 66186.0 | 66186.0 | 1.0 | False | None | None | False | None | False | 66186.0 | 0 | 4044128 | 156939 | None | CS49 | 11. 48 Fibre (DWSM) including Installation Hardware
set for 48 Approach Cable | Kms | 204000.0 | 204000.0 | 1.0 | False | None | None | False | None | False | 204000.0 | 0 |
| 1726893212000 | 0 | None | None | Sub-Station | Station Erection GIS | 35630437.47 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
4044129 | 156940 | None | SE1 | POWER TRANSFORMERs:
a) Power Transformer: 3 Ph. 50Hz Core type, 3 winding Star/Star/Delta, Transformer Vector Group : YNyn0d11, OLTC, bushing CT for teritiary of ratio 1515/1A, 5P20, 15VA, ONAN/ONAF/OFAF with Fan control cubicle, Numerical RTCC panel with optic fibre temperature sensor, oil etc., complete with 2x50% separate radiator bank on left side and terminal connector suitable for Single Drake ACSR on primary and Twin Drake ASCR on secondary side of transformer and Neutral connectors suitable for Copper Flats as per specifications
150MVA, 220/66/11kV Transformer | No | 983082.0 | 983082.0 | 2.0 | False | None | None | False | None | False | 1966164.0 | 0 | 4044130 | 156940 | None | SE2 | Erection and Testing & commissioning of 220kV GIS Modules-Total
Note:Refer Techno Commercial sheets for detailed break up. | No | 480130.0 | 480130.0 | 8.0 | False | None | None | False | None | False | 3841040.0 | 0 | 4044131 | 156940 | None | SE3 | Erection and Testing & commissioning of 66kV GIS Modules-Total
Note:Refer Techno Commercial sheets for detailed break up. | No | 426784.0 | 426784.0 | 11.0 | False | None | None | False | None | False | 4694624.0 | 0 | 4044132 | 156940 | None | SE4 | GAS INSULATED BUS-DUCTS :
66 kV, 2500 A, 40 kA SF6 duct outside the GIS
building including SF6 gas monitoring system for
connecting GIS module to SF6 - Air bushing including
support structure and civil foundation
Note:
For 66kV Lines = 12 meter floor *3 Lines = 36 meter / Line;
5 Line Bays * 36 Meter = 180 Meter
For 66kV Transformer Bay = 15 meter 1st floor+ 30 Meter upto Transformer upto air bushing = 45 meter / Transformer = 2 transformer * 45 Meter = 90 Meter
For 66kV Interconnecting Bay = 15 meter 1st Floor + 45 meter upto existing Bay = 60 Meter
Total Bus duct= 180+90+60 = 330 Meter | Mtr | 6558.0 | 6558.0 | 330.0 | False | None | None | False | None | False | 2164140.0 | 0 | 4044133 | 156940 | None | SE5 | Bus Maintenance earth switch 3 Phase, Single pole, Group operated maintenance earthing switch complete with manual operating mechanism -1600 Amp. Along with mounting structure, foundation, earthing etc.,
i)220 kV - (1 for each bus) | No | 96026.0 | 96026.0 | 2.0 | False | None | None | False | None | False | 192052.0 | 0 | 4044134 | 156940 | None | SE6 | Bus Maintenance earth switch 3 Phase, Single pole, Group operated maintenance earthing switch complete with manual operating mechanism -1600 Amp. Along with mounting structure, foundation, earthing etc.,
ii)66 kV - (1 for each bus) | No | 85356.0 | 85356.0 | 2.0 | False | None | None | False | None | False | 170712.0 | 0 | 4044135 | 156940 | None | SE7 | SF-6 CIRCUIT BREAKER: SF-6 Circuit Breaker with rigid bi-metallic terminal connector suitable for Drake ACSR with spring / semi-pneumatic / pneumatic type operating mechanism and with mounting structure.
220 kV, 1250A, 40kA Class | No | 82772.0 | 82772.0 | 1.0 | False | None | None | False | None | False | 82772.0 | 0 | 4044136 | 156940 | None | SE8 | Current Transformer : Oil filled current transformer with rigid terminal connector suitable for copper flat
NOTE:
All the current transformers in each KV class shall be of one and the same make for interchangeability and reliability of performance.
(i) 22 0kV 40KA CT of Ratio 600-300/1-1-1A
(Required for 150MVA Transformer NCT) | No | 13298.67 | 13298.67 | 2.0 | False | None | None | False | None | False | 26597.34 | 0 | 4044137 | 156940 | None | SE9 | ii. 220 kV, 40kA CT of Ratio 1200-800/1-1-1A with additional 2 Cores of 1200/1A Type-1
For Metering: Accuracy 0.2S, Burden 10VA
For Backup Protection: 5P20, Burden 30VA
For Differential/Distance Protection: PS Class, Knee Point Voltage - 1200V at 1200/1A Rct 12 ohms - 600V at 600/1A Rct 6 ohms.
For Bus Bar Protection: PS Class, Knee Point Voltage 1200V, Rct-12 ohms at 1200/1A
Remarks: Terminal connectors shall be suitable for Double Drake ACSR. | No | 13298.67 | 13298.67 | 3.0 | False | None | None | False | None | False | 39896.01 | 0 | 4044138 | 156940 | None | SE10 | 66kV 40KA CT of Ratio 1600-1000/1-1-1A
(Required for 150MVA Transformer NCT -66kV side) | No | 6205.34 | 6205.34 | 2.0 | False | None | None | False | None | False | 12410.68 | 0 | 4044139 | 156940 | None | SE11 | Isolators:-including Marshalling box & terminal connectors as per technical specification including solid core cylindrical post insulators
I. 220kV, 1250A, 31.5kA Class Double Break Motor Operated Isolators:
Note:-i) Rigid type terminal connector suitable for Double Drake - 24 nos ii) Flexible Type Terminal Connector suitable for 63 mm al. Pipe - 6 nos
a) Upright mounting type with manually operated Earth Switch LPH 5750 mm. | No | 7191.0 | 7191.0 | 1.0 | False | None | None | False | None | False | 7191.0 | 0 | 4044140 | 156940 | None | SE12 | b) Upright mounting type without earth Switch
i. Live Point Height 8250mm | No | 7191.0 | 7191.0 | 2.0 | False | None | None | False | None | False | 14382.0 | 0 | 4044141 | 156940 | None | SE13 | ii. Live Point Height 5750mm | No | 7191.0 | 7191.0 | 1.0 | False | None | None | False | None | False | 7191.0 | 0 | 4044142 | 156940 | None | SE14 | iii. Under hung mounting type without earth switch | No | 10815.0 | 10815.0 | 1.0 | False | None | None | False | None | False | 10815.0 | 0 | 4044143 | 156940 | None | SE15 | II. 66 kV, 2000A, 31.5 kA, class Double break motor operated Isolator Suitable for 63 mm Al tube for interconnecting bay at existing 66/11 kV Substation.
i.upright mounting type with earth switch (Live point Height 4250 mm) | No | 5119.0 | 5119.0 | 1.0 | False | None | None | False | None | False | 5119.0 | 0 | 4044144 | 156940 | None | SE16 | III. 66 kV, 1250A, 31.5 kA, class Double break motor operated Isolator -
i. upright mounting type without earth switch (Live point Height 4250 mm) For replacing existing 2 nos line side Bus Isolator, 2 nos Transformer side Bus isolator & 1 no PT isolator at the existing 66/11 kV Banashankari sub-station. | No | 5119.0 | 5119.0 | 5.0 | False | None | None | False | None | False | 25595.0 | 0 | 4044145 | 156940 | None | SE17 | Releasing & re-erection of existing 66 kV Isolators (Tr-1no & Bus-2 nos) at the 66/11 kV Banashankari sub-sttaion | No | 9412.0 | 9412.0 | 3.0 | False | None | None | False | None | False | 28236.0 | 0 | 4044146 | 156940 | None | SE18 | SURGE ARRESTOR :(Procelain housing)
Remarks: All the Surge Arresters are with Surge Monitors & Insulating Base
198kV, 10kA, Class-III, Metal Oxide Type | No | 1834.0 | 1834.0 | 9.0 | False | None | None | False | None | False | 16506.0 | 0 | 4044147 | 156940 | None | SE19 | SURGE ARRESTOR :(Procelain housing)
Remarks: All the Surge Arresters are with Surge Monitors & Insulating Base
60kV, 10kA, Class-III, Metal Oxide Type
Note Refer Techno Commercial Sheet for detail break up. | No | 244.34 | 244.34 | 12.0 | False | None | None | False | None | False | 2932.08 | 0 | 4044148 | 156940 | None | SE20 | Erection and Testing & commissioning of 220kV Relay & Protection Panel, SAS and LCC-Total
Note:Refer Techno Commercial sheets for detailed break up. | No | 77514.0 | 77514.0 | 8.0 | False | None | None | False | None | False | 620112.0 | 0 | 4044149 | 156940 | None | SE21 | Erection and Testing & commissioning of 66kV Relay & Protection Panel, SAS and LCC-Total
Note:Refer Techno Commercial sheets for detailed break up. | No | 55840.0 | 55840.0 | 13.0 | False | None | None | False | None | False | 725920.0 | 0 | 4044150 | 156940 | None | SE22 | 8.11kV Line - Type 11L (as per Annexure RPP7- SAS) (Provision for 2 feeders to be made in one panel and provision for one BC and one spare feeder to be made in one panel, provision for two capacitor bank feeders to be made in one panel) | No | 23165.0 | 23165.0 | 15.0 | False | None | None | False | None | False | 347475.0 | 0 | 4044151 | 156940 | None | SE23 | Installation, integration, testing & commissioning of C&R panels with SAS supplied by a company for new bay extension with their existing Automation System .
Note: Integration to existing SAS system at the existing sub-station and configuration to remote gateway to send the data to SLDC
i.220kV feeder C&F panels with BCUs including integration with existing Bus bar scheme | No | 242000.0 | 242000.0 | 1.0 | False | None | None | False | None | False | 242000.0 | 0 | 4044152 | 156940 | None | SE24 | ii.66kV feeder C&F panels with BCUs including integration with existing Bus bar scheme | No | 211750.0 | 211750.0 | 1.0 | False | None | None | False | None | False | 211750.0 | 0 | 4044153 | 156940 | None | SE25 | Erection of Station structures & Mounting Structures (including Bolts & nuts) | t | 4666.0 | 4666.0 | 27.134 | False | None | None | False | None | False | 126607.244 | 0 | 4044154 | 156940 | None | SE26 | INSULATORS:
Post Insulators - Cylindrical Solid Core Insulators as per IS:5350, Part-II & III as per technical specification
For 66KV Side-1 Unit/Stack
i. High Level Post Insulators (for 150MVA Tr.-6 Nos.31.5 MVA Tr.-6 Nos,). | No | 244.0 | 244.0 | 15.0 | False | None | None | False | None | False | 3660.0 | 0 | 4044155 | 156940 | None | SE27 | Auxiliary Transformers with oil, cable termination type on both HT & LT, outdoor type with off load tap changer in steps of 2.5% as per specification including LT Distribution box with copper windings:
250 kVA, 11 kV/433 V Auxillary Transformers, 3 Ph, Delta / star Dyn11. | No | 22729.0 | 22729.0 | 2.0 | False | None | None | False | None | False | 45458.0 | 0 | 4044156 | 156940 | None | SE28 | LTAC panel (indoor):
415V, LTAC panel (2 I/C ACB 800A+2 O/G SFU, 200A + 8 O/G SFU 100A+14 O/G SFU, 63A+12 O/G SFU, 32A+1B/C SFU, 800A+1DG Change over switch 300A etc. | Set | 4175.0 | 4175.0 | 1.0 | False | None | None | False | None | False | 4175.0 | 0 | 4044157 | 156940 | None | SE29 | a) Power Cable from Auxiliary Transformers to LTAC panel:
1.1 kV PVC Insulated 240 Sqmm Al.cable 3.5 core with glands /lugs/Ferrules | Mtr | 32.28 | 32.28 | 100.0 | False | None | None | False | None | False | 3228.0 | 0 | 4044158 | 156940 | None | SE30 | b) PVC insulated aluminium power cable (AC supply for lighting etc):
1.1 kV PVC Insulated 240 Sqmm Al.cable 3.5 core with glands /lugs/Ferrules | Mtr | 31.14 | 31.14 | 1000.0 | False | None | None | False | None | False | 31140.0 | 0 | 4044159 | 156940 | None | SE31 | AC Distribution Box (outdoor):
AC Distribution Box single front type, 6 terminals, 750x1350x300mm , 1 I/c of 100A, MCCB 20kA+6 O/G MCB 16A+ 1 O/G of 100A, HRC fuse | No | 4175.0 | 4175.0 | 2.0 | False | None | None | False | None | False | 8350.0 | 0 | 4044160 | 156940 | None | SE32 | Station Battery
2x220V, 600AH Battery Set consisting of 110 No. Cells per bank with float (2 Nos.) & boost cum float (2 Nos.) type battery charger including control panels, change over arrangements etc., complete along with 2 separate DC Distribution Panels (Indoor) each considering of 1I/C+20 O/G SFU 60A + 20 O/G SFU 30A.
Note: The rating of the Battery & Battery charger is indicative only. However, the successful bidder has to provide adequate rating of battery & battery charger along with battery sizing calculation | Set | 36146.0 | 36146.0 | 1.0 | False | None | None | False | None | False | 36146.0 | 0 | 4044161 | 156940 | None | SE33 | Battery Charger suitable for 2x220V, 600AH Battery Set consisting of 110 No. Cells per bank with float (2 Nos.) & boost cum float (2 Nos.) type battery charger including control panels, change over arrangements etc., complete along with 2 separate DC Distribution Panels (Indoor) each considering of 1I/C+20 O/G SFU 60A + 20 O/G SFU 30A.
Note: The rating of the Battery & Battery charger is indicative only. However, the successful bidder has to provide adequate rating of battery & battery charger along with battery sizing calculation | Set | 48770.0 | 48770.0 | 1.0 | False | None | None | False | None | False | 48770.0 | 0 | 4044162 | 156940 | None | SE34 | Laying of Coper Control Cable, PVC insulated aluminium power cable along with glands/lugs/ferrules -Total
Note:Refer Techno Commercial sheets for detailed break up. | Km | 15000.0 | 15000.0 | 53.4 | False | None | None | False | None | False | 801000.0 | 0 | 4044163 | 156940 | None | SE35 | 11kV Switchgear:
11kV MCVCB: 500MVA, 31.5 kA, 1600A for feeders (1F+1AP) Annuciator panel shall be simplex panel instead of desk type mentioned else where in specification.
Note: 1. The switchgear for capacitor bank shall have necessary Over voltage / Under voltage / Circulating current relays and other protection relays as per specification
2. The Remote Announciation cum Control panel is Simplex type.
3.The Electronic Trivector meters with 0.2s accuracy class with ABT & TOD features & DLMS ICS compliant features has to provided.
4.The Switchgear will be supplied by KPTCL and the Bidder has to quote for complete scope of erection of Switchgear including moving the Switchgear from the point of unloading to the point of erection, erection of the complete Switchgear, wiring of Switchgear, testing & commissioning etc., complete.
5.Auxilliary supply will be extended from 66/11kV Sub-station existing in the premises | Set | 394693.0 | 394693.0 | 1.0 | False | None | None | False | None | False | 394693.0 | 0 | 4044164 | 156940 | None | SE36 | 11kV UG Cable with the required cable terminations:
[a] 11kV XLPE 95 Sq.mm Aluminium Cable-3 Core ( for auxiliary transformers from the 11kV Switchgear of 66/11KV Sub-station) | Mtr | 72.0 | 72.0 | 400.0 | False | None | None | False | None | False | 28800.0 | 0 | 4044165 | 156940 | None | SE37 | b) 11kV Cable Termination Kit suitable for 95 Sq.mm 3 Core as per Technical Specification. | No | 2658.0 | 2658.0 | 4.0 | False | None | None | False | None | False | 10632.0 | 0 | 4044166 | 156940 | None | SE38 | 220 kV XLPE Cable & termination:
i. 220kV, 1000Sq.mm single core XLPE insulated, copper conductor, lead sheathed cable required for connecting GIS module to 220/66KV Transformer as per specification. | Mtr | 392.67 | 392.67 | 200.0 | False | None | None | False | None | False | 78534.0 | 0 | 4044167 | 156940 | None | SE39 | ii. 220kV Pre moulded outdoor cable termination kit for 1000Sq.mm XLPE UG Cable (as per specification). | No | 244420.0 | 244420.0 | 6.0 | False | None | None | False | None | False | 1466520.0 | 0 | 4044168 | 156940 | None | SE40 | iii.Indoor type suitable for plug in type cable termination of GIS modules confirm to IEC 62271-209 for 220KV 1000Sq.mm XLPE cable to 220/66kV Transformer | No | 244420.0 | 244420.0 | 6.0 | False | None | None | False | None | False | 1466520.0 | 0 | 4044169 | 156940 | None | SE41 | iv.Three phase Link box along with sheath earthing cables etc as per specification. | No | 53337.0 | 53337.0 | 2.0 | False | None | None | False | None | False | 106674.0 | 0 | 4044170 | 156940 | None | SE42 | v.Single phase Link box along with sheath earthing cables etc as per specification. | No | 17779.0 | 17779.0 | 6.0 | False | None | None | False | None | False | 106674.0 | 0 | 4044171 | 156940 | None | SE43 | Smart Surveillance system (CCTV): using PTZ & fixed cameras, OFC monitoring system, HMI, etc as per bid specification.
Note:
1. Exact Location of the cameras to be given at the time of commissioning.
2. P/S unit to be housed with outdooe box with IP 66 compliance and provision of ELCB to be provided by thr integrator.
3. 6F Armoured Multimode OFC to be used for interconnectivities between cameras & HMI.
4. One no.of addittional work station and network switch (at 220kV Khodays) as per specification.
5. The requirement of materials will be furnished by SEE, SCADA, Bangalore
i. PTZ Camera:
Speifications:
Lens type-Auto Focus with optical Zoom of 30x, Digital Zoom+10x.
Pan Angle:360 degree endless .
Tilt angle:210 degrees with e-flip/higher. Zoom:30X Optical and 12X Digital
Mode:Day & Night. Image size:-Full HD.
streaming:High speed
Weather Proof:IP 66 complaint.
Network Protocol:TCP/IP should be compliant of any other protocol required.
Connectivity:Cat 6/Optical fibre. Ethernet:10 Base-T/100 Base-TX (RJ45)
Power source:Both self powered & externally powered.
Vol:06, Pg No: 52, Sl.no:34.1 & Pg.no:128, Sl.No: e i | No | 1210.0 | 1210.0 | 4.0 | False | None | None | False | None | False | 4840.0 | 0 | 4044172 | 156940 | None | SE44 | ii. Fixed Camera:
Speifications:
Lens type:-Bi-focal auto iris with 10x digital zoom.
Mode:Day/Night
Image size:720x486 (NTSC).
Streaming:High Speed.
Weather proof:IP 66 complaint Network Protocol:TCP/IP should be complaint of any other protocol required.
Connectivity:Cat 6/optical fibre
Ethernet:10Base-t/100Base-TX(RJ45) Power source:both Self powered/externally powered. | No | 1210.0 | 1210.0 | 11.0 | False | None | None | False | None | False | 13310.0 | 0 | 4044173 | 156940 | None | SE45 | iii. HMI (Industrial Grade PC)
a. Operating System : Windows 10 Professional
b. CPU : Intel i7 quad core processor or latest
c. RAM : 32 GB or higher
d. Network : TCP/IP
e. Graphics adaptor : NVIDA Quadra digital video
f. pipeline or higher
g. Hard disk : 1.5 TB (500x3) RAID 1 configuration
h. External drives : Blu-Ray RW and DVD RW
i. Monitor : 24 inch dual screen
j. Keyboard / Mouse : Wireless
k. Network adaptor
l. LAN switch
m. Fibre LIU | No | 81237.0 | 81237.0 | 1.0 | False | None | None | False | None | False | 81237.0 | 0 | 4044174 | 156940 | None | SE46 | iv. OFC: 6F Armoured Multimode with LIU along with required number of SC/ST connectors and accessories | Set | 60500.0 | 60500.0 | 1.0 | False | None | None | False | None | False | 60500.0 | 0 | 4044175 | 156940 | None | SE47 | Station and Yard Lighting/Lightning protection (Outdoor):
Remark: 1 No.of Lighting Mast (LM0 are proposed for lighting protection and illumination of the station Yard. The quantity of lighting /lighting mast indicated are located such that the entire station yard with equipments is protected against lightining. However any, additional ligting mast may be provided for sufficient illumination and lightning protection (DSLP) of yard, if necessary. The design of lighting outdoor & indoor is also in the scope of the bidder as specified elsewhere in the technical specification. The scope also includes supply & erection of lighting fixures, lighting mast panels with timer, contactor, control cable etc., suitable 2.5M lightining spikes shall be provided on top of GIS for building for lightining protection
i. Supply of LED flood light luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of antiglare clear diff user with Injection moulded polycarbonate/clearglassmaterial, delivering superior light output Rated life Burning Hrs 50000hr @ Lumen Maintenance of 70%,CCT greater than 5500K, IP66 optical and electrical compartment & impact resistance of complete luminaire greater than IK08. Power Factor greater than 0.9withmains,SurgeProtection-Min5KV along with Overvoltage/Overload, shortcircuit/miss-wiring protection.Compatible for pole mauling without erdia of 40mm to 50mm.Universal Voltage drivert ooperate wide voltage range from 100V to 270V 50/60 Hz application. Compliance to IS10322 / IEC60598, LM79 & LM80 Adherence with RoHS. UL approved MCPCB. To paccess street light with singles crew to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with. WSystem Power consumption. LED Efficiency greater than 1301m/w, nominal CRI greater than 75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO9001:2008. Housing with supplier wordmark/name shall be Engraved /Embossing on the die cast housing /Body part Warranty of 2Years against any manufacturing defect working under standard electrical condition same as mentionedaboveshouldbegivenbyLEDmanufacturer&Cree/Nichia/Lumileds/Osrammake LED Source. LED Floodlight 240W( 6 Light / mast= 6 No.s) Note: The Design of lighting outdoor and indoor in station yard and GIS Building etc., is in the scope of bidder as specified in the technical specification. | No | 162.0 | 162.0 | 6.0 | False | None | None | False | None | False | 972.0 | 0 | 4044176 | 156940 | None | SE48 | ii 2C x 2.5Sqmm Copper Cable from Light fitting to lighting panel mounted at Bottom of mast for each fitting required 30mtr cable( One additional run/mast provision made for future use)
[30 Mtr *1 Mast *7 run = 210 Mtrs ] | Mtr | 15.0 | 15.0 | 210.0 | False | None | None | False | None | False | 3150.0 | 0 | 4044177 | 156940 | None | SE49 | Communication Equipments: 1.SDH Equipment
(STM-16 MADM UPTO 3 MSP PROTECTED DIRECTIONS)-BASE EQUIPMENT (COMMON CARDS, CROSS CONNECT/CONTROL CARDS, OPTICAL BASECARDS, POWER SUPPLY CARDS, POWER CABLING, OTHER HARDWARE ANDACCESSORIES INCLUDING SUB RACKS, PATCH CORD, DDF ETC FULLY EQUIPEDEXCLUDING OPTICAL INTERFACE & TRIBUTARY CARDS | No | 42955.0 | 42955.0 | 1.0 | False | None | None | False | None | False | 42955.0 | 0 | 4044178 | 156940 | None | SE50 | Installation of Cabinet Equipment to house SDH Equipment + Optical cards + Tributary Cards, Drop/Insert MUX Equipments and DACS Equipment | Set | 1210.0 | 1210.0 | 1.0 | False | None | None | False | None | False | 1210.0 | 0 | 4044179 | 156940 | None | SE51 | Digital protection coupler with 8 command version (Direct fiber intype) | No | 7513.0 | 7513.0 | 2.0 | False | None | None | False | None | False | 15026.0 | 0 | 4044180 | 156940 | None | SE52 | 48V Battery Charger suitable for 200AH Battery set | No | 25599.0 | 25599.0 | 1.0 | False | None | None | False | None | False | 25599.0 | 0 | 4044181 | 156940 | None | SE53 | 48V, 200AH Battery Set | No | 3573.0 | 3573.0 | 1.0 | False | None | None | False | None | False | 3573.0 | 0 | 4044182 | 156940 | None | SE54 | Modification work in the existing 66/11KV sub station
i) Existing 66/11kV transformers will have to be made compatible to sub-station automation, by replacing the 110V DC contacts by 220V DC contacts in RTCC and OLTC and providing transducers for remote WTI & OTI indications and remote tap position indication. | No | 242000.0 | 242000.0 | 3.0 | False | None | None | False | None | False | 726000.0 | 0 | 4044183 | 156940 | None | SE55 | ii) Shifting of existing RTCC panels located in the existing control room to proposed Kiosk room & wiring from the existing transformer to the RTCC panels. | No | 61698.0 | 61698.0 | 3.0 | False | None | None | False | None | False | 185094.0 | 0 | 4044184 | 156940 | None | SE56 | iii) Existing 66kV Circuit Breakers will have to be made compatible to sub-station automation and 220V DC, by replacing the 110V DC contacts by 220V DC contacts and other required modifications. | No | 242000.0 | 242000.0 | 5.0 | False | None | None | False | None | False | 1210000.0 | 0 | 4044185 | 156940 | None | SE57 | iv) Modification of existing 11kV Switchgear has to be made compatible for SAS regarding control, Monitoring and measures etc., and also existing switchgear is to be made suitable for 220V DC system, as the existing 11kV switchgear is with 110V DC. | Set | 242000.0 | 242000.0 | 30.0 | False | None | None | False | None | False | 7260000.0 | 0 | 4044186 | 156940 | None | SE58 | Motor operating mechanism suitable for existing 66 kV Isolators | No | 50000.0 | 50000.0 | 3.0 | False | None | None | False | None | False | 150000.0 | 0 | 4044187 | 156940 | None | SE59 | Earth Mat Formation:
Supplying and laying MS flat 75 x 12 mm flat welding and applying ACB paint to welded portion and covering with soil as per drawing / standards without sodium bentonate clay (all materials to be supplied by the contractor) | Mtr | 839.0 | 839.0 | 4800.0 | False | None | None | False | None | False | 4027200.0 | 0 | 4044188 | 156940 | None | SE60 | Grounding of equipments with 75x12 mm G I flat and
connecting equipment to the earthmat/ground pit. Each point
of earthing with all formation works like bending, twisting, drilling of holes and connecting by welding (inclusive of all T&P and consumables) to the earthmat/ground pit/point of
earth connection, all the materials supplied by the
contractor | Mtr | 916.0 | 916.0 | 845.0 | False | None | None | False | None | False | 774020.0 | 0 | 4044189 | 156940 | None | SE61 | Providing 25mm dia, 1.05mtr. Long Earth mat spike of MS Rod including bending top 50mm etc and connecting to earthmat flat as per specification. | No | 453.0 | 453.0 | 95.0 | False | None | None | False | None | False | 43035.0 | 0 | 4044190 | 156940 | None | SE62 | Grounding of equipment by providing C.I . Pipe of 100mm ID 13mm thick 2.75mtr long with 2 part clamp out of GI flat 50x6 mmcontinuously welded alround the pipe using cast iron
welding electrodes as per drawing including the cost of
excavation (All materials to be supplied by the contractor) | No | 16283.0 | 16283.0 | 33.0 | False | None | None | False | None | False | 537339.0 | 0 | 4044191 | 156940 | None | SE63 | Suppling and fixing 450mm dia x450mm height 1.5" to 2" Hume pipe collars for earth pits. | No | 1499.0 | 1499.0 | 33.0 | False | None | None | False | None | False | 49467.0 | 0 | 4044192 | 156940 | None | SE64 | Providing Deep Bore earthing
Sinking bore of 150 mm clear dia using fast rig including fixing of 40 mm dia MS Rod, including jointing the pipes as per KPTCL standard and providing sodium bentonite treatment in the annular space, including transportation of rig and other supporting vehicles etc., complete as per the directions of Engineer in charge including cost of MS Rod & sodium bentonit
Drilling 150 mm dia bore
( 4Mtr x 3 No) = 12 Rmtr. | Mtr | 848.0 | 848.0 | 12.0 | False | None | None | False | None | False | 10176.0 | 0 | 4044193 | 156940 | None | SE65 | 40mm dia MS rod | Mtr | 940.0 | 940.0 | 12.0 | False | None | None | False | None | False | 11280.0 | 0 | 4044194 | 156940 | None | SE66 | Bentonite clay | Kg | 25.0 | 25.0 | 120.0 | False | None | None | False | None | False | 3000.0 | 0 | 4044195 | 156940 | None | SE67 | Cost of GI Flat for joining two rods by welding to obtain continuous length
GI flats for joining two rods by welding to obtain continuos length(Including Material labour etc,. Complete)( Per Joint=Nos) | No | 995.0 | 995.0 | 3.0 | False | None | None | False | None | False | 2985.0 | 0 | 4044196 | 156940 | None | SE68 | Dismantling of existing towers for running 66kV 1000sqmm UG cable by making LILO of existing 66kV REMCO-RR Nagar line.
66kV Double circuit NB type tower in the existing line without stubs | MT | 5723.0 | 5723.0 | 1.0 | False | None | None | False | None | False | 5723.0 | 0 | 4044197 | 156940 | None | SE69 | Dismantling of existing equipments at the existing 66/11kV Banashankari sub-station
1. Existing 66kV C&R Panels 66kv line Panel | No | 4191.0 | 4191.0 | 2.0 | False | None | None | False | None | False | 8382.0 | 0 | 4044198 | 156940 | None | SE70 | 2. 66/11kv Power Transformer Panel | No | 4191.0 | 4191.0 | 3.0 | False | None | None | False | None | False | 12573.0 | 0 | 4044199 | 156940 | None | SE71 | 3. ACDB | No | 2466.0 | 2466.0 | 1.0 | False | None | None | False | None | False | 2466.0 | 0 | 4044200 | 156940 | None | SE72 | 4. DCDB | No | 2466.0 | 2466.0 | 1.0 | False | None | None | False | None | False | 2466.0 | 0 | 4044201 | 156940 | None | SE73 | 5. I-Beam Structures (20Nos of Beams, each 0.2t) | t | 5723.0 | 5723.0 | 4.0 | False | None | None | False | None | False | 22892.0 | 0 | 4044202 | 156940 | None | SE74 | 6. Auxillary Transformer | No | 18592.0 | 18592.0 | 1.0 | False | None | None | False | None | False | 18592.0 | 0 | 4044203 | 156940 | None | SE75 | 7. 110V DC Battery Set | No | 11621.0 | 11621.0 | 1.0 | False | None | None | False | None | False | 11621.0 | 0 | 4044204 | 156940 | None | SE76 | 8. 110V DC Battery charger | No | 1147.0 | 1147.0 | 1.0 | False | None | None | False | None | False | 1147.0 | 0 | 4044205 | 156940 | None | SE77 | 9. 66kV Isolator without earth switch | No | 4293.0 | 4293.0 | 5.0 | False | None | None | False | None | False | 21465.0 | 0 | 4044206 | 156940 | None | SE78 | 10. Isolator mounting structure ( 5Nos = 2.375 t) | t | 5723.0 | 5723.0 | 2.375 | False | None | None | False | None | False | 13592.125 | 0 | 4044207 | 156940 | None | SE79 | Existing Strung bus conductor (Drake) No=Bay | No | 19587.0 | 19587.0 | 1.0 | False | None | None | False | None | False | 19587.0 | 0 | 4044208 | 156940 | None | SE80 | PVC insulated - Copper control cables with lugs/Ferrules
Note:Refer Techno Commercial sheets for detailed break up. | Mtr | 15.0 | 15.0 | 1650.0 | False | None | None | False | None | False | 24750.0 | 0 |
| 1726893213000 | 0 | None | None | Sub-Station | Cable Erection | 31979687.4 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
4044209 | 156941 | None | CE1 | 220kV /66kV UG Cable Surveying: Detailed survey along the route alignment by using Modern Survey equipment like DGPS /Total stations / Digital theodolites / GPS including profiling by using computer aided techniques as detailed in the scope of work, includes the
following:
Drawing the route profile including features like Roads, Railway lines, drains,
park, gardens, P&T Lines, Railways crossing etc.,
a) Preparation of cable route profile and final cable route alignment, marking lines
and grades.
Leveling of the profile with reference to Survey of India bench marks (MSL).
b)Line Schedule along the Right of Way.
c)Soil resistivity along the selected route with measurement at a distance not
exceeding 2 km.
d) Route marking along the route with GPS Co-ordinates at every 50 m duly marking road/power line/telecommunication/railway line crossings.
e) Making 150 mm dia bore holes for a depth not less than 3 m or refusal strata at every 50 m for soil classification along with GPS Co-ordinates for each bore holes and back filling of bore holes on completion of work.
f) Burgie details and providing GPS, Co-ordinates at every 50 m, turning points including permanent marks, like poles, telephones lines, buildings etc.,
g)Submission of detailed consolidated final report for surveying work done appending all the reports including all relevant information collected during survey, calibration certificates of the instruments used for the work, photos/videos taken at site and submitting soft copies of all documents and hard copy of reports in 6 sets.
h)The detailed report shall contain detailed Survey Report/Soil Resistivity Report/ Line Schedule/Land schedule/Geo referenced and superimposed on the line corridor. | Kms | 15651.0 | 15651.0 | 15.481 | False | None | None | False | None | False | 242293.131 | 0 | 4044210 | 156941 | None | CE2 | Laying including Testing & Commissioning :
220kV EHT single core XLPE copper cable in trefoil, tapping, fixing pipes for drain and gate crossing as per drawings & specification in trench pipes, ducts by pulling, drawing etc., handling of cable
drums, paving out cables using standard cable installation equipment.
NOTE: The rate per km shall include laying one circuit per km each circuit consisting of 3 nos. of single core cables including transport
of cable drums material equipment to site and retaining unused items to stores
( 4Rkms x 2Ckts X 10% extra for bending, deep excavtion, etc.,) | Ckt Kms | 1178000.0 | 1178000.0 | 9.777 | False | None | None | False | None | False | 11517306.0 | 0 | 4044211 | 156941 | None | CE3 | Handling and making normal straight joints/Insulated shield break type Joint for EHV power cables with all consumables at site etc.,- 220kV complete | Nos | 131105.0 | 131105.0 | 54.0 | False | None | None | False | None | False | 7079670.0 | 0 | 4044212 | 156941 | None | CE4 | Handling and making of cable end termination for EHV single core XLPE copper cable | Nos | 141271.0 | 141271.0 | 12.0 | False | None | None | False | None | False | 1695252.0 | 0 | 4044213 | 156941 | None | CE5 | Erection of Single phase/ earth link box at Joint bay with connecting earth leads, all lugs, fixtures, clamps bolts and nuts complete-220Kv (for Straight/Cross Bonds) | Nos | 9883.67 | 9883.67 | 3.0 | False | None | None | False | None | False | 29651.01 | 0 | 4044214 | 156941 | None | CE6 | Erection of Three phase earth link box at Joint bay with connecting earth leads, all lugs, fixtures, clamps bolts and nuts complete-220Kv (for Straight/Cross Bonds) | Nos | 58473.0 | 58473.0 | 21.0 | False | None | None | False | None | False | 1227933.0 | 0 | 4044215 | 156941 | None | CE7 | Laying including Testing & Commissioning :
66kV EHT single core XLPE copper cable in trefoil, tapping, fixing pipes for drain and gate crossing as per drawings & specification in trench pipes, ducts by pulling, drawing etc., handling of cable drums, paving out cables using standard cable installation equipment.
NOTE: The rate per km shall include laying one circuit per km each circuit consisting of 3 nos. of single core cables including transport of cable drums material equipment to site and retaining unused items to stores | Ckt Kms | 406000.0 | 406000.0 | 7.916 | False | None | None | False | None | False | 3213896.0 | 0 | 4044216 | 156941 | None | CE8 | Handling and making of cable end termination for 66kV EHV single core XLPE copper cable-66KV | Nos | 59035.0 | 59035.0 | 18.0 | False | None | None | False | None | False | 1062630.0 | 0 | 4044217 | 156941 | None | CE9 | Handling and making normal straight joints/Insulated shield break type Joint for EHV power cables with all consumables at site etc., complete-66kV | Nos | 59035.0 | 59035.0 | 42.0 | False | None | None | False | None | False | 2479470.0 | 0 | 4044218 | 156941 | None | CE10 | Erection of Single phase/Three phase earth link box at Joint bay with connecting earth leads, all lugs, fixtures, clamps bolts and nuts complete (for Straight/Cross Bonds)-66kV | Nos | 44275.0 | 44275.0 | 22.0 | False | None | None | False | None | False | 974050.0 | 0 | 4044219 | 156941 | None | CE11 | Erection of Transmision Line Towers (including tower accessories,etc., except GI angle with Barbed wire & Grounding materials)
Note:
(i)The Bidders are required to quote the rates taking in to consideration of the charges for sorting of towers, loading, unloading, stub setting, aligning,fixing of tower accessories,etc., except GI angle with Barbed wire & Grounding materials, dismantling & transportation of templates from one location to another and tack welding.
(ii)Rate to be quoted on per t Basis. | Nos | 41653.13 | 41653.13 | 2.0 | False | None | None | False | None | False | 83306.26 | 0 | 4044220 | 156941 | None | CE12 | Tower accessories:
a. Supplying and fixing GI angle 45 x 45 X 5mm, 1Mtr length with cleats, bolts nuts as per specification and fixing above 0.5mtr length each at inner and outer surface of tower to facilitate running of barbed wire | Set | 4121.0 | 4121.0 | 2.0 | False | None | None | False | None | False | 8242.0 | 0 | 4044221 | 156941 | None | CE13 | Supplying and fixing Barbed wire | Mtr | 76.0 | 76.0 | 90.0 | False | None | None | False | None | False | 6840.0 | 0 | 4044222 | 156941 | None | CE14 | c.Grounding of towers including cost of 40 mm dia 2.5 mm thick,class 'C' G.I. Pipe of 3 metres length as per specification with 50 X 6 mm GI Flats 3 metrelong, salt, charcoal, including
excavation charges | Set | 7335.0 | 7335.0 | 2.0 | False | None | None | False | None | False | 14670.0 | 0 | 4044223 | 156941 | None | CE15 | Conductor & conductor accessories:
Paving out conductor from anchor to anchor normally spaced at 5 spans with 4 tangent towers in between, including providing stays at each anchor points and jointing of conductors, hoisting and fixing of insulator string, armour rods, vibration dampers, including the cost of T&P materials like comealong, wire ropes, pulley, rollers, suspension clamps, compression jointing machines with bits, drum stands, manila ropes, truckker and jeep etc.,
Stringing of ACSR Conductor / HPC without allowing the conductor to touch the ground
and without damaging the conductor | Kms | 11000.0 | 11000.0 | 0.2 | False | None | None | False | None | False | 2200.0 | 0 | 4044224 | 156941 | None | CE16 | Laying of 48 fibre dual window mono mode (DWMM) optical fibre cable as per drawings & specifications | Ckt Kms | 38000.0 | 38000.0 | 16.25 | False | None | None | False | None | False | 617500.0 | 0 | 4044225 | 156941 | None | CE17 | Handling and making Normal straight joint closures for 48Fiber unarmoured Under Ground FO cable with all consumables at site complete. | Kit | 6660.0 | 6660.0 | 13.0 | False | None | None | False | None | False | 86580.0 | 0 | 4044226 | 156941 | None | CE18 | OFC end terminal (LIU suitable for 12F/24F/48F) | Nos | 14508.0 | 14508.0 | 10.0 | False | None | None | False | None | False | 145080.0 | 0 | 4044227 | 156941 | None | CE19 | Grounding of equipments by providing cast iron pipe of 100 mm ID 13mm thickness , 2.75 m long with 2 part clamp out of GI flat 50X6 mm as per drawing including the cost of excavation. | Nos | 16283.0 | 16283.0 | 20.0 | False | None | None | False | None | False | 325660.0 | 0 | 4044228 | 156941 | None | CE20 | OPGW Cable:
Installation, testing & commissioning of 24F/48F OPGW cable along with associated hardware fittings as per technical specification for LIVE LINE condition | Kms | 88000.0 | 88000.0 | 12.0 | False | None | None | False | None | False | 1056000.0 | 0 | 4044229 | 156941 | None | CE21 | Installation, testing & commissioning of FODP for 24F/48F/96F : Indoor type, rack mounted with FCPC coupling and pigtails | Nos | 26620.0 | 26620.0 | 1.0 | False | None | None | False | None | False | 26620.0 | 0 | 4044230 | 156941 | None | CE22 | Laying, installation, testing & commissioning of 12/24/48 F Optical fibre approach cable in switch yards of 400 kV & 220 kV (Including hardware) along with HDPE Pipe | Kms | 61000.0 | 61000.0 | 1.0 | False | None | None | False | None | False | 61000.0 | 0 | 4044231 | 156941 | None | CE23 | UG OFC to OPGW Joint kit:
Joint Box (48 Fiber) including Coiling bracket as per requirement for looping/coiling of 30 meters of cable as per technical requirement | Nos | 11919.0 | 11919.0 | 2.0 | False | None | None | False | None | False | 23838.0 | 0 |
| 1726893213000 | 0 | None | None | Sub-Station | Station Mandatory Spares | 41250517.72 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
4044232 | 156942 | None | MS1 | A. For GIS Common Spares, Maintenance and Testing Tools
1.SF6 Gas pressure relief devices of each type | Set | 32239.0 | 32239.0 | 1.0 | False | None | None | False | None | False | 32239.0 | 0 | 4044233 | 156942 | None | MS2 | 2.Pressure gauges (of each type) along with coupling device | Set | 88176.0 | 88176.0 | 1.0 | False | None | None | False | None | False | 88176.0 | 0 | 4044234 | 156942 | None | MS3 | 3.Rubber Gaskets, “o” Rings and seals for SF6 gas | Set | 102657.0 | 102657.0 | 1.0 | False | None | None | False | None | False | 102657.0 | 0 | 4044235 | 156942 | None | MS4 | 4.Molecular filter for SF6 gas | Set | 180569.0 | 180569.0 | 3.0 | False | None | None | False | None | False | 541707.0 | 0 | 4044236 | 156942 | None | MS5 | 5.Density Monitors for SF6 gas | No | 104047.68 | 104047.68 | 2.0 | False | None | None | False | None | False | 208095.36 | 0 | 4044237 | 156942 | None | MS6 | 6.All types of Control Valves for SF6 gas | Set | 4000.0 | 4000.0 | 1.0 | False | None | None | False | None | False | 4000.0 | 0 | 4044238 | 156942 | None | MS7 | 7.SF6 gas 10%** of total gas requirement subject to min of 30Kgs. | LS | 1894398.0 | 1894398.0 | 1.0 | False | None | None | False | None | False | 1894398.0 | 0 | 4044239 | 156942 | None | MS8 | 8. 220 / 66 kV Bushing for connection to GIS duct | Set | 431476.4 | 431476.4 | 1.0 | False | None | None | False | None | False | 431476.4 | 0 | 4044240 | 156942 | None | MS9 | B.CIRCUIT BREAKERS:- GIS
1.SF6 CIRCUIT BREAKER: All spares shall be for 220KV and 66KV separately.
a) 220 kV, Single ph., 2000A Circuit Breaker interrupting chamber complete with all necessary apparatus.
Note: The spares under sl. Nos. MS9 to MS39 shall be for 220KV & 66KV rating separately, prices shall be quoted accordingly. | No | 2903380.0 | 2903380.0 | 1.0 | False | None | None | False | None | False | 2903380.0 | 0 | 4044241 | 156942 | None | MS10 | b) 66 kV, Single ph., 2000A Circuit Breaker interrupting chamber complete with all necessary apparatus. | No | 31208.0 | 31208.0 | 1.0 | False | None | None | False | None | False | 31208.0 | 0 | 4044242 | 156942 | None | MS11 | 2.Rubber gaskets, O' rings and seals | Set | 10284.12 | 10284.12 | 1.0 | False | None | None | False | None | False | 10284.12 | 0 | 4044243 | 156942 | None | MS12 | 3.Trip coils with resistor. | No | 4152.0 | 4152.0 | 3.0 | False | None | None | False | None | False | 12456.0 | 0 | 4044244 | 156942 | None | MS13 | 4.Closing coils with resistor | No | 4152.0 | 4152.0 | 3.0 | False | None | None | False | None | False | 12456.0 | 0 | 4044245 | 156942 | None | MS14 | 5.Relays, Power contactors, push buttons, timers & MCB etc. | Set | 53031.0 | 53031.0 | 1.0 | False | None | None | False | None | False | 53031.0 | 0 | 4044246 | 156942 | None | MS15 | 6.Closing assembly/ valve | No | 4000.0 | 4000.0 | 1.0 | False | None | None | False | None | False | 4000.0 | 0 | 4044247 | 156942 | None | MS16 | 7.Trip assembly/ valve | No | 4000.0 | 4000.0 | 1.0 | False | None | None | False | None | False | 4000.0 | 0 | 4044248 | 156942 | None | MS17 | 8.Pressure switches | Set | 3000.0 | 3000.0 | 1.0 | False | None | None | False | None | False | 3000.0 | 0 | 4044249 | 156942 | None | MS18 | 9.Auxiliary switch assembly | No | 14801.0 | 14801.0 | 1.0 | False | None | None | False | None | False | 14801.0 | 0 | 4044250 | 156942 | None | MS19 | 10.Operation Counter | No | 6379.0 | 6379.0 | 1.0 | False | None | None | False | None | False | 6379.0 | 0 | 4044251 | 156942 | None | MS20 | 11.Rupture disc/diaphragm | No | 35673.0 | 35673.0 | 1.0 | False | None | None | False | None | False | 35673.0 | 0 | 4044252 | 156942 | None | MS21 | 12.Windoscope / Observing window | No | 3527.0 | 3527.0 | 1.0 | False | None | None | False | None | False | 3527.0 | 0 | 4044253 | 156942 | None | MS22 | 13.a) 220 kV, Single ph., 2000A Circuit Breaker operating mechanism, complete with all necessary connecting apparatus. | No | 433542.0 | 433542.0 | 1.0 | False | None | None | False | None | False | 433542.0 | 0 | 4044254 | 156942 | None | MS23 | 13. b) 66 kV, Single ph., 2000A Circuit Breaker operating mechanism, complete with all necessary connecting apparatus. | No | 44524.0 | 44524.0 | 1.0 | False | None | None | False | None | False | 44524.0 | 0 | 4044255 | 156942 | None | MS24 | 14.All types of coupling for SF6 gas(1 no. each type) | Set | 34641.0 | 34641.0 | 1.0 | False | None | None | False | None | False | 34641.0 | 0 | 4044256 | 156942 | None | MS25 | C. ISOLATORS & E/SWITCH GIS
1.a) 220 kV, Single ph., 1600A Disconnecting & maintenance earthing Switch internal parts, complete with all necessary gaskets, mounting hardware, etc. | Set | 2281295.0 | 2281295.0 | 1.0 | False | None | None | False | None | False | 2281295.0 | 0 | 4044257 | 156942 | None | MS26 | 1. b) 66 kV, Single ph., 1600A disconnecting & maintenance earthing Switch internal parts, complete with all necessary gaskets, mounting hardware, etc. | Set | 212216.0 | 212216.0 | 1.0 | False | None | None | False | None | False | 212216.0 | 0 | 4044258 | 156942 | None | MS27 | 2.a) Operating mechanism of 220kV, 1600A Disconnecting Switch, complete with all necessary connecting apparatus. | Set | 291254.24 | 291254.24 | 1.0 | False | None | None | False | None | False | 291254.24 | 0 | 4044259 | 156942 | None | MS28 | 2. b) Operating mechanism of 66 kV, 1600A Disconnecting Switch, complete with all necessary connecting apparatus. | Set | 636647.0 | 636647.0 | 1.0 | False | None | None | False | None | False | 636647.0 | 0 | 4044260 | 156942 | None | MS29 | 3.a) 220kV, 1600A, single phase high speed fault making Earthing switch, Internal parts complete with all necessary gaskets mounting hardware etc. | Set | 820085.0 | 820085.0 | 1.0 | False | None | None | False | None | False | 820085.0 | 0 | 4044261 | 156942 | None | MS30 | 3.b) 66 kV, single phase high speed fault making Earthing switch, Internal parts complete with all necessary gaskets mounting hardware etc. | Set | 318324.0 | 318324.0 | 1.0 | False | None | None | False | None | False | 318324.0 | 0 | 4044262 | 156942 | None | MS31 | 4.a) Operating mechanism of 220kV, 1600A, high speed fault making Earthing switch, complete with all necessary gaskets connecting apparatus. | Set | 583172.0 | 583172.0 | 1.0 | False | None | None | False | None | False | 583172.0 | 0 | 4044263 | 156942 | None | MS32 | 4.b) Operating mechanism of 66 kV, high speed fault making Earthing switch, complete with all necessary gaskets connecting apparatus. | Set | 302935.0 | 302935.0 | 1.0 | False | None | None | False | None | False | 302935.0 | 0 | 4044264 | 156942 | None | MS33 | 5.Limit switch & Aux. switches | Set | 54672.0 | 54672.0 | 1.0 | False | None | None | False | None | False | 54672.0 | 0 | 4044265 | 156942 | None | MS34 | D.CURRENT TRANSFORMER - GIS
Complete CT
1.220 kV | No | 2734056.0 | 2734056.0 | 1.0 | False | None | None | False | None | False | 2734056.0 | 0 | 4044266 | 156942 | None | MS35 | 2.66 kV | No | 727911.0 | 727911.0 | 1.0 | False | None | None | False | None | False | 727911.0 | 0 | 4044267 | 156942 | None | MS36 | E.VOLTAGE TRANSFORMER - GIS
1.Single phase VT complete with all gaskets and mounting hardware. (220 kV) | No | 644465.0 | 644465.0 | 1.0 | False | None | None | False | None | False | 644465.0 | 0 | 4044268 | 156942 | None | MS37 | 2.Single phase VT complete with all gaskets and mounting hardware. (66 kV) | No | 339513.0 | 339513.0 | 1.0 | False | None | None | False | None | False | 339513.0 | 0 | 4044269 | 156942 | None | MS38 | F.SURGE ARRESTOR - GIS
Complete L.A. including with Surge counter & accessories:
(i) 220 kV | No | 600710.0 | 600710.0 | 1.0 | False | None | None | False | None | False | 600710.0 | 0 | 4044270 | 156942 | None | MS39 | ii) 66 kV | No | 188619.0 | 188619.0 | 1.0 | False | None | None | False | None | False | 188619.0 | 0 | 4044271 | 156942 | None | MS40 | G.EMERGENCY DG SETS :
1.Set of filters (Lubeoil/fuel/Air ckt) | Set | 20397.0 | 20397.0 | 1.0 | False | None | None | False | None | False | 20397.0 | 0 | 4044272 | 156942 | None | MS41 | 2.Solenoid coil assembly | No | 16318.0 | 16318.0 | 1.0 | False | None | None | False | None | False | 16318.0 | 0 | 4044273 | 156942 | None | MS42 | 3.Self starter assembly | No | 65271.0 | 65271.0 | 1.0 | False | None | None | False | None | False | 65271.0 | 0 | 4044274 | 156942 | None | MS43 | 4.Lub-oil pressure safety control | No | 16318.0 | 16318.0 | 1.0 | False | None | None | False | None | False | 16318.0 | 0 | 4044275 | 156942 | None | MS44 | 5.High water temp. safety control | No | 16318.0 | 16318.0 | 1.0 | False | None | None | False | None | False | 16318.0 | 0 | 4044276 | 156942 | None | MS45 | 6.Diode | No | 12238.0 | 12238.0 | 2.0 | False | None | None | False | None | False | 24476.0 | 0 | 4044277 | 156942 | None | MS46 | Relay Panel Spares
H.SPARES FOR RELAY AND PROTECTION PANELS
1.All type of Numerical relays (each Type) | No | 4012549.0 | 4012549.0 | 1.0 | False | None | None | False | None | False | 4012549.0 | 0 | 4044278 | 156942 | None | MS47 | 2. Trip circuit supervision relay | No | 2698.51 | 2698.51 | 2.0 | False | None | None | False | None | False | 5397.02 | 0 | 4044279 | 156942 | None | MS48 | 3.Self reset trip relay (each Type) | No | 4372.0 | 4372.0 | 1.0 | False | None | None | False | None | False | 4372.0 | 0 | 4044280 | 156942 | None | MS49 | 4.Hand reset trip relay (each Type) | No | 17057.0 | 17057.0 | 1.0 | False | None | None | False | None | False | 17057.0 | 0 | 4044281 | 156942 | None | MS50 | 5.Timer relay (each Type) | No | 5000.0 | 5000.0 | 1.0 | False | None | None | False | None | False | 5000.0 | 0 | 4044282 | 156942 | None | MS51 | 6.DC supervision relays | No | 2668.0 | 2668.0 | 1.0 | False | None | None | False | None | False | 2668.0 | 0 | 4044283 | 156942 | None | MS52 | 7.Flag relays (each Type) | No | 33278.0 | 33278.0 | 1.0 | False | None | None | False | None | False | 33278.0 | 0 | 4044284 | 156942 | None | MS53 | 8.Auxiliary relays (each Type) | No | 38798.0 | 38798.0 | 1.0 | False | None | None | False | None | False | 38798.0 | 0 | 4044285 | 156942 | None | MS54 | I.COMMON SPARES:
1.Each type of module of bus bar differential relay for Bus Bar protection. | Set | 2204092.0 | 2204092.0 | 1.0 | False | None | None | False | None | False | 2204092.0 | 0 | 4044286 | 156942 | None | MS55 | 2.Metrosil(Non-linear resistor) each type | Set | 11717.0 | 11717.0 | 1.0 | False | None | None | False | None | False | 11717.0 | 0 | 4044287 | 156942 | None | MS56 | 3.Inter-posing CT & PTs each type | Set | 5000.0 | 5000.0 | 1.0 | False | None | None | False | None | False | 5000.0 | 0 | 4044288 | 156942 | None | MS57 | J.Mandatory spares for Sub-Stn Automation system
1.Bay control unit with configuration software | Set | 221014.5 | 221014.5 | 2.0 | False | None | None | False | None | False | 442029.0 | 0 | 4044289 | 156942 | None | MS58 | 2.Ethernet Switch of each type | No | 223326.0 | 223326.0 | 1.0 | False | None | None | False | None | False | 223326.0 | 0 | 4044290 | 156942 | None | MS59 | 3.Optical cable of longest length | No | 19339.0 | 19339.0 | 1.0 | False | None | None | False | None | False | 19339.0 | 0 | 4044291 | 156942 | None | MS60 | K.MANDATORY SPARES FOR POWER TRANSFORMER
a.Power transformer
1.Oil collecting bottle | No | 21129.74 | 21129.74 | 3.0 | False | None | None | False | None | False | 63389.22 | 0 | 4044292 | 156942 | None | MS61 | 2.Terminal connector clamps
a)Suitable for 245kV class bushing to suit single Drake ACSR | No | 22896.0 | 22896.0 | 3.0 | False | None | None | False | None | False | 68688.0 | 0 | 4044293 | 156942 | None | MS62 | b)Suitable for 66kV class bushing to suit Double Drake ACSR | No | 16960.0 | 16960.0 | 3.0 | False | None | None | False | None | False | 50880.0 | 0 | 4044294 | 156942 | None | MS63 | 3.Valves
a)Drain valve (100mm to 200mm size) | No | 100700.0 | 100700.0 | 1.0 | False | None | None | False | None | False | 100700.0 | 0 | 4044295 | 156942 | None | MS64 | b)Top/Bottom Filter Valve (50mm to 100mm size) | No | 79500.0 | 79500.0 | 2.0 | False | None | None | False | None | False | 159000.0 | 0 | 4044296 | 156942 | None | MS65 | c)Top/Middle/Bottom Oil sampling valve with plug (15 to 25 mm) | No | 20458.0 | 20458.0 | 3.0 | False | None | None | False | None | False | 61374.0 | 0 | 4044297 | 156942 | None | MS66 | d)Header pipe valve | No | 29680.0 | 29680.0 | 1.0 | False | None | None | False | None | False | 29680.0 | 0 | 4044298 | 156942 | None | MS67 | e) Gate/Butterfly valves of various sizes ranging from 50mm to 200mm | Set | 29680.0 | 29680.0 | 1.0 | False | None | None | False | None | False | 29680.0 | 0 | 4044299 | 156942 | None | MS68 | 4.MOG | No | 33496.0 | 33496.0 | 1.0 | False | None | None | False | None | False | 33496.0 | 0 | 4044300 | 156942 | None | MS69 | 5.Prismatic Gauge | No | 7950.0 | 7950.0 | 1.0 | False | None | None | False | None | False | 7950.0 | 0 | 4044301 | 156942 | None | MS70 | 6.Starters, contactors, relays | Set | 93810.0 | 93810.0 | 1.0 | False | None | None | False | None | False | 93810.0 | 0 | 4044302 | 156942 | None | MS71 | 7.Pressure Relief Device (PRD or PRV) | No | 27348.0 | 27348.0 | 1.0 | False | None | None | False | None | False | 27348.0 | 0 | 4044303 | 156942 | None | MS72 | 8.Oil Surge relay | No | 14098.0 | 14098.0 | 1.0 | False | None | None | False | None | False | 14098.0 | 0 | 4044304 | 156942 | None | MS73 | 9.Bucholtz relay | No | 40651.0 | 40651.0 | 1.0 | False | None | None | False | None | False | 40651.0 | 0 | 4044305 | 156942 | None | MS74 | 10.Tap position Indicator | No | 31270.0 | 31270.0 | 1.0 | False | None | None | False | None | False | 31270.0 | 0 | 4044306 | 156942 | None | MS75 | 11.Fixed and moving contacts for diverter switch | Set | 171720.0 | 171720.0 | 1.0 | False | None | None | False | None | False | 171720.0 | 0 | 4044307 | 156942 | None | MS76 | 12.Fixed and moving contacts for selector switch 220kV and above class | Set | 171720.0 | 171720.0 | 1.0 | False | None | None | False | None | False | 171720.0 | 0 | 4044308 | 156942 | None | MS77 | 13.WTI with 4 contacts, 15 meters capillary length with built in CCU RTD and external remote indicator, range 0-150 deg C with SCADA/SAS compatibility | Set | 44520.0 | 44520.0 | 1.0 | False | None | None | False | None | False | 44520.0 | 0 | 4044309 | 156942 | None | MS78 | 14.OTI with 2 contacts, 15 meters capillary length with built in CCU RTD and external remote indicator range 0-150 deg C with SCADA/SAS compatibility | Set | 29150.0 | 29150.0 | 1.0 | False | None | None | False | None | False | 29150.0 | 0 | 4044310 | 156942 | None | MS79 | 15.PT 100 sensor along with probe of suitable length | Set | 24539.0 | 24539.0 | 1.0 | False | None | None | False | None | False | 24539.0 | 0 | 4044311 | 156942 | None | MS80 | L.Testing and Maintenance for GIS/Relays
1.SF6 Gas filling and evacuating & storage plant | Set | 6814474.94 | 6814474.94 | 1.0 | False | None | None | False | None | False | 6814474.94 | 0 | 4044312 | 156942 | None | MS81 | 2.Portable Partial Discharge Monitoring for GIS(minimum 6 channels) | Set | 3187664.04 | 3187664.04 | 1.0 | False | None | None | False | None | False | 3187664.04 | 0 | 4044313 | 156942 | None | MS82 | 3.Portable SF6 gas leak Detector | No | 1466052.15 | 1466052.15 | 1.0 | False | None | None | False | None | False | 1466052.15 | 0 | 4044314 | 156942 | None | MS83 | 4.Portable SF6 gas quality analyzer- Online measurement of moisture (Dew point/PPM), purity, SO2, HF, CF4 & air content of SF6 gas. | Set | 3699418.23 | 3699418.23 | 1.0 | False | None | None | False | None | False | 3699418.23 | 0 |
| 1726893213000 | 0 | None | None | Sub-Station | Station Supply GIS | 725398556.5 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
4044315 | 156943 | None | SS1 | POWER TRANSFORMERs:
a) Power Transformer: 3 Ph. 50Hz Core type, 3 winding Star/Star/Delta, Transformer Vector Group : YNyn0d11, OLTC, bushing CT for teritiary of ratio 1515/1A, 5P20, 15VA, ONAN/ONAF/OFAF with Fan control cubicle, Numerical RTCC panel with optic fibre temperature sensor, oil etc., complete with 2x50% separate radiator bank on left side and terminal connector suitable for Single Drake ACSR on primary and Twin Drake ASCR on secondary side of transformer and Neutral connectors suitable for Copper Flats as per specifications
150MVA, 220/66/11kV Transformer | No | 120650000.0 | 120650000.0 | 2.0 | False | None | None | False | None | False | 241300000.0 | 0 | 4044316 | 156943 | None | SS2 | Metal encapsulated SF6 gas insulated Switchgear 50kA for 220kV and 40KA for 66kV rating suitable for indoor installation of modular design.
1. 220 kV line (U.G.Cable) Module:
(i)Each module comprising of the following:
Suitable for Double Bus-bar system
a)SF6 circuit breaker Complete with operating Mechanism, 2000A, 1 Phase / 3 Phase- 1No.
b)Disconnector:
bi) 3 Phase, Single Pole, Group operated isolator switch complete with manual & motor driven operating mechanism 1600A -3 Nos.
bii) 3 Phase, Single Pole, Group operated maintenance earthing switch complete with manual operating mechanism 2 Nos.
biii)3 Phase, Single pole, fast acting, fault make earthing switch complete with group operated manual & motor driven operating mechanism-1 No.
c)Current Transformer: 5 Core, Multi ratio, single phase current transformer 1600-800/ 1-1-1A plus additional 2 cores of 1600/1-1A (1 Set) 3Nos.
d)Surge Arresters :- (198kV)-(1set) 3 Nos.
e)Bus Bar-Double bus arrangement:Main Bus - 3000A.
f)Auxiliary bus - 1600A.
g)Cable end unit (Plug in type): 3Phase, Single pole, plug in type cable termination - 1 Run of 1200 sq.mm for each phase - 1 set.
h)Gas monitoring device, remote gas pressure transmitters (4-20mA signals) barrier pressure switches, UHF sensors, etc. as required.
Note :The bus and the equipments may be with single phase or 3 phase enclosure.
i)Control/Power /screened cables (FRLS type) from GIS module to LCC panel as per Technical specification- As required. | No | 21686830.0 | 21686830.0 | 3.0 | False | None | None | False | None | False | 65060490.0 | 0 | 4044317 | 156943 | None | SS3 | 2.220 kV Bus Coupler Module
(i)Each module comprising of the following:
Suitable for Double Bus-bar system
a)SF6 circuit breaker Complete with operating Mechanism, 2000A, 1 Phase / 3 Phase- 1 No.
b)Disconnector:
bi) 3 Phase, Single Pole, Group operated isolator switch complete with manual & motor driven operating mechanism 1600A - 2 Nos.
bii) 3 Phase, Single Pole, Group operated maintenance earthing switch complete with manual operating mechanism - 2 Nos.
c)Current Transformer: 3 Core, Multi ratio, single phase current transformer 1600-800 / 1-1-1A Plus additional 2 cores of 1600/1-1A (1Set)3Nos.
d)Bus Bar-Double bus arrangement:Main Bus - 3000A
e)Auxiliary bus - 1600A
f)Gas monitoring device, remote gas pressure transmitters (4-20mA signals), barrier pressure switches, UHF sensors, etc. as required.
NOTE: The bus and the equipments may be with single phase or 3 phase enclosure.
g)Control/Power /screened cables (FRLS type) from GIS module to LCC panel as per Technical specification-As required | No | 17836610.0 | 17836610.0 | 1.0 | False | None | None | False | None | False | 17836610.0 | 0 | 4044318 | 156943 | None | SS4 | 3.Transformer Module: (For 150 MVA-220 kV Side)
(i)Each module comprising of the following:
Suitable for Double Bus-bar system
a)SF6 circuit breaker Complete with operating Mechanism, 2000A, 1 Phase / 3 Phase-1 No.
b)Disconnectors:
bi) 3 Phase, Single pole, Group operated isolator switch complete with manual & motor driven operating mechanism 1600 A - 3 Nos.
bii)3 Phase, Single pole, Group operated maintenance earthing switch complete with manual operating mechanism -3Nos.
c)Current Transformers 3 Core, Multi ratio, single phase current transformer 600-300/1-1-1A plus additional 2 cores of 1600/1-1A (1Set) -3 Nos.
d)Surge Arrestor (198 kV)-(1 set)- 3 nos.
e)Bus Bar-Double bus arrangement:Main Bus - 3000A
f)Auxiliary bus - 1600A
g)GIS module, Gas monitoring device, remote gas pressure transmitters (4-20 mA signals), barriers pressure switchers, UHF sensors, etc. as required.
h)Single phase/3 phase SF6 ducts & SF6 to air bushings for out door connection along with support structures , foundation for SF6 to air bushing - As required). Note:- The bus and the equipments may be with single phase or 3 phase enclosure.
i)Control/Power /screened cables (FRLS type) from GIS module to LCC panel as per Technical specification -As required. | No | 19996460.0 | 19996460.0 | 2.0 | False | None | None | False | None | False | 39992920.0 | 0 | 4044319 | 156943 | None | SS5 | 4.Transformer Module: (For 150 MVA-66 kV Side)
(i)Each module comprising of the following:
Suitable for Double Bus-bar system
a)SF6 circuit breaker Complete with operating Mechanism, 2000A, 1 Phase / 3 Phase-1 No.
b)Disconnectors:
bi) 3 Phase, Single pole, Group operated isolator switch complete with manual & motor driven operating mechanism 1600 A - 3 Nos.
bii)3 Phase, Single pole, Group operated maintenance earthing switch complete with manual operating mechanism -3Nos.
c)Current Transformers 3 Core, Multi ratio, single phase current transformer 1600-1000/1-1-1 A (1Set) 3 Nos
d)Surge Arrestor (60 kV)-(1 set)- 3 nos.
e)Bus Bar-Double bus arrangement:Main Bus - 2500A
f)Auxiliary bus - 1600A
g)Gas monitoring device, remote gas pressure trabsmitters (4-20mA signals), barriers pressure switches, UHF sensors, etc., as required.
h)Single phase/3 phase SF6 ducts & SF6 to air bushings for out door connection along with support structures , foundation for SF6 to air bushing - As required). Note:- The bus and the equipments may be with single phase or 3 phase enclosure.
i)Control/Power /screened cables (FRLS type) from GIS module to LCC panel as per Technical specification -As required. | No | 13670580.0 | 13670580.0 | 2.0 | False | None | None | False | None | False | 27341160.0 | 0 | 4044320 | 156943 | None | SS6 | 66 kV Line (U.G.Cable) Module: with GIS surge arrester
Metal encapsulated SF6 gas insulated Switchgear 40 kA for 66 kV rating suitable for outdoor installation of modular design.
(i)Each module comprising of the following:
Suitable for Double Bus-bar system
a)SF6 circuit breaker Complete with operating Mechanism, 2000A, 1 Phase / 3 Phase-1 No.
b)Disconnectors:
bi) 3 Phase, Single pole, Group operated isolator switch complete with manual & motor driven operating mechanism 1600A -3 Nos.
bii) 3 Phase, Single Pole, Group operated maintenance earthing switch complete with manual operating mechanism -2 Nos.
biii)3phase, single pole, fast acting, fault make earthing switch complete with group operated manual & motor driven operating mechanism-1 No.
c)Current Transformer : 3 Core, Multi ratio, Single phase current transformer.1200-800/1-1-1A - 1 Set (3 Nos)
d)Surge Arresters 60kV-1Set (3Nos)
e)Cable end unit (Plug in type): 3Phase, Single pole, plug in type cable termination - 1 Run of 1000 sqmm for each phase - 1 set.
f)Bus Bar-Double bus arrangement:Main Bus - 2500A
g)Auxiliary bus -1250A.
h)Gas monitoring device, remote gas pressure trabsmitters (4-20mA signals), barriers pressure switches, UHF sensors, etc., as required.
Note:- The bus and the equipments may be with single phase or 3 phase enclosure.
i)Control/Power /screened cables (FRLS type) from GIS module to LCC panel as per Technical specification -As required. | No | 15007630.0 | 15007630.0 | 6.0 | False | None | None | False | None | False | 90045780.0 | 0 | 4044321 | 156943 | None | SS7 | 6.66kV Interconnecting module with GIS duct (Rate of 66 kV UG Cable module is considered)
Note:-(rate=module rate - rate of LCC)
Each module comprising of the following:
SF6 circuit breaker Complete with operating Mechanism, 2000A, 1 Phase/3phase -1 No.
Disconnector:
bi) 3 Phase, Single Pole, Group operated isolator switch complete with manual & motor driven operating mechanism 2000A - 3 Nos.
bii) 3 Phase, Single Pole, Group operated maintenance earthing switch complete with manual operating mechanism- 3 Nos.
Current Transformer: 3 Core, Multi ratio, single phase current transformer 1600-1000/1-1-1A- (1 Set) 3 Nos.
Surge Arresters (60kV):- To be provided at the end of SF6 ducts to be connected to SF6 to Air bushing for connecting 66 kV GIS to rigid bus of existing 66 kV AIS station. 3Nos.(1set)
Bus Bar- Double bus arrangement:Main bus- 2500 A
Auxiliary bus- 2500A
GIS module, Gas monitoring device, remote gas pressure transmitters (4-20mA signals), barriers pressure switches, UHF sensors, etc., as required.
Single/3 phase SF6 ducts & SF6 to air bushings for outdoor connections along with support structure & foundation - As required (SF6 to air bushing shall be provided in the existing 66/11 kV switchyard & SF6 duct shall be provided from GIS module up to existing switchyard bus interconnecting bay). Note:-The bus and the equipments may be with single phase or 3 phase closure.
Control Cables/power cables/Twisted pair screened cables etc., (FRLS type) from GIS module to LCC Panel as per Technical specification, as required for entire module. | No | 15007630.0 | 15007630.0 | 1.0 | False | None | None | False | None | False | 15007630.0 | 0 | 4044322 | 156943 | None | SS8 | 7.66kV Bus Coupler module
(i)Each module comprising of the following:
Suitable for Double Bus-bar system
a)SF6 circuit breaker Complete with operating Mechanism, 2000A, 1 Phase / 3 Phase-1 No.
b)Disconnectors:
bi) 3 Phase, Single pole, Group operated isolator switch complete with manual & motor driven operating mechanism 1600A -2 Nos.
bii) 3 Phase, Single Pole, Group operated maintenance earthing switch complete with manual operating mechanism -2 Nos.
c)Current Transformer : 3 Core, Multi ratio, Single phase current transformer 1600-1000/1-1-1A
d)Bus Bar-Double bus arrangement:Main Bus - 2500A
e)Auxiliary bus -1600A.
f)Gas monitoring device, remote gas pressure trabsmitters (4-20mA signals), barriers pressure switches, UHF sensors, etc., as required.
Note:- The bus and the equipments may be with single phase or 3 phase enclosure.
g)Control/Power /screened cables (FRLS type) from GIS module to LCC panel as per Technical specification -As required. | No | 6435990.0 | 6435990.0 | 1.0 | False | None | None | False | None | False | 6435990.0 | 0 | 4044323 | 156943 | None | SS9 | Local Control cubical-Total (including supply, Erection & Testing & Commissioning Charges)-220kV & 66kV Note:Refer Techno Commercial sheets for detailed break up. | No | 402930.0 | 402930.0 | 15.0 | False | None | None | False | None | False | 6043950.0 | 0 | 4044324 | 156943 | None | SS10 | GAS INSULATED BUS-DUCTS :
66 kV, 2500 A, 40 kA SF6 duct outside the GIS
building including SF6 gas monitoring system for
connecting GIS module to SF6 - Air bushing including
support structure and civil foundation
Note:
For 66kV Lines = 12 meter floor *3 Lines = 36 meter / Line;
5 Line Bays * 36 Meter = 180 Meter
For 66kV Transformer Bay = 15 meter 1st floor+ 30 Meter upto Transformer upto air bushing = 45 meter / Transformer = 2 transformer * 45 Meter = 90 Meter
For 66kV Interconnecting Bay = 15 meter 1st Floor + 45 meter upto existing Bay = 60 Meter
Total Bus duct= 180+90+60 = 330 Meter | Mtr | 163350.0 | 163350.0 | 330.0 | False | None | None | False | None | False | 53905500.0 | 0 | 4044325 | 156943 | None | SS11 | PT Module
i)220 kV (1 for each bus)
Each module comprising of the following:
Suitable for Double Bus-bar system
a)Disconnector:
ai) 3 Phase, Single pole, Group operated isolator switch complete with manual & motor driven operating mechanism, 1600 A - For 220 kV -1 No.
aii) 3 Phase, Single Pole, Group operated maintenance earthing switch complete with manual operating mechanism -1 No.
b)Potential Transformer: 3 Core, Multi ratio, single phase potential transformer.
bi)220 kV/sqrt3/110 V/sqrt3 - 110 V/sqrt3 -110/-sqrt3-1Set (3Nos).
c) Bus Bar-Double bus arrangement:
Main Bus - 3000A for 220kV.
d)Auxiliary bus 1600 A-for 220 kV
e)Gas monitoring device, remote gas pressure trabsmitters (4 20mA signals) barriers pressure switches, UHF sensors, etc., as required.
f)Control/Power /screened cables (FRLS type) from GIS module to LCC panel as per Technical specification- As required.
g)Mounting structure along with foundation, earthing etc for the above - 1 set | No | 4833950.0 | 4833950.0 | 2.0 | False | None | None | False | None | False | 9667900.0 | 0 | 4044326 | 156943 | None | SS12 | PT Module
i)66 kV (1 for each bus)
Each module comprising of the following:
Suitable for Double Bus-bar system
a)Disconnector:
ai) 3 Phase, Single pole, Group operated isolator switch complete with manual & motor driven operating mechanism 1250A -for 66kV, -1 No.
aii) 3 Phase, Single Pole, Group operated maintenance earthing switch complete with manual operating mechanism -1 No.
b)Potential Transformer: 3 Core, Multi ratio, single phase potential transformer.
bi) 66 kV/sqrt3/110 V/sqrt3 - 110 V/sqrt3 -1Set (3Nos).
c) Bus Bar-Double bus arrangement:
Main Bus - 2500 A for 66kV.
d)Auxiliary bus 1250 A-for 66 kV
e)Gas monitoring device, remote gas pressure trabsmitters (4 20mA signals) barriers pressure switches, UHF sensors, etc., as required.
f)Control/Power /screened cables (FRLS type) from GIS module to LCC panel as per Technical specification- As required.
g)Mounting structure along with foundation, earthing etc for the above -1 set | No | 3263370.0 | 3263370.0 | 2.0 | False | None | None | False | None | False | 6526740.0 | 0 | 4044327 | 156943 | None | SS13 | Bus Maintenance earth switch 3 Phase, Single pole, Group operated maintenance earthing switch complete with manual operating mechanism -1600 Amp. Along with mounting structure, foundation, earthing etc.,
i)220 kV - (1 for each bus) | No | 2070310.0 | 2070310.0 | 2.0 | False | None | None | False | None | False | 4140620.0 | 0 | 4044328 | 156943 | None | SS14 | ii)66 kV -(1 for each bus) | No | 1310430.0 | 1310430.0 | 2.0 | False | None | None | False | None | False | 2620860.0 | 0 | 4044329 | 156943 | None | SS15 | SF-6 CIRCUIT BREAKER: SF-6 Circuit Breaker with rigid bi-metallic terminal connector suitable for Drake ACSR with spring / semi-pneumatic / pneumatic type operating mechanism and with mounting structure.
220 kV, 1250A, 50kA Class | No | 1714000.0 | 1714000.0 | 1.0 | False | None | None | False | None | False | 1714000.0 | 0 | 4044330 | 156943 | None | SS16 | Current Transformer : Oil filled current transformer with rigid terminal connector suitable for copper flat
NOTE:
All the current transformers in each KV class shall be of one and the same make for interchangeability and reliability of performance.
The characteristic of 11KV NCT should be same as that of the incomer CT of 11KV Switchgear.
(i) 22 0kV 40KA CT of Ratio 600-300/1-1-1A
(Required for 150MVA Transformer NCT) | No | 366000.0 | 366000.0 | 2.0 | False | None | None | False | None | False | 732000.0 | 0 | 4044331 | 156943 | None | SS17 | ii. 220 kV, 40kA CT of Ratio 1200-800/1-1-1A with additional 2 Cores of 1200/1A Type-1
For Metering: Accuracy 0.2S, Burden 10VA
For Backup Protection: 5P20, Burden 30VA
For Differential/Distance Protection: PS Class, Knee Point Voltage - 1200V at 1200/1A Rct 12 ohms - 600V at 600/1A Rct 6 ohms.
For Bus Bar Protection: PS Class, Knee Point Voltage 1200V, Rct-12 ohms at 1200/1A
Remarks: Terminal connectors shall be suitable for Double Drake ACSR. | No | 366000.0 | 366000.0 | 3.0 | False | None | None | False | None | False | 1098000.0 | 0 | 4044332 | 156943 | None | SS18 | 66kV 40KA CT of Ratio 1600-1000/1-1-1A
(Required for 150MVA Transformer NCT -66kV side) | No | 137000.0 | 137000.0 | 2.0 | False | None | None | False | None | False | 274000.0 | 0 | 4044333 | 156943 | None | SS19 | Isolators:-including Marshalling box & terminal connectors as per technical specification including solid core cylindrical post insulators
I. 220kV, 1250A, 40kA Class Double Break Manual/Electrical Operated Isolators:
Note:-i) Rigid type terminal connector suitable for Double Drake - 24 nos ii) Flexible Type Terminal Connector suitable for 63 mm al. Pipe - 6 nos
a) Upright mounting type with manually operated Earth Switch LPH 5750 mm. | No | 566280.0 | 566280.0 | 1.0 | False | None | None | False | None | False | 566280.0 | 0 | 4044334 | 156943 | None | SS20 | b) Upright mounting type without earth Switch
i. Live Point Height 8250mm | No | 480370.0 | 480370.0 | 2.0 | False | None | None | False | None | False | 960740.0 | 0 | 4044335 | 156943 | None | SS21 | ii. Live Point Height 5750mm | No | 474320.0 | 474320.0 | 1.0 | False | None | None | False | None | False | 474320.0 | 0 | 4044336 | 156943 | None | SS22 | iii. Under hung mounting type without earth switch | No | 496100.0 | 496100.0 | 1.0 | False | None | None | False | None | False | 496100.0 | 0 | 4044337 | 156943 | None | SS23 | II. 66 kV, 2000A, 31.5 kA, class Double break motor operated Isolator Suitable for 63 mm Al tube for interconnecting bay at existing 66/11 kV Substation.
i.upright mounting type with earth switch (Live point Height 4250 mm) | No | 290400.0 | 290400.0 | 1.0 | False | None | None | False | None | False | 290400.0 | 0 | 4044338 | 156943 | None | SS24 | III. 66 kV, 1250A, 31.5 kA, class Double break motor operated Isolator -
i. upright mounting type without earth switch (Live point Height 4250 mm) For replacing existing 2 nos line side Bus Isolator, 2 nos Transformer side Bus isolator & 1 no PT isolator at the existing 66/11 kV Banashankari sub-station. | No | 246840.0 | 246840.0 | 5.0 | False | None | None | False | None | False | 1234200.0 | 0 | 4044339 | 156943 | None | SS25 | SURGE ARRESTOR :(Procelain housing)
Remarks: All the Surge Arresters are with Surge Monitors & Insulating Base
a) 198kV, 10kA, Class-III, Metal Oxide Type | No | 57000.0 | 57000.0 | 9.0 | False | None | None | False | None | False | 513000.0 | 0 | 4044340 | 156943 | None | SS26 | b) 60kV, 10kA, Class-III, Metal Oxide Type | No | 32000.0 | 32000.0 | 12.0 | False | None | None | False | None | False | 384000.0 | 0 | 4044341 | 156943 | None | SS27 | C&R Panel compatible to IEC 61850, communication protocol for Sub-station
Automation System in 220 kV Sub-station complete as per technical
specification
Note:1) The Accuracy class of metering core of CTs, CVTs, VTs and also trivector meter of control & relay panels shall be 0.2 class instead of that specified elsewhere in the respective clauses of Technical specification of bidding documents.
2)The proposed C&R panel shall match with that of existing panels with respect to dimensions, mimic etc.,.
3) The proposed C & R panel shall also be interfaced with Bus-Bar protection, Bus-Coupler & SAS provided at 220/66 kV Nagarabhavi sub-station / 66/11kV National College Sub-station
4) 2 nos of numerical line differential cum distance relays in the proposed C&R panel shall be of same make as that provided in proposed 220/66 kV Banashankari 3rd stage GIS sub-station end.
Relay & Protection Panels, SAS and LCC panel:-
1.220 kV Line -Type 2L (Annexure RPP1-Cable -SAS) | No | 1972300.0 | 1972300.0 | 4.0 | False | None | None | False | None | False | 7889200.0 | 0 | 4044342 | 156943 | None | SS28 | 2.220/66/11KV Transformer - Type 2T6 (Annexure RPP2-SAS) | No | 2190100.0 | 2190100.0 | 2.0 | False | None | None | False | None | False | 4380200.0 | 0 | 4044343 | 156943 | None | SS29 | 3.220KV Bus Coupler - Type 2BC (Annexure RPP1-SAS) | No | 1347940.0 | 1347940.0 | 1.0 | False | None | None | False | None | False | 1347940.0 | 0 | 4044344 | 156943 | None | SS30 | 4.220KV Bus Bar Protection - Type 2BBA (Annexure RPP3-SAS) | No | 3100020.0 | 3100020.0 | 1.0 | False | None | None | False | None | False | 3100020.0 | 0 | 4044345 | 156943 | None | SS31 | 5. 66 kV line -Type 6L (Annexure RPP4-SAS) | No | 1331000.0 | 1331000.0 | 6.0 | False | None | None | False | None | False | 7986000.0 | 0 | 4044346 | 156943 | None | SS32 | 6. 66KV UG cable - Type 6L (Annexure RPP4-Cable-SAS)-For existing AIS bays | No | 1525810.0 | 1525810.0 | 3.0 | False | None | None | False | None | False | 4577430.0 | 0 | 4044347 | 156943 | None | SS33 | 7. 66KV Bus Coupler - Type 6BC (Annexure RPP6-SAS) | No | 1166440.0 | 1166440.0 | 1.0 | False | None | None | False | None | False | 1166440.0 | 0 | 4044348 | 156943 | None | SS34 | 8. 66/11KV Transformer - Type 6T1 (Annexure RPP5-SAS) | No | 1983190.0 | 1983190.0 | 3.0 | False | None | None | False | None | False | 5949570.0 | 0 | 4044349 | 156943 | None | SS35 | 9.11kV Line - Type 1L (as per Annexure RPP7- SAS) (Provision for 2 feeders to be made in one panel and provision for one capacitor bank & 1feeder to be made in one panel) | No | 980100.0 | 980100.0 | 15.0 | False | None | None | False | None | False | 14701500.0 | 0 | 4044350 | 156943 | None | SS36 | Sub - station Automation system including installation:
Complete Sub-station Automation System including hardware and software for Sub-station and for operation from remote control centre along with associated equipment as per Annexure-SAS of Relay & Protection Panel and Sub-station Automation specification along with OFC and Ethernet switches, separate Auxiliary panel etc.
(As per Annexure - SAS of Relay & Protection Panels and Sub-station Automation specification)
Note:
1)The Accuracy class of metering core of CTs and also trivector meter of control & relay panels shall be 0.2s class and 0.2 for CVT & VT instead of that specified elsewhere in the respective clauses of Technical specification of bidding documents.
2)All the panels shall be of one and the same make for uniformity and interchangeability of components.
3)The Electronic Trivector meters with DLMS protocol & ABT features has to be provided both on the HV side and IV side of both 220/66kV transformers & 66/11kV Transformer. | Set | 15916340.0 | 15916340.0 | 1.0 | False | None | None | False | None | False | 15916340.0 | 0 | 4044351 | 156943 | None | SS37 | RIGID BUS WITH TAPS & CLAMPS including erection:
i. Aluminium Tube Conforming to 6340WP of IS-5082/1969 (BS1600-Sch.40) of following sizes.
Note: Quantity indicated is 5% more than the required assessed value & is rounded off to nearest multiple of 6, as it is generally supplied in length of 6Mts
i. 63mm Size
(for 66kV Side for proposed 220/66kV 3rd stage Banashankari Sub-station , for connecting isolator to vertical tap- 220kV side at proposed 220kV Nagarbavi Sub-station) | Mtr | 1452.0 | 1452.0 | 168.0 | False | None | None | False | None | False | 243936.0 | 0 | 4044352 | 156943 | None | SS38 | ii. Inverted ‘V’ taps made of 63mm Aluminium Tube (BS-1600) of 2500mm vertical height for vertical portion and cross bus on 220kV Side with rounded off end. | No | 4551.0 | 4551.0 | 6.0 | False | None | None | False | None | False | 27306.0 | 0 | 4044353 | 156943 | None | SS39 | iii. End capsuitable for 63 mm Aluminium pipe | No | 491.0 | 491.0 | 6.0 | False | None | None | False | None | False | 2946.0 | 0 | 4044354 | 156943 | None | SS40 | iv. Straight taps made of 63mm Aluminium Tube (BS-1600) of 1250mm vertical height for vertical portion and cross bus with rounded off end. | No | 3736.0 | 3736.0 | 3.0 | False | None | None | False | None | False | 11208.0 | 0 | 4044355 | 156943 | None | SS41 | v. Clamp suitable for 63mm Al tube & Drake ACSR conductor | No | 2117.0 | 2117.0 | 9.0 | False | None | None | False | None | False | 19053.0 | 0 | 4044356 | 156943 | None | SS42 | vi. Post Insulator Clamp suitable for 63mm Aluminium Pipe and post insulators solid core type
66kV Side
a. Rigid Type | No | 1753.0 | 1753.0 | 9.0 | False | None | None | False | None | False | 15777.0 | 0 | 4044357 | 156943 | None | SS43 | b.Expansion Type | No | 4948.0 | 4948.0 | 3.0 | False | None | None | False | None | False | 14844.0 | 0 | 4044358 | 156943 | None | SS44 | c.Sliding Type | No | 1481.0 | 1481.0 | 3.0 | False | None | None | False | None | False | 4443.0 | 0 | 4044359 | 156943 | None | SS45 | vii. Corona Bell Suitable for 63mm Aluminium Pipe | No | 617.0 | 617.0 | 6.0 | False | None | None | False | None | False | 3702.0 | 0 | 4044360 | 156943 | None | SS46 | viii. Isolator (existing 66/11 kV Tr-3 Bay) clamp suitable for 63 mm Al Tube (Rigid/Flexible Type) | No | 2986.0 | 2986.0 | 3.0 | False | None | None | False | None | False | 8958.0 | 0 | 4044361 | 156943 | None | SS47 | Grand Total weight of Tower parts- Mild Steel
Note:(i) Rate to be quoted on per t Basis.
(ii) Refer Techno Commercial Sheet for detail break up. | t | 130000.0 | 130000.0 | 36.7172 | False | None | None | False | None | False | 4773236.0 | 0 | 4044362 | 156943 | None | SS48 | Grand Total weight of Bolts & Nuts
Note:(i) Rate to be quoted on per t Basis.
(ii) Refer Techno Commercial Sheet for detail break up. | t | 142780.0 | 142780.0 | 1.675 | False | None | None | False | None | False | 239156.5 | 0 | 4044363 | 156943 | None | SS49 | Condutcor & its accessories
i. Drake ACSR
Note: Refer TechNosCommercial Sheet for detail break up. | Mtr | 410.0 | 410.0 | 950.0 | False | None | None | False | None | False | 389500.0 | 0 | 4044364 | 156943 | None | SS50 | ii. Spacers for Twin Drake | No | 561.0 | 561.0 | 12.0 | False | None | None | False | None | False | 6732.0 | 0 | 4044365 | 156943 | None | SS51 | INSULATORS:
Post Insulators - Cylindrical Solid Core Insulators as per IS:5350, Part-II & III as per technical specification
For 66KV Side-1 Unit/Stack
i. High Level Post Insulator | No | 5412.0 | 5412.0 | 15.0 | False | None | None | False | None | False | 81180.0 | 0 | 4044366 | 156943 | None | SS52 | Disc Insulators
A. 11kV, 120KN Disc Insulator | No | 799.0 | 799.0 | 372.0 | False | None | None | False | None | False | 297228.0 | 0 | 4044367 | 156943 | None | SS53 | B. 11kV, 90KN Disc Insulator | No | 591.0 | 591.0 | 42.0 | False | None | None | False | None | False | 24822.0 | 0 | 4044368 | 156943 | None | SS54 | Insulator Hardware & Clamps:
1.Bolted type Double Tension clamp to suit double Drake ACSR for 66kV side of 150MVA Transformer | No | 4461.0 | 4461.0 | 6.0 | False | None | None | False | None | False | 26766.0 | 0 | 4044369 | 156943 | None | SS55 | 2.Bolted type suspension clamp to suit Double Drake ACSR
(a) 66kV Side | No | 2863.0 | 2863.0 | 3.0 | False | None | None | False | None | False | 8589.0 | 0 | 4044370 | 156943 | None | SS56 | 3.C’ Type wedge connector suitable for Double Drake to double Drake on 220kV side -Line bays | No | 6169.0 | 6169.0 | 24.0 | False | None | None | False | None | False | 148056.0 | 0 | 4044371 | 156943 | None | SS57 | 4.PI Clamp suitable for Rigid Bus 63mm Aluminum tube-220kV Side | No | 1753.0 | 1753.0 | 15.0 | False | None | None | False | None | False | 26295.0 | 0 | 4044372 | 156943 | None | SS58 | 8.Spacers for Double Drake ACSR | No | 561.0 | 561.0 | 20.0 | False | None | None | False | None | False | 11220.0 | 0 | 4044373 | 156943 | None | SS59 | Auxiliary Transformers with oil, cable termination type on both HT & LT, outdoor type with off load tap changer in steps of 2.5% as per specification including LT Distribution box with copper windings:
250 kVA, 11 kV/433 V Auxillary Transformers, 3 Ph, Delta / star Dyn11. | No | 459252.0 | 459252.0 | 2.0 | False | None | None | False | None | False | 918504.0 | 0 | 4044374 | 156943 | None | SS60 | LTAC panel (indoor):
415V, LTAC panel (2 I/C ACB 800A+2 O/G SFU, 200A + 8 O/G SFU 100A+14 O/G SFU, 63A+12 O/G SFU, 32A+1B/C SFU, 800A+1DG Change over switch 300A etc. | Set | 617100.0 | 617100.0 | 1.0 | False | None | None | False | None | False | 617100.0 | 0 | 4044375 | 156943 | None | SS61 | a) Power Cable from Auxiliary Transformers to LTAC panel:
1.1 kV PVC Insulated 240 Sqmm Al.cable 3.5 core with glands /lugs/Ferrules | Mtr | 862.67 | 862.67 | 100.0 | False | None | None | False | None | False | 86267.0 | 0 | 4044376 | 156943 | None | SS62 | b) PVC insulated aluminium power cable (AC supply for lighting etc):
70 Sqmm 3.5 core, with glands / lugs/ferrules | Mtr | 317.91 | 317.91 | 1000.0 | False | None | None | False | None | False | 317910.0 | 0 | 4044377 | 156943 | None | SS63 | AC Distribution Box (outdoor):
AC Distribution Box single front type, 6 terminals, 750x1350x300mm , 1 I/c of 100A, MCCB 20kA+6 O/G MCB 16A+ 1 O/G of 100A, HRC fuse | No | 43560.0 | 43560.0 | 2.0 | False | None | None | False | None | False | 87120.0 | 0 | 4044378 | 156943 | None | SS64 | DG set, 3 Phase , 50Hz, 415V, 0.8 PF, 58.5 KVA
including erection
50 kW/58.5 kVA Diesel Generator set rated at
50 kW/58.5 kVA, 415 V, 0.8 pf mounted on a base
frame, complete with inbuilt fuel tank and battery
1 no. 12 V & inbuilt standard manual Control Panel
with acoustic enclosure : NAL Approved D.G. Set
58.5 kVA capacity with AMF panel as per technical
specification | Set | 1090595.0 | 1090595.0 | 1.0 | False | None | None | False | None | False | 1090595.0 | 0 | 4044379 | 156943 | None | SS65 | Station Battery
2x220V, 600AH Battery Set consisting of 110 No. Cells per bank with float (2 Nos.) & boost cum float (2 Nos.) type battery charger including control panels, change over arrangements etc., complete along with 2 separate DC Distribution Panels (Indoor) each considering of 1I/C+20 O/G SFU 60A + 20 O/G SFU 30A.
Note: The rating of the Battery & Battery charger is indicative only. However, the successful bidder has to provide adequate rating of battery & battery charger along with battery sizing calculation | Set | 9404000.0 | 9404000.0 | 1.0 | False | None | None | False | None | False | 9404000.0 | 0 | 4044380 | 156943 | None | SS66 | Battery Charger suitable for 2x220V, 600AH Battery Set consisting of 110 No. Cells per bank with float (2 Nos.) & boost cum float (2 Nos.) type battery charger including control panels, change over arrangements etc., complete along with 2 separate DC Distribution Panels (Indoor) each considering of 1I/C+20 O/G SFU 60A + 20 O/G SFU 30A.
Note: The rating of the Battery & Battery charger is indicative only. However, the successful bidder has to provide adequate rating of battery & battery charger along with battery sizing calculation | Set | 1851000.0 | 1851000.0 | 1.0 | False | None | None | False | None | False | 1851000.0 | 0 | 4044381 | 156943 | None | SS67 | Copper Control cable:
PVC Insulated Copper Control Cable with lugs / ferrules (Refer annexure for details at the end of this schedule of quantities)
1) 2.5 Sq.mm 19 Core | Km | 560000.0 | 560000.0 | 10.5 | False | None | None | False | None | False | 5880000.0 | 0 | 4044382 | 156943 | None | SS68 | 2) 2.5 Sq.mm 10 Core | Km | 332000.0 | 332000.0 | 8.0 | False | None | None | False | None | False | 2656000.0 | 0 | 4044383 | 156943 | None | SS69 | 3) 2.5 Sq.mm 4 Core | Km | 151000.0 | 151000.0 | 6.8 | False | None | None | False | None | False | 1026800.0 | 0 | 4044384 | 156943 | None | SS70 | 4) 6 Sq.mm 4 Core | Km | 247000.0 | 247000.0 | 15.0 | False | None | None | False | None | False | 3705000.0 | 0 | 4044385 | 156943 | None | SS71 | 5) 16 Sq.mm 4 Core
( 100mtrs for Yard lighting) | Km | 560000.0 | 560000.0 | 1.1 | False | None | None | False | None | False | 616000.0 | 0 | 4044386 | 156943 | None | SS72 | 6) 4 Sq.mm 4 Core | Km | 177000.0 | 177000.0 | 3.3 | False | None | None | False | None | False | 584100.0 | 0 | 4044387 | 156943 | None | SS73 | 7) 70 sq.mm 2 Core | Km | 1915000.0 | 1915000.0 | 0.2 | False | None | None | False | None | False | 383000.0 | 0 | 4044388 | 156943 | None | SS74 | 8) 2PX0.5 sq mm Screened cable | Km | 56000.0 | 56000.0 | 2.5 | False | None | None | False | None | False | 140000.0 | 0 | 4044389 | 156943 | None | SS75 | 9) 4PX0.5 sq mm Screened cable | Km | 77000.0 | 77000.0 | 2.0 | False | None | None | False | None | False | 154000.0 | 0 | 4044390 | 156943 | None | SS76 | 10) 8PX0.5 sq mm Screened cable | Km | 132000.0 | 132000.0 | 2.0 | False | None | None | False | None | False | 264000.0 | 0 | 4044391 | 156943 | None | SS78 | 11kV UG Cable with the required cable terminations:
[a] 11kV XLPE 95 Sq.mm Aluminium Cable-3 Core ( for auxiliary transformers from the 11kV Switchgear of 66/11KV Sub-station) | Mtr | 889.67 | 889.67 | 400.0 | False | None | None | False | None | False | 355868.0 | 0 | 4044392 | 156943 | None | SS79 | b) 11kV Cable Termination Kit suitable for 95 Sq.mm 3 Core as per Technical Specification. | Set | 3744.0 | 3744.0 | 4.0 | False | None | None | False | None | False | 14976.0 | 0 | 4044393 | 156943 | None | SS80 | 220 kV XLPE Cable & termination:
i. 220kV, 1000Sq.mm single core XLPE insulated, copper conductor, lead sheathed cable required for connecting GIS module to 220/66KV Transformer as per specification. | Mtr | 24613.0 | 24613.0 | 200.0 | False | None | None | False | None | False | 4922600.0 | 0 | 4044394 | 156943 | None | SS81 | ii. 220kV Pre moulded outdoor cable termination kit for 1000Sq.mm XLPE UG Cable (as per specification). | No | 1102310.0 | 1102310.0 | 6.0 | False | None | None | False | None | False | 6613860.0 | 0 | 4044395 | 156943 | None | SS82 | iii.Indoor type suitable for plug in type cable termination of GIS modules confirm to IEC 62271-209 for 220KV 1000Sq.mm XLPE cable to 220/66kV Transformer | No | 730840.0 | 730840.0 | 6.0 | False | None | None | False | None | False | 4385040.0 | 0 | 4044396 | 156943 | None | SS83 | iv.Three phase Link box along with sheath earthing cables etc as per specification. | No | 105270.0 | 105270.0 | 2.0 | False | None | None | False | None | False | 210540.0 | 0 | 4044397 | 156943 | None | SS84 | v.Single phase Link box along with sheath earthing cables etc as per specification. | No | 105270.0 | 105270.0 | 6.0 | False | None | None | False | None | False | 631620.0 | 0 | 4044398 | 156943 | None | SS85 | Fire Fighting Equipments with necessary mounting Stands:
a) Mechanical Foam Extinguisher Type:
i.50 Liters | No | 10112.0 | 10112.0 | 8.0 | False | None | None | False | None | False | 80896.0 | 0 | 4044399 | 156943 | None | SS86 | ii.9.0 Liters | No | 4118.0 | 4118.0 | 8.0 | False | None | None | False | None | False | 32944.0 | 0 | 4044400 | 156943 | None | SS87 | b) Water Type (Gas Pressure Type)- 9.0 Liters | No | 2503.0 | 2503.0 | 10.0 | False | None | None | False | None | False | 25030.0 | 0 | 4044401 | 156943 | None | SS88 | c) Carbon Dioxide Type 4.5 Kgs | No | 8691.0 | 8691.0 | 10.0 | False | None | None | False | None | False | 86910.0 | 0 | 4044402 | 156943 | None | SS89 | Dry Chemical powder type - 4.5kgs | No | 5111.0 | 5111.0 | 5.0 | False | None | None | False | None | False | 25555.0 | 0 | 4044403 | 156943 | None | SS90 | d) Sand Type
i. G.I. Bucket 9 Liters | No | 603.0 | 603.0 | 16.0 | False | None | None | False | None | False | 9648.0 | 0 | 4044404 | 156943 | None | SS91 | ii. Steel Stands | No | 2362.0 | 2362.0 | 4.0 | False | None | None | False | None | False | 9448.0 | 0 | 4044405 | 156943 | None | SS92 | e) Nitrogen Injection fire extinguishing system including Supply, Erection, Testing& Commissioning and Civil Engineering works like soak pit etc., as per the recommendations of the supplier of the fire fighting system. | Set | 1511895.0 | 1511895.0 | 2.0 | False | None | None | False | None | False | 3023790.0 | 0 | 4044406 | 156943 | None | SS93 | f) Addressable type Fire alarm system using smoke detectors, heat detectors etc as per specification for GIS hall & control room. | Set | 1125339.0 | 1125339.0 | 1.0 | False | None | None | False | None | False | 1125339.0 | 0 | 4044407 | 156943 | None | SS94 | Maintenance Tools and Plant:
a)Earth Resistance Tester | No | 28123.0 | 28123.0 | 1.0 | False | None | None | False | None | False | 28123.0 | 0 | 4044408 | 156943 | None | SS95 | b) Welding machine (arc welding) 10kVA | No | 27891.0 | 27891.0 | 1.0 | False | None | None | False | None | False | 27891.0 | 0 | 4044409 | 156943 | None | SS96 | c) Heavy duty drilling machine | No | 42744.0 | 42744.0 | 1.0 | False | None | None | False | None | False | 42744.0 | 0 | 4044410 | 156943 | None | SS97 | d) Hickery rods | No | 5399.0 | 5399.0 | 4.0 | False | None | None | False | None | False | 21596.0 | 0 | 4044411 | 156943 | None | SS98 | e) Grounding sticks extendable upto 18 ft : 3 nos. of
each 6 ft Sticks of 3 phase R, Y, B (3 nos. of 1 set) | No | 1755.0 | 1755.0 | 4.0 | False | None | None | False | None | False | 7020.0 | 0 | 4044412 | 156943 | None | SS99 | f) Manila Rope 1 inch | Mtr | 66.7 | 66.7 | 100.0 | False | None | None | False | None | False | 6670.0 | 0 | 4044413 | 156943 | None | SS100 | g) Manila Rope 3/4 inch | Mtr | 39.33 | 39.33 | 100.0 | False | None | None | False | None | False | 3933.0 | 0 | 4044414 | 156943 | None | SS101 | h) Files of Various Sizes | No | 8661.0 | 8661.0 | 6.0 | False | None | None | False | None | False | 51966.0 | 0 | 4044415 | 156943 | None | SS102 | i) Portable Drilling Machine with Stand heavy duty | No | 42744.0 | 42744.0 | 1.0 | False | None | None | False | None | False | 42744.0 | 0 | 4044416 | 156943 | None | SS103 | j) Hand Drilling Machine | No | 21373.0 | 21373.0 | 1.0 | False | None | None | False | None | False | 21373.0 | 0 | 4044417 | 156943 | None | SS104 | k) Safety Belts | No | 1012.0 | 1012.0 | 2.0 | False | None | None | False | None | False | 2024.0 | 0 | 4044418 | 156943 | None | SS105 | l) Safety Helmets | No | 276.0 | 276.0 | 2.0 | False | None | None | False | None | False | 552.0 | 0 | 4044419 | 156943 | None | SS106 | m) Steel Measuring tape 30Mtrs | No | 759.0 | 759.0 | 1.0 | False | None | None | False | None | False | 759.0 | 0 | 4044420 | 156943 | None | SS107 | n) Steel Measuring tape 15Mtrs | No | 557.0 | 557.0 | 1.0 | False | None | None | False | None | False | 557.0 | 0 | 4044421 | 156943 | None | SS108 | Insulation Tester Digital Type (Megger)
2.5 kV - 5 kV | No | 55308.0 | 55308.0 | 1.0 | False | None | None | False | None | False | 55308.0 | 0 | 4044422 | 156943 | None | SS109 | MISCELLANOUS ITEMS(as per DPR Rates)
1.Rubber mats 1000 mm x 1000 mm x 10 mm size | No | 1900.0 | 1900.0 | 17.0 | False | None | None | False | None | False | 32300.0 | 0 | 4044423 | 156943 | None | SS110 | 2.First aid box. | No | 600.0 | 600.0 | 1.0 | False | None | None | False | None | False | 600.0 | 0 | 4044424 | 156943 | None | SS111 | 3.Shock treatment charts, hard board, liminated with coloured pictures & literature both in Kannada & English | No | 2000.0 | 2000.0 | 1.0 | False | None | None | False | None | False | 2000.0 | 0 | 4044425 | 156943 | None | SS112 | 4.Water filter / Water purifier : Wall mounting type (Aqua-guard type).(rate obtained from GEM portal) | No | 10000.0 | 10000.0 | 1.0 | False | None | None | False | None | False | 10000.0 | 0 | 4044426 | 156943 | None | SS113 | 5.Sub-station name board duly painted. | No | 9000.0 | 9000.0 | 1.0 | False | None | None | False | None | False | 9000.0 | 0 | 4044427 | 156943 | None | SS114 | 6. Fixograph of size 1.5m x 2.5m with English / Kannada alphabets.(Previous approved DPR rate) | Set | 5000.0 | 5000.0 | 1.0 | False | None | None | False | None | False | 5000.0 | 0 | 4044428 | 156943 | None | SS115 | 7.Lock 7 levers (best make of approved quality) 75 mm size | No | 500.0 | 500.0 | 5.0 | False | None | None | False | None | False | 2500.0 | 0 | 4044429 | 156943 | None | SS116 | 8.Danger board(prohibited) with support structure including fixing in front of the gate(Previous approved DPR rate) | No | 2000.0 | 2000.0 | 1.0 | False | None | None | False | None | False | 2000.0 | 0 | 4044430 | 156943 | None | SS117 | 9.Equipment name plates and earthing name plates including fixing at outdoor yard | No | 398.0 | 398.0 | 36.0 | False | None | None | False | None | False | 14328.0 | 0 | 4044431 | 156943 | None | SS118 | Smart Surveillance system (CCTV): using PTZ & fixed cameras, OFC monitoring system, HMI, etc as per bid specification.
Note:
1. Exact Location of the cameras to be given at the time of commissioning.
2. P/S unit to be housed with outdooe box with IP 66 compliance and provision of ELCB to be provided by thr integrator.
3. 6F Armoured Multimode OFC to be used for interconnectivities between cameras & HMI.
4. One no.of addittional work station and network switch (at 220kV Khodays) as per specification.
5. The requirement of materials will be furnished by SEE, SCADA, Bangalore
i. PTZ Camera:
Speifications:
Lens type-Auto Focus with optical Zoom of 30x, Digital Zoom+10x.
Pan Angle:360 degree endless .
Tilt angle:210 degrees with e-flip/higher. Zoom:30X Optical and 12X Digital
Mode:Day & Night. Image size:-Full HD.
streaming:High speed
Weather Proof:IP 66 complaint.
Network Protocol:TCP/IP should be compliant of any other protocol required.
Connectivity:Cat 6/Optical fibre. Ethernet:10 Base-T/100 Base-TX (RJ45)
Power source:Both self powered & externally powered. | No | 67352.0 | 67352.0 | 4.0 | False | None | None | False | None | False | 269408.0 | 0 | 4044432 | 156943 | None | SS119 | ii. Fixed Camera:
Speifications:
Lens type:-Bi-focal auto iris with 10x digital zoom.
Mode:Day/Night
Image size:720x486 (NTSC).
Streaming:High Speed.
Weather proof:IP 66 complaint Network Protocol:TCP/IP should be complaint of any other protocol required.
Connectivity:Cat 6/optical fibre
Ethernet:10Base-t/100Base-TX(RJ45) Power source:both Self powered/externally powered.
Vol:06, Pg No: 52, Sl.no:34.2 & Pg.no:128, Sl.No: e ii | No | 11987.0 | 11987.0 | 11.0 | False | None | None | False | None | False | 131857.0 | 0 | 4044433 | 156943 | None | SS120 | iii. HMI (Industrial Grade PC)
a. Operating System : Windows 10 Professional
b. CPU : Intel i7 quad core processor or latest
c. RAM : 32 GB or higher
d. Network : TCP/IP
e. Graphics adaptor : NVIDA Quadra digital video pipeline or higher
f. Hard disk : 1.5 TB (500x3) RAID 1 configuration
g. External drives : Blu-Ray RW and DVD RW
h. Monitor : 24 inch dual screen
i. Keyboard / Mouse : Wireless
j. Network adaptor
k. LAN switch
l. Fibre LIU | No | 2835994.0 | 2835994.0 | 1.0 | False | None | None | False | None | False | 2835994.0 | 0 | 4044434 | 156943 | None | SS121 | iv. OFC: 6F Armoured Multimode with LIU along with required number of SC/ST connectors and accessories | Set | 57756.0 | 57756.0 | 1.0 | False | None | None | False | None | False | 57756.0 | 0 | 4044435 | 156943 | None | SS122 | Station and Yard Lighting/Lightning protection (Outdoor): Remark: 1 No. of Lighting Mast (LM0 are proposed for lighting protection and illumination of the station Yard. The quantity of lighting /lighting mast indicated are located such that the entire station yard with equipments is protected against lightning. However any, additional lightning mast may be provided for sufficient illumination and lightning protection (DSLP) of yard, if necessary. The design of lighting outdoor & indoor is also in the scope of the bidder as specified elsewhere in the technical specification. The scope also includes supply & erection of lighting fixtures, lighting mast panels with timer, contactor, control cable etc., suitable 2.5M lightning spikes shall be provided on top of GIS for building for lightning protection i. Supply of LED flood light luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of antiglare clear diff user with Injection moulded polycarbonate/clear glass material, delivering superior light output Rated life Burning Hrs 50000hr @ Lumen Maintenance of 70%,CCT greater than 5500K, IP66 optical and electrical compartment & impact resistance of complete luminaire greater than IK08. Power Factor greater than 0.9withmains, Surge Protection-Min5KV along with Overvoltage/Overload, short circuit/miss-wiring protection. Compatible for pole mauling without of 40mm to 50mm.Universal Voltage divert operate wide voltage range from 100V to 270V 50/60 Hz application. Compliance to IS10322 / IEC60598, LM79 & LM80 Adherence with RoHS. UL approved MCPCB. To access street light with singles crew to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with.......W System Power consumption. LED Efficiency greater than 1301m/w, nominal CRI greater than 75. Luminaire manufacturer should have in-house facility accredited by NABL/CPRI & any Government certified agency & Design & Development facility certified by ISO9001:2008. Housing with supplier wordmark/name shall be Engraved /Embossing on the die cast housing /Body part Warranty of 2Years against any manufacturing defect working under standard electrical condition as mentionedaboveshouldbegivenbyLEDmanufacturer&Cree/Nichia/Lumileds/Osrammake LED Source.. LED Floodlight 240W( 6 Light / mast= 6 No) Note: The Design of lighting outdoor and indoor in station yard and GIS Building etc., is in the scope of bidder as specified in the technical specification. | No | 22068.0 | 22068.0 | 6.0 | False | None | None | False | None | False | 132408.0 | 0 | 4044436 | 156943 | None | SS123 | ii 2C x 2.5Sqmm Copper Cable from Light fitting to lighting panel mounted at Bottom of mast for each fitting required 30mtr cable( One additional run/mast provision made for future use)
[30 Mtr *1 Mast *7 run = 210 Mtrs ] | Mtr | 94.0 | 94.0 | 210.0 | False | None | None | False | None | False | 19740.0 | 0 | 4044437 | 156943 | None | SS124 | iv. Supply and Installation /Fixing/Provision of Outdoor type Thermo plastic Modular Panel enclosure with transparent Poly carbonate Lid, shock proof, IP65(WeatherProof), rustproof,dustproof,waterproof,corrosion proof having internally Embedded gasket on both lid and flap suitable to fix Single Phase/Three Phase Energy Meter in suitable base plate and having a provision for Fuse/ MCBcut-out with suitable transparent hinged flap opening for operating MCB along with complete tamper proof SEALING facility with timer.
600 mm x 600 mm x 170 mm | No | 14520.0 | 14520.0 | 1.0 | False | None | None | False | None | False | 14520.0 | 0 | 4044438 | 156943 | None | SS125 | Communication Equipments:
1.SDH Equipment
(STM-16 MADM UPTO 3 MSP PROTECTED DIRECTIONS)-BASE EQUIPMENT (COMMON CARDS, CROSS CONNECT/CONTROL CARDS, OPTICAL BASECARDS, POWER SUPPLY CARDS, POWER CABLING, OTHER HARDWARE ANDACCESSORIES INCLUDING SUB RACKS, PATCH CORD, DDF ETC FULLY EQUIPEDEXCLUDING OPTICAL INTERFACE & TRIBUTARY CARDS | No | 494709.0 | 494709.0 | 1.0 | False | None | None | False | None | False | 494709.0 | 0 | 4044439 | 156943 | None | SS126 | 2. Optical Interface
Transceiver Type (To be considered based on the line length)*
a.S16.1 SFP | No | 1572.0 | 1572.0 | 2.0 | False | None | None | False | None | False | 3144.0 | 0 | 4044440 | 156943 | None | SS127 | 3.Tributary Interface
E1 Interface card (Min. 16 interfaces per card) - 3 MSP | No | 46717.0 | 46717.0 | 2.0 | False | None | None | False | None | False | 93434.0 | 0 | 4044441 | 156943 | None | SS128 | 4.1x1000 base SFP | No | 987.0 | 987.0 | 1.0 | False | None | None | False | None | False | 987.0 | 0 | 4044442 | 156943 | None | SS129 | 5.ETHERNET INTERFACE 10/100 BASE T WITH LAYER-2 SWITCHING
(MIN 8INTERFACES PER CARD) | No | 53579.0 | 53579.0 | 2.0 | False | None | None | False | None | False | 107158.0 | 0 | 4044443 | 156943 | None | SS130 | 6.Cabinet Equipment to house SDH Equipment + Optical cards + Tributary Cards, Drop/Insert MUX Equipments and DACS Equipment | Set | 34940.0 | 34940.0 | 1.0 | False | None | None | False | None | False | 34940.0 | 0 | 4044444 | 156943 | None | SS131 | 7.Digital protection coupler with 8 command version (Direct fiber intype) | No | 289190.0 | 289190.0 | 2.0 | False | None | None | False | None | False | 578380.0 | 0 | 4044445 | 156943 | None | SS132 | 8.48V Battery Charger suitable for 200AH Battery set | No | 278300.0 | 278300.0 | 1.0 | False | None | None | False | None | False | 278300.0 | 0 | 4044446 | 156943 | None | SS133 | 9.48V, 200AH Battery Set | No | 337590.0 | 337590.0 | 1.0 | False | None | None | False | None | False | 337590.0 | 0 | 4044447 | 156943 | None | SS134 | Furniture for Control Room Staff and maintenance staff Steel
Note; The above rates are obtained from GEM portal
1.Almirahs 6 1/2 feet | No | 8000.0 | 8000.0 | 2.0 | False | None | None | False | None | False | 16000.0 | 0 | 4044448 | 156943 | None | SS135 | 2.Steel Almirahs 6 1/2 feet with glass panel doors | No | 8000.0 | 8000.0 | 1.0 | False | None | None | False | None | False | 8000.0 | 0 | 4044449 | 156943 | None | SS136 | 3.Officers tables | No | 6400.0 | 6400.0 | 4.0 | False | None | None | False | None | False | 25600.0 | 0 | 4044450 | 156943 | None | SS137 | 4.Steel Slotted angle rack (big Size) | No | 2200.0 | 2200.0 | 4.0 | False | None | None | False | None | False | 8800.0 | 0 | 4044451 | 156943 | None | SS138 | 5.Steel Slotted angle rack (small Size) | No | 1400.0 | 1400.0 | 4.0 | False | None | None | False | None | False | 5600.0 | 0 | 4044452 | 156943 | None | SS139 | 6.Steel dustbins | No | 400.0 | 400.0 | 4.0 | False | None | None | False | None | False | 1600.0 | 0 | 4044453 | 156943 | None | SS140 | 7.Executive revolving chairs | No | 7000.0 | 7000.0 | 8.0 | False | None | None | False | None | False | 56000.0 | 0 | 4044454 | 156943 | None | SS141 | 8.S’ Type Arm Chairs | No | 1800.0 | 1800.0 | 10.0 | False | None | None | False | None | False | 18000.0 | 0 | 4044455 | 156943 | None | SS142 | 9.Steel folding Chairs | No | 1100.0 | 1100.0 | 4.0 | False | None | None | False | None | False | 4400.0 | 0 | 4044456 | 156943 | None | SS143 | Motor operating mechanism suitable for existing 66 kV Isolators Note:- The rate is considered by subtracting the rate of 66 kV, 1250 A/800 A, 31.5 kA double break Electrically cum Manually operated isolators of Upright without Earth Switch of Live Point Height 5500 mm and the rate of 66 kV, 1250 A/800 A, 31.5 kA double break Manually operated isolators of Upright without Earth Switch of Live Point Height 5500 mm. | No | 25000.0 | 25000.0 | 3.0 | False | None | None | False | None | False | 75000.0 | 0 |
| 1726893213000 | 0 | None | None | Sub-Station | Civil | 235184557.83 | id | tenderSubEstimateId | categoryName | itemCode | description | uomName | baseRate | finalRate | quantity | modifyQuantityYn | minQuantity | maxQuantity | buyBackYn | buyBackValue | hideYn | netAmount | taxCount |
---|
4044457 | 156944 | None | CVL1 | Earth work in surface excavation by mechanical means for lowering & leveling the ground for all works other than foundation in all kinds of soils & upto depth not exceeding 300mm as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenances required to complete the work.
In all kinds of soils upto 300 mm depth | Cum | 95.0 | 95.0 | 2268.0 | False | None | None | False | None | False | 215460.0 | 0 | 4044458 | 156944 | None | CVL2 | Construction of Embankment with approved materials deposited at site from roadway cutting and excavation from drain and foundation of other structures graded with desired compaction. | Cum | 119.0 | 119.0 | 693.0 | False | None | None | False | None | False | 82467.0 | 0 | 4044459 | 156944 | None | CVL3 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work
In all kinds of soils Depth upto 3 m | Cum | 102.0 | 102.0 | 6631.11 | False | None | None | False | None | False | 676373.22 | 0 | 4044460 | 156944 | None | CVL4 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work
In all kinds of soils Depth 3m to 6m | Cum | 117.0 | 117.0 | 536.84 | False | None | None | False | None | False | 62810.28 | 0 | 4044461 | 156944 | None | CVL5 | Earth work excavation by manual means for drains, canals, waste weir, draft, approach channels, key trenches, foundation of Buildings & bridges and such simillar works in all kinds of soils, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, removal of stumps and other deleterious matter, excavated surface leveled and sides neatly dressed disposing off the excavated stuff or sorting & stacking the selected stuff for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools & other appurtenaces required to complete the work.
In all kinds of soils Depth upto 1.5 m | Cum | 242.0 | 242.0 | 405.27 | False | None | None | False | None | False | 98075.34 | 0 | 4044462 | 156944 | None | CVL6 | Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications.
Mix 1:4:8 Using 40 mm nominal size graded crushed coarse aggregates | Cum | 5664.0 | 5664.0 | 313.45 | False | None | None | False | None | False | 1775380.8 | 0 | 4044463 | 156944 | None | CVL7 | Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to complete the work as per technical specifications
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates. | Cum | 6475.61 | 6475.61 | 1176.74 | False | None | None | False | None | False | 7620109.3114 | 0 | 4044464 | 156944 | None | CVL8 | Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to complete the work as per technical specifications
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns below GL | Cum | 10687.9 | 10687.9 | 29.06 | False | None | None | False | None | False | 310590.374 | 0 | 4044465 | 156944 | None | CVL9 | Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for plinth beam | Cum | 9484.5 | 9484.5 | 32.03 | False | None | None | False | None | False | 303788.535 | 0 | 4044466 | 156944 | None | CVL10 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for lintel beam at Ground floor | Cum | 10608.0 | 10608.0 | 7.94 | False | None | None | False | None | False | 84227.52 | 0 | 4044467 | 156944 | None | CVL11 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for lintel beam at AHU floor level | Cum | 10714.08 | 10714.08 | 2.14 | False | None | None | False | None | False | 22928.1312 | 0 | 4044468 | 156944 | None | CVL12 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for lintel beam at first floor level | Cum | 10820.16 | 10820.16 | 12.28 | False | None | None | False | None | False | 132871.5648 | 0 | 4044469 | 156944 | None | CVL13 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for lintel beam at Mezzanine floor level | Cum | 11032.32 | 11032.32 | 4.69 | False | None | None | False | None | False | 51741.5808 | 0 | 4044470 | 156944 | None | CVL14 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for lintel beam at second floor level | Cum | 11138.4 | 11138.4 | 12.28 | False | None | None | False | None | False | 136779.552 | 0 | 4044471 | 156944 | None | CVL15 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof beam at ground floor | Cum | 10608.0 | 10608.0 | 101.82 | False | None | None | False | None | False | 1080106.56 | 0 | 4044472 | 156944 | None | CVL16 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof beam at AHU floor | Cum | 10820.16 | 10820.16 | 10.7 | False | None | None | False | None | False | 115775.712 | 0 | 4044473 | 156944 | None | CVL17 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof beam at first floor | Cum | 11997.65 | 11997.65 | 90.65 | False | None | None | False | None | False | 1087586.9725 | 0 | 4044474 | 156944 | None | CVL18 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof beam at Mezzanine floor | Cum | 11244.48 | 11244.48 | 32.64 | False | None | None | False | None | False | 367019.8272 | 0 | 4044475 | 156944 | None | CVL19 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof beam at second floor | Cum | 12315.89 | 12315.89 | 60.78 | False | None | None | False | None | False | 748559.7942 | 0 | 4044476 | 156944 | None | CVL20 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for corbel beam first floor | Cum | 10926.24 | 10926.24 | 14.8799 | False | None | None | False | None | False | 162581.358576 | 0 | 4044477 | 156944 | None | CVL21 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for corbel beam at second floor | Cum | 11350.56 | 11350.56 | 14.8799 | False | None | None | False | None | False | 168895.197744 | 0 | 4044478 | 156944 | None | CVL22 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof slab at ground floor | Cum | 9945.0 | 9945.0 | 121.22 | False | None | None | False | None | False | 1205532.9 | 0 | 4044479 | 156944 | None | CVL23 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof slab at AHU floor | Cum | 10143.9 | 10143.9 | 12.6 | False | None | None | False | None | False | 127813.14 | 0 | 4044480 | 156944 | None | CVL24 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof slab at first floor | Cum | 11308.13 | 11308.13 | 98.52 | False | None | None | False | None | False | 1114076.9676 | 0 | 4044481 | 156944 | None | CVL25 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof slab at mezzanine floor | Cum | 10541.7 | 10541.7 | 33.6 | False | None | None | False | None | False | 354201.12 | 0 | 4044482 | 156944 | None | CVL26 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for roof slab at second floor | Cum | 11599.85 | 11599.85 | 110.9 | False | None | None | False | None | False | 1286423.365 | 0 | 4044483 | 156944 | None | CVL27 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns in super structure at ground floor | Cum | 11271.0 | 11271.0 | 49.13 | False | None | None | False | None | False | 553744.23 | 0 | 4044484 | 156944 | None | CVL28 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns in super structure, at 3.6m to 6.6m level. | Cum | 11383.71 | 11383.71 | 27.54 | False | None | None | False | None | False | 313507.3734 | 0 | 4044485 | 156944 | None | CVL29 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns in super structure, at 6.6m to 9.6m level. | Cum | 11496.42 | 11496.42 | 27.54 | False | None | None | False | None | False | 316611.4068 | 0 | 4044486 | 156944 | None | CVL30 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns in super structure at 9.6m to 12.6m level. | Cum | 11609.13 | 11609.13 | 27.54 | False | None | None | False | None | False | 319715.4402 | 0 | 4044487 | 156944 | None | CVL31 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns in super structure at 12.6m to 15.6m level. | Cum | 11721.84 | 11721.84 | 27.54 | False | None | None | False | None | False | 322819.4736 | 0 | 4044488 | 156944 | None | CVL32 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns in super structure at 15.6m to 18.6m level. | Cum | 11834.55 | 11834.55 | 27.54 | False | None | None | False | None | False | 325923.507 | 0 | 4044489 | 156944 | None | CVL33 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns in super structure at 18.6m to 21.6m level | Cum | 11947.26 | 11947.26 | 27.54 | False | None | None | False | None | False | 329027.5404 | 0 | 4044490 | 156944 | None | CVL34 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns in super structure at 21.6m to 24.6m level | Cum | 12059.97 | 12059.97 | 27.54 | False | None | None | False | None | False | 332131.5738 | 0 | 4044491 | 156944 | None | CVL35 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for columns in super structure at 24.6m to 27.6m level | Cum | 12172.68 | 12172.68 | 27.54 | False | None | None | False | None | False | 335235.6072 | 0 | 4044492 | 156944 | None | CVL36 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for chejja and canopy. | Cum | 9613.5 | 9613.5 | 13.46 | False | None | None | False | None | False | 129397.71 | 0 | 4044493 | 156944 | None | CVL37 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates.for stair case. | Cum | 9945.0 | 9945.0 | 36.46 | False | None | None | False | None | False | 362594.7 | 0 | 4044494 | 156944 | None | CVL38 | Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for floor concrete. | Cum | 6323.0 | 6323.0 | 57.75 | False | None | None | False | None | False | 365153.25 | 0 | 4044495 | 156944 | None | CVL39 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for lift wall | Cum | 7293.0 | 7293.0 | 63.7 | False | None | None | False | None | False | 464564.1 | 0 | 4044496 | 156944 | None | CVL40 | Providing and laying in position Cement Concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite / trap /basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - For foundation of drains. | Cum | 8487.45 | 8487.45 | 47.19 | False | None | None | False | None | False | 400522.7655 | 0 | 4044497 | 156944 | None | CVL41 | Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - for Retaining wall | Cum | 6955.3 | 6955.3 | 399.95 | False | None | None | False | None | False | 2781772.235 | 0 | 4044498 | 156944 | None | CVL42 | Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications.
Mix 1:3:6 (M10) Using 20 mm and down size graded crushed coarse aggregates. | Cum | 6403.51 | 6403.51 | 97.2 | False | None | None | False | None | False | 622421.172 | 0 | 4044499 | 156944 | None | CVL43 | Providing and laying in position Reinforced cement concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work and all other appurtenances required to complete the work as per technical specifications.
Mix 1:2:4 (M15) Using 20 mm nominal size graded crushed coarse aggregates. | Cum | 6596.12 | 6596.12 | 82.84 | False | None | None | False | None | False | 546422.5808 | 0 | 4044500 | 156944 | None | CVL44 | Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification - For buildings | Kg | 89.46 | 89.46 | 205367.82 | False | None | None | False | None | False | 18372205.1772 | 0 | 4044501 | 156944 | None | CVL45 | Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification -For other type of structures | Kg | 79.01 | 79.01 | 121556.67 | False | None | None | False | None | False | 9604192.4967 | 0 | 4044502 | 156944 | None | CVL46 | Providing and fixing Structural Steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a 2 coat of approved paint over the priming coat of approved steel primer all complete including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. | Kg | 113.0 | 113.0 | 75502.84 | False | None | None | False | None | False | 8531820.92 | 0 | 4044503 | 156944 | None | CVL47 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming andwatering, lead up to 50 m and lift upto 1.5 m. | Cum | 266.0 | 266.0 | 3336.7 | False | None | None | False | None | False | 887562.2 | 0 | 4044504 | 156944 | None | CVL48 | Removal of Unserviceable Soil with Disposal upto a suitable distance as directed by the Engineer incharge of work | Cum | 85.0 | 85.0 | 3693.87 | False | None | None | False | None | False | 313978.95 | 0 | 4044505 | 156944 | None | CVL49 | Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work. | Cum | 7969.0 | 7969.0 | 817.7 | False | None | None | False | None | False | 6516251.3 | 0 | 4044506 | 156944 | None | CVL50 | Providing 20 mm cement plaster of mix :1:6 (1 cement: 6 fine sand) to brick/stone masonary including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 333.0 | 333.0 | 9122.42 | False | None | None | False | None | False | 3037765.86 | 0 | 4044507 | 156944 | None | CVL51 | Providing 12 mm cement plaster with cement mortar 1:6 (1 cement: 6 fine sand) including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 241.0 | 241.0 | 3176.17 | False | None | None | False | None | False | 765456.97 | 0 | 4044508 | 156944 | None | CVL52 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of Engineer in charge. | Sqm | 100.0 | 100.0 | 7868.45 | False | None | None | False | None | False | 786845.0 | 0 | 4044509 | 156944 | None | CVL53 | Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade :Two coats on new work over one coat of primer after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 180.0 | 180.0 | 8218.45 | False | None | None | False | None | False | 1479321.0 | 0 | 4044510 | 156944 | None | CVL54 | Finishing walls with Acrylic Smooth exterior paint of required shade New work (Two coat applied @ 1.67 ltr/10 m² over and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. | Sqm | 174.0 | 174.0 | 4376.99 | False | None | None | False | None | False | 761596.26 | 0 | 4044511 | 156944 | None | CVL55 | Providing Water based glossy paint (Green certified product) to Kerb Stones as per IS 164:2015 technical specifications including cleaning & surface preparation | Sqm | 295.0 | 295.0 | 180.0 | False | None | None | False | None | False | 53100.0 | 0 | 4044512 | 156944 | None | CVL56 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (Made of G.I. wire of dia. 4 mm, PVC coated to achieve outer dia not less than 5 mm in required colour and shade) | Sqm | 841.0 | 841.0 | 517.5 | False | None | None | False | None | False | 435217.5 | 0 | 4044513 | 156944 | None | CVL57 | Fencing with G.I. barbed wire Angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 kg per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Cost of angle iron posts, struts, earth work and concrete work to be paid for separately). Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire | m | 18.0 | 18.0 | 1242.0 | False | None | None | False | None | False | 22356.0 | 0 | 4044514 | 156944 | None | CVL58 | Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate sections and other sections of approved make conforming to IS: 733 and IS:1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber / neoprene gasket required (Fittings shall be paid for separately) Polyester powder coated aluminium (minimum thickness of polyester powder coating 50 micron) including cost of materials, labour, usage charges of machinery complete as per specifications. | Kg | 582.0 | 582.0 | 1946.78 | False | None | None | False | None | False | 1133025.96 | 0 | 4044515 | 156944 | None | CVL59 | Providing and fixing double action hydraulic floor spring of approved brand manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge: With brass cover plate minimum 1.25 mm thickness including cost of materials, labour, usage charges of machinery complete as per specifications. | No | 2804.0 | 2804.0 | 27.0 | False | None | None | False | None | False | 75708.0 | 0 | 4044516 | 156944 | None | CVL60 | False ceiling: Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per m2 including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all T sections shall be pre-painted with polyster baked paint, for all heights, as per specifications, drawings and as directed by Engineer-in-Charge. | Sqm | 1693.0 | 1693.0 | 410.0 | False | None | None | False | None | False | 694130.0 | 0 | 4044517 | 156944 | None | CVL61 | Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS: 12823 Grade l Type ll, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of ngineer-in charge: Pre-laminated particle board with decorative lamination on one side and balancing lamination on other side including cost of materials, labour, usage charges of machinery complete as per specifications. | Sqm | 897.0 | 897.0 | 28.48 | False | None | None | False | None | False | 25546.56 | 0 | 4044518 | 156944 | None | CVL62 | Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5 mm thickness (weight not less than 12.50 kg/m²) including cost of materials, labour, usage charges of machinery complete as per specifications. | Sqm | 1171.0 | 1171.0 | 321.8 | False | None | None | False | None | False | 376827.8 | 0 | 4044519 | 156944 | None | CVL63 | Filling the gap in between aluminium/ stone/ wood frame and adjacent RCC/Brick/ Stone/ wood/ Ceramic/ Gypsum work by providing weather/structural non sag elastomeric PU sealant over backer rod of approved quality as per architectural drawings and direction of Engineer-in-charge complete, complying to ASTM C920, DIN 18540- F & ISO 11600 Upto 20 mm depth and 20 mm width including cost of materials, labour, usage charges of machinery complete as per specifications. | m | 296.0 | 296.0 | 897.4 | False | None | None | False | None | False | 265630.4 | 0 | 4044520 | 156944 | None | CVL64 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. | Sqm | 2633.0 | 2633.0 | 69.0 | False | None | None | False | None | False | 181677.0 | 0 | 4044521 | 156944 | None | CVL65 | Providing and fixing ball bearing for rolling shutters including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. | No | 403.0 | 403.0 | 8.0 | False | None | None | False | None | False | 3224.0 | 0 | 4044522 | 156944 | None | CVL66 | Extra for providing Manually operated Bevel Gear Box for operating rolling shutters including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. | No | 3086.0 | 3086.0 | 4.0 | False | None | None | False | None | False | 12344.0 | 0 | 4044523 | 156944 | None | CVL67 | Extra for providing 2 HP Mild Steel Auto Reverse Shutter Gearbox for operating rolling shutters including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. | No | 24686.0 | 24686.0 | 4.0 | False | None | None | False | None | False | 98744.0 | 0 | 4044524 | 156944 | None | CVL68 | Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slabover 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. ** Polished Granite stone slab Black, Cherry Red, Brown, Cat Eye, River Pink or equivalent. | Sqm | 2852.0 | 2852.0 | 487.07 | False | None | None | False | None | False | 1389123.64 | 0 | 4044525 | 156944 | None | CVL69 | Providing and laying 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 L per 50 kg of cement or as per direction of Engineer incharge.
Ironite flooring, | Sqm | 800.0 | 800.0 | 1400.0 | False | None | None | False | None | False | 1120000.0 | 0 | 4044526 | 156944 | None | CVL70 | Providing and laying 5mm thick Self levelling Epoxy Flooring for Residential, Commercial, Sports & Industrial purpose made of reputed brand applied at 1L/m2 on existing Concrete substrate of 25Mpa or more. The Concrete shall be free from any defects and cracks. The epoxy compound shall have low VOC (Based on USEPA Method 24 Section 11.2.2 & ASTM D2369-98)and is chemically resistant & antimicrobial. The surface of Concrete shall be cleaned thoroughly and free from laitance and applied with primer cured for 6-8 hours. The mix shall be mixed using Hand mixing rotary machine. The underlay shall be laid with 3mm thickness and overlay at 2mm. The entire operation shall be finished in line with epoxy coving and marked with 100mm thickness yellow marking lines complete as per the direction of Engineer in chargePU Coating/Epoxy flooring | Sqm | 1446.0 | 1446.0 | 1400.0 | False | None | None | False | None | False | 2024400.0 | 0 | 4044527 | 156944 | None | CVL71 | Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in- charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge | Kg | 565.0 | 565.0 | 2302.36 | False | None | None | False | None | False | 1300833.4 | 0 | 4044528 | 156944 | None | CVL72 | Providing and fixing of wall cladding using 20mm thick gang saw water cut Shiva gold granite, grey granite in CM 1:3 (1 cement : 3 coarse sand) proportion cut to required shape, pattern with paper joints, finished with cement mortal using white cement and colour pigments to match the colour of slab making through jointing with sealant, making holes 25mmx12mm grooves in joints including cost of all materials, mortar, labour, curing etc., complete. | Sqm | 3359.0 | 3359.0 | 450.0 | False | None | None | False | None | False | 1511550.0 | 0 | 4044529 | 156944 | None | CVL73 | Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) greater than 78, solar reflection greater than 0.70 and initial emittance greater than 0.75 on waterproof and slo[ed surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement :4 coarse sand) and grounting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm heightr along the parapet walls in the same manner as per direction of incharge | Sqm | 1405.0 | 1405.0 | 639.0 | False | None | None | False | None | False | 897795.0 | 0 | 4044530 | 156944 | None | CVL74 | Providing skirting, dadooing, rises of steps with colour glazed tiles 6mm thick on 10mm thick cement plaster 1:3 and jointed with white cement slurry over existing rough plaster surface using glazed tiles of approved make and size including cost of materials, labour, complete as per specifications. | Sqm | 1449.0 | 1449.0 | 67.2 | False | None | None | False | None | False | 97372.8 | 0 | 4044531 | 156944 | None | CVL75 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thick ness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick bed of cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ m2 including pointing the joints with white cement and matching pigments etc., complete | Sqm | 889.0 | 889.0 | 16.0 | False | None | None | False | None | False | 14224.0 | 0 | 4044532 | 156944 | None | CVL76 | Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding for Bathrooms: Toilet: Chemically exposed areas and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge.
In dado/skirting on 12 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand) with Acid and alkali resistant tile | Sqm | 1260.0 | 1260.0 | 67.2 | False | None | None | False | None | False | 84672.0 | 0 | 4044533 | 156944 | None | CVL77 | Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding for Bathrooms: Toilet: Chemically exposed areas and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge.
In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand) with Acid and alkali resistant tile. | Sqm | 1246.0 | 1246.0 | 60.0 | False | None | None | False | None | False | 74760.0 | 0 | 4044534 | 156944 | None | CVL78 | Providing and fixing chromium plated brass handles of 100/125 mm with necessary screws etc. complete. | No | 237.0 | 237.0 | 30.0 | False | None | None | False | None | False | 7110.0 | 0 | 4044535 | 156944 | None | CVL79 | Providing and fixing bright finished brass butt hinges with necessaryscrews etc. complete. 125x85x5.5mm (Heavy type) : | No | 275.0 | 275.0 | 30.0 | False | None | None | False | None | False | 8250.0 | 0 | 4044536 | 156944 | None | CVL80 | Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade, with necessary screws etc. complete. | No | 130.0 | 130.0 | 30.0 | False | None | None | False | None | False | 3900.0 | 0 | 4044537 | 156944 | None | CVL81 | Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete. | No | 1052.0 | 1052.0 | 30.0 | False | None | None | False | None | False | 31560.0 | 0 | 4044538 | 156944 | None | CVL82 | supplying and fixing hold fasts. Hold fasts | No | 50.0 | 50.0 | 30.0 | False | None | None | False | None | False | 1500.0 | 0 | 4044539 | 156944 | None | CVL83 | Providing & fixing CPVC pipes having thermal stablity for hot & cold water supply, including all CPVC plain and brass threaded fittings, including fixing the pipe with clamps at 1.00M spacing. this includes jointing of pipes and fittings with one step CPVC solvent cement and testing of joints complete as per specifications -
32mm nominal dia pipes. | m | 400.0 | 400.0 | 250.0 | False | None | None | False | None | False | 100000.0 | 0 | 4044540 | 156944 | None | CVL84 | Providing & fixing CPVC pipes having thermal stablity for hot & cold water supply, including all CPVC plain and brass threaded fittings, including fixing the pipe with clamps at 1.00M spacing. this includes jointing of pipes and fittings with one step CPVC solvent cement and testing of joints complete as per specifications -
20mm nominal dia pipes. | m | 242.0 | 242.0 | 100.0 | False | None | None | False | None | False | 24200.0 | 0 | 4044541 | 156944 | None | CVL85 | White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar tap. | No | 2561.0 | 2561.0 | 6.0 | False | None | None | False | None | False | 15366.0 | 0 | 4044542 | 156944 | None | CVL86 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required. One urinal basin with 5 litre white P.V.C. automatic flushing cistern. | No | 4454.0 | 4454.0 | 4.0 | False | None | None | False | None | False | 17816.0 | 0 | 4044543 | 156944 | None | CVL87 | Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing. Rectangular shape 453x357 mm, | No | 1018.0 | 1018.0 | 6.0 | False | None | None | False | None | False | 6108.0 | 0 | 4044544 | 156944 | None | CVL88 | Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. 32 mm dia, | No | 76.0 | 76.0 | 6.0 | False | None | None | False | None | False | 456.0 | 0 | 4044545 | 156944 | None | CVL89 | Providing and fixing 100 mm sand cast Iron grating for gully trap. | No | 47.0 | 47.0 | 10.0 | False | None | None | False | None | False | 470.0 | 0 | 4044546 | 156944 | None | CVL90 | Providing and fixing PTMT towel ring trapezoidal shape 215 mm long, 200 mm wide with minimum distances of 37 mm from wall face with concealed fittings rrangement of approved quality and colour, weighing not less than 88 g. 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 g. | No | 496.0 | 496.0 | 4.0 | False | None | None | False | None | False | 1984.0 | 0 | 4044547 | 156944 | None | CVL91 | Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean type W.C. of quality and make as approved by Engineer - in - charge. | No | 272.0 | 272.0 | 4.0 | False | None | None | False | None | False | 1088.0 | 0 | 4044548 | 156944 | None | CVL92 | Providing and fixing vitreous china dual purpose closet suitable for use as squatting pan or European type water closet (Anglo Indian W.C pan) with seat & lid fixed with C.P. brass hinges and rubber buffers, 10 litre low level flushing cistern with fitting and brackets, 40 mm flush bend, 20 mm over flow pipe, with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required: White vitreous china dual purpose WC pan with white solid plastic seat and lid with white vitreous china flushing cistern and C.P. flush bend., | No | 8632.0 | 8632.0 | 4.0 | False | None | None | False | None | False | 34528.0 | 0 | 4044549 | 156944 | None | CVL93 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests. | No | 4884.0 | 4884.0 | 4.0 | False | None | None | False | None | False | 19536.0 | 0 | 4044550 | 156944 | None | CVL94 | Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings. | No | 1423.0 | 1423.0 | 6.0 | False | None | None | False | None | False | 8538.0 | 0 | 4044551 | 156944 | None | CVL95 | Bottle trap 31mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the centre of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 260 gms. | No | 306.0 | 306.0 | 6.0 | False | None | None | False | None | False | 1836.0 | 0 | 4044552 | 156944 | None | CVL96 | Providing and fixing Brass full way valve gate with C.I. wheel of approved quality (screwed end) : 32 mm nominal bore. | No | 598.0 | 598.0 | 10.0 | False | None | None | False | None | False | 5980.0 | 0 | 4044553 | 156944 | None | CVL97 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS:893. | No | 635.0 | 635.0 | 10.0 | False | None | None | False | None | False | 6350.0 | 0 | 4044554 | 156944 | None | CVL98 | Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame. | m | 643.0 | 643.0 | 25.0 | False | None | None | False | None | False | 16075.0 | 0 | 4044555 | 156944 | None | CVL99 | Providing and fixing to existing door frames Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast onolithically with 5 mm thick FRP laminate for panels conforming to IS: 14856, including fixing to frames.30mm Thickness. | Sqm | 3204.0 | 3204.0 | 10.0 | False | None | None | False | None | False | 32040.0 | 0 | 4044556 | 156944 | None | CVL100 | Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for:.
PVC pipes 110mm dia., 6 kg/sqcm & class 3, | m | 411.0 | 411.0 | 756.0 | False | None | None | False | None | False | 310716.0 | 0 | 4044557 | 156944 | None | CVL101 | Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for:
PVC pipes 160mm dia., 6 kg/sqcm & class 3, | m | 618.0 | 618.0 | 300.0 | False | None | None | False | None | False | 185400.0 | 0 | 4044558 | 156944 | None | CVL102 | Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with latest amentments using ordinary portland cement, for sanitary works and conveying to work site, rolling and lowering into trenches, laying true to line and level including loading and unloading at both destinations and jointing of pipes and specials, perfect linking of joints with jack to correct position including cost of jointing materials, i.e, rubber rings conforming to IS: 5382 for S&S RCC pipes, with all leads and lifts as directed and giving necessary hydraulic test as per ISS to the required pressure and commissioning etc. complete. (Contractor will make his own arrangements for procuring water for testing). Before the execution of the work, the contractor shall carry out the survey.
RCC NP3 Class pipe of 450 mm dia | m | 2353.0 | 2353.0 | 30.0 | False | None | None | False | None | False | 70590.0 | 0 | 4044559 | 156944 | None | CVL103 | Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with latest amentments using ordinary portland cement, for sanitary works and conveying to work site, rolling and lowering into trenches, laying true to line and level including loading and unloading at both destinations and jointing of pipes and specials, perfect linking of joints with jack to correct position including cost of jointing materials, i.e, rubber rings conforming to IS: 5382 for S&S RCC pipes, with all leads and lifts as directed and giving necessary hydraulic test as per ISS to the required pressure and commissioning etc. complete. (Contractor will make his own arrangements for procuring water for testing). Before the execution of the work, the contractor shall carry out the survey.
RCC NP3 Class pipe of 300 mm dia | m | 1332.0 | 1332.0 | 50.0 | False | None | None | False | None | False | 66600.0 | 0 | 4044560 | 156944 | None | CVL104 | Providing Size Stone masonry with hard stone in foundation & plinth with
Cement mortar 1:6 (1 cement : 6 coarse sand) | Cum | 6389.0 | 6389.0 | 10.82 | False | None | None | False | None | False | 69128.98 | 0 | 4044561 | 156944 | None | CVL105 | Providing flush/ruled pointing on stone work with cement mortar 1:3 after raking joints to depth nicely lining, including cost of materials, labours, curing as per specifications and direction of engineer in-charge of work. | Sqm | 255.0 | 255.0 | 15.6 | False | None | None | False | None | False | 3978.0 | 0 | 4044562 | 156944 | None | CVL106 | Cutting transverse contraction joints in concrete road using concrete cutting machine with diamond studded saw as per standard technical specificatio and direction of engineer incharge of work including cost of materials, labours etc., complete. | m | 70.0 | 70.0 | 270.0 | False | None | None | False | None | False | 18900.0 | 0 | 4044563 | 156944 | None | CVL107 | Providing and filling joint sealing compound as per approved drawing and technical specification with coarse sand and 6 percent bitumen by weight, | m | 48.0 | 48.0 | 270.0 | False | None | None | False | None | False | 12960.0 | 0 | 4044564 | 156944 | None | CVL108 | Providing and fixing rainy make rain water filter of FL500 specification as per direction of engineer in charge of work. | No | 10500.0 | 10500.0 | 1.0 | False | None | None | False | None | False | 10500.0 | 0 | 4044565 | 156944 | None | CVL109 | Providing & fixing 1.5HP mono submersible pump set for rain water sump with electrification including necessary cables, starter and control panels | No | 10000.0 | 10000.0 | 2.0 | False | None | None | False | None | False | 20000.0 | 0 | 4044566 | 156944 | None | CVL110 | Sinking of borewell of 165mm mm clear using Super fast hydrualic rig of capacity 3000PSIG and above 1100CMF and above in all strata including over burden upto 20 m fixing of casing pipe, collers and cap with necessary cutting and threading and welding including transportation of rig and supporting vehicles screw charges and cost of consumables etc., complete including yeld testing at final depth with minimum continous working of compressor for 1 hour(Excluding cost of casing pipes,collars and cap etc)
depth Upto 0 to 50.00 mtrs. | m | 370.0 | 370.0 | 50.0 | False | None | None | False | None | False | 18500.0 | 0 | 4044567 | 156944 | None | CVL111 | Sinking of borewell of 165mm mm clear using Super fast hydrualic rig of capacity 3000PSIG and above 1100CMF and above in all strata including over burden upto 20 m fixing of casing pipe, collers and cap with necessary cutting and threading and welding including transportation of rig and supporting vehicles screw charges and cost of consumables etc., complete including yeld testing at final depth with minimum continous working of compressor for 1 hour(Excluding cost of casing pipes,collars and cap etc)
depth 50.00 mtrs to 100.00 mtrs. | m | 464.0 | 464.0 | 50.0 | False | None | None | False | None | False | 23200.0 | 0 | 4044568 | 156944 | None | CVL112 | Sinking of borewell of 165mm mm clear using Super fast hydrualic rig of capacity 3000PSIG and above 1100CMF and above in all strata including over burden upto 20 m fixing of casing pipe, collers and cap with necessary cutting and threading and welding including transportation of rig and supporting vehicles screw charges and cost of consumables etc., complete including yeld testing at final depth with minimum continous working of compressor for 1 hour(Excluding cost of casing pipes,collars and cap etc)
depth 100.00 mtrs to 150.00 mtrs. | m | 493.0 | 493.0 | 50.0 | False | None | None | False | None | False | 24650.0 | 0 | 4044569 | 156944 | None | CVL113 | Sinking of borewell of 165mm mm clear using Super fast hydrualic rig of capacity 3000PSIG and above 1100CMF and above in all strata including over burden upto 20 m fixing of casing pipe, collers and cap with necessary cutting and threading and welding including transportation of rig and supporting vehicles screw charges and cost of consumables etc., complete including yeld testing at final depth with minimum continous working of compressor for 1 hour(Excluding cost of casing pipes,collars and cap etc)
depth 150.00 mtrs to 200.00 mtrs. | m | 572.0 | 572.0 | 50.0 | False | None | None | False | None | False | 28600.0 | 0 | 4044570 | 156944 | None | CVL114 | Sinking of borewell of 165mm mm clear using Super fast hydrualic rig of capacity 3000PSIG and above 1100CMF and above in all strata including over burden upto 20 m fixing of casing pipe, collers and cap with necessary cutting and threading and welding including transportation of rig and supporting vehicles screw charges and cost of consumables etc., complete including yeld testing at final depth with minimum continous working of compressor for 1 hour(Excluding cost of casing pipes,collars and cap etc)
depth 200.00 mtrs to 250.00 mtrs. | m | 671.0 | 671.0 | 50.0 | False | None | None | False | None | False | 33550.0 | 0 | 4044571 | 156944 | None | CVL115 | Sinking of borewell of 165mm mm clear using Super fast hydrualic rig of capacity 3000PSIG and above 1100CMF and above in all strata including over burden upto 20 m fixing of casing pipe, collers and cap with necessary cutting and threading and welding including transportation of rig and supporting vehicles screw charges and cost of consumables etc., complete including yeld testing at final depth with minimum continous working of compressor for 1 hour(Excluding cost of casing pipes,collars and cap etc)
depth 250.00 mtrs to 300.00 mtrs. | m | 740.0 | 740.0 | 50.0 | False | None | None | False | None | False | 37000.0 | 0 | 4044572 | 156944 | None | CVL116 | Sinking of borewell of 165mm mm clear using Super fast hydrualic rig of capacity 3000PSIG and above 1100CMF and above in all strata including over burden upto 20 m fixing of casing pipe, collers and cap with necessary cutting and threading and welding including transportation of rig and supporting vehicles screw charges and cost of consumables etc., complete including yeld testing at final depth with minimum continous working of compressor for 1 hour(Excluding cost of casing pipes,collars and cap etc)
depth 300.00 mtrs to 350.00 mtrs. | m | 868.0 | 868.0 | 50.0 | False | None | None | False | None | False | 43400.0 | 0 | 4044573 | 156944 | None | CVL117 | Sinking of borewell of 165mm mm clear using Super fast hydrualic rig of capacity 3000PSIG and above 1100CMF and above in all strata including over burden upto 20 m fixing of casing pipe, collers and cap with necessary cutting and threading and welding including transportation of rig and supporting vehicles screw charges and cost of consumables etc., complete including yeld testing at final depth with minimum continous working of compressor for 1 hour(Excluding cost of casing pipes,collars and cap etc)
depth 350.00 mtrs to 400.00 mtrs. | m | 937.0 | 937.0 | 50.0 | False | None | None | False | None | False | 46850.0 | 0 | 4044574 | 156944 | None | CVL118 | Supply of ISI mark 175mm nominal bore,plain and steel casing pipe grade of steel Fe 410 of wall thickness conforming to IS 4270-2001 andlatest ammendments, electrical resistance welded steel tubes, material and conforming to IS 1387-1993 and manufactured by basic open hearth electric or basic oxygen process in random length of 5-7m both ends.threaded conforming to IS 554-1985 one end fixed with socket conforming to IS 4270-2001 and the other end with screwed pipes all shall be responsibaly free from defects. The tubes shall be responsible straight end should be with ISI marking weighing 25.10kg/m.pricesinclude Collar-Medium duty | m | 1933.0 | 1933.0 | 25.0 | False | None | None | False | None | False | 48325.0 | 0 | 4044575 | 156944 | None | CVL119 | Providing and laying at site of work MS casing caps as per IS 1239 (part- II) 1982 with all latest amendments if any for any dia. The thickness of plate used for covering one end shall be 3mm (minimum). The dimensions of caps and colars shall be strictly as per IS 1239 (Part-II) 1982 with all amendments including cost of material and labour charges for fixing, if any etc. complete with all lead and lifts and as directed by the Engineer in charge | No | 164.0 | 164.0 | 1.0 | False | None | None | False | None | False | 164.0 | 0 | 4044576 | 156944 | None | CVL120 | Geophysical investigation at site for sinking borewells for providing drinking water to the habitation either through the Hand Pump MWS or P.W.S.S, by vertical electrical sounding by adopting Venner or Schlumbergers’s method, including reconnaissance survey of geological formation. Geophysical investigation of existing ground water in the vicinity, its quality, quantity and acceptability of the users, indicating the location of the site, recommended depth of casing pipe required to seal the top unconsolidated formation including an extra depth of 1.0 metre in consolidated formation for proper seating of casing pipe, depth of drilling required to cover full depth of aquifer proposed to be tapped, probable yield and other information required including transportation of instruments and accessories to work site, engaging technical personal and labour required etc | No | 5288.0 | 5288.0 | 1.0 | False | None | None | False | None | False | 5288.0 | 0 | 4044577 | 156944 | None | CVL121 | PUMPSET :
Providing, Single Phase Submersible Pump Sets of 100mm dia (4 inch) suitable for bore well confirming to IS 8034-2000 specifications, to work site with testing of as per instructions of engineer incharge of work and latest ammendments etc. complete 5.00 HP 50 STG | No | 29650.0 | 29650.0 | 1.0 | False | None | None | False | None | False | 29650.0 | 0 | 4044578 | 156944 | None | CVL122 | Supply and delivery at site Brand new best make PVC insulated submersible cable of Flat 3 core (sheathed) of nominal cross sectional area as per IS 694-1990 with ISI Mark and as per its latest amendments. 3CX4.0Sq.mm | m | 135.0 | 135.0 | 900.0 | False | None | None | False | None | False | 121500.0 | 0 | 4044579 | 156944 | None | CVL123 | PRESSURE GAUGE :
Supply and delivery at site of brand new best make pressure gauge bourdon type as per IS 778/1984 with ISI Mark and as per its latest amendments. For size 100mm | No | 654.0 | 654.0 | 1.0 | False | None | None | False | None | False | 654.0 | 0 | 4044580 | 156944 | None | CVL124 | GATE VALVE :
Supply and delivery at site of brand new best make gate valve as per IS 778/1984 with ISI Mark and as per its latest amendments. | No | 1250.0 | 1250.0 | 1.0 | False | None | None | False | None | False | 1250.0 | 0 | 4044581 | 156944 | None | CVL125 | NON - RETURN VALVE :
Providing and fixing in position 50mm dia nominal bore gun metal non-return valve horizontal type of approved make mark including cost of all materials, lab our and HOM of equipments with all leads complete as per secificationns. | No | 1250.0 | 1250.0 | 1.0 | False | None | None | False | None | False | 1250.0 | 0 | 4044582 | 156944 | None | CVL126 | Control panel board for borewell motor pumpset:
Supply, installing,testing and commissioning COMMON control panel consisting of the following INCOMING:1 No set of Phase indicating lamps with SFU of suitable rating 1 No, Analog Ammeter, 1 No Analog Voltmeter 1ni with Phase selector switch, Isolating switch OUTGOING for Main Electrical Pump: 1 No. MCB 1 No. DOL of S/D Starter suitable for respective HP 1 No. Electrcal Protection Like single Phase preventor, under voltage over Volage, under current over current & dry run protection suitable for the pump described above 1 no Indoor type NOTE: 1) DOLDirect Online Starter 2)S-D- Star Delta Starter | No | 9550.0 | 9550.0 | 1.0 | False | None | None | False | None | False | 9550.0 | 0 | 4044583 | 156944 | None | CVL127 | POWER CAPACITOR :
Supply and delivery at site best indigenous brand new power capacitor as per IS 2834/1986 with latest amendments with KPTCL authorities and erection, electrification and commissioning of the same at the location of respective pump sets. | Kvar | 550.0 | 550.0 | 2.0 | False | None | None | False | None | False | 1100.0 | 0 | 4044584 | 156944 | None | CVL128 | MCB :
Supply and delivery at site delivery of best indigenous brand new MCB(Miniature Circuit Breakers) of required capacity as per IS 88228/1978 and its latest amendments and with ISI Mark of 6/10/16/20/25/40 Amps with scalable box. | Per 3 Poles | 1250.0 | 1250.0 | 1.0 | False | None | None | False | None | False | 1250.0 | 0 | 4044585 | 156944 | None | CVL129 | HDPE Pipes:
Supplying & installation of 50mm dia HDPE pipes of specified grade and confirming to IS standards and direction of engineer in charge of work including cost of labour, materials etc., complete as per specification | No | 200.0 | 200.0 | 450.0 | False | None | None | False | None | False | 90000.0 | 0 | 4044586 | 156944 | None | CVL130 | Erection elctrification & Commissioning works of pumpsets :
Labour Charges Including aligning and balancing with all necessary erection of materials and labour including supply & erection of two pair of supporting clamps borewell cap, cable clips, water right glands, cable protectors bolts, nuts, valves & gauges etc., involved in the job. the contractor has to arrange at his own cost all erection materials. | No | 6500.0 | 6500.0 | 1.0 | False | None | None | False | None | False | 6500.0 | 0 | 4044587 | 156944 | None | CVL131 | Main connections:
Providing main connection from pole PVC insulated sheathed steel wire cable in new trench as per IS 1554/ 1988 with latest amendments with ISI mark from KPTCL pole to meter board unit. | m | 135.0 | 135.0 | 50.0 | False | None | None | False | None | False | 6750.0 | 0 | 4044588 | 156944 | None | CVL132 | ELECTRICAL ACCESSORIES:
Supplying of TPST with reqirable porcelain channels in SM enclosure, made out of 14 SWG powder coated paint of approved colour. 32 AMPS. | No | 1701.0 | 1701.0 | 6.0 | False | None | None | False | None | False | 10206.0 | 0 | 4044589 | 156944 | None | CVL133 | Supplying and fixing of Porcelain fuse channel with cut out on existing wooden/panel using necessary nuts, bolts and washers 32 AMPS | No | 241.0 | 241.0 | 6.0 | False | None | None | False | None | False | 1446.0 | 0 | 4044590 | 156944 | None | CVL134 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work
for 50mm dia | m | 721.0 | 721.0 | 300.0 | False | None | None | False | None | False | 216300.0 | 0 | 4044591 | 156944 | None | CVL135 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work
for 40mm dia | m | 477.0 | 477.0 | 250.0 | False | None | None | False | None | False | 119250.0 | 0 | 4044592 | 156944 | None | CVL136 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. External work
for 25mm dia | m | 296.0 | 296.0 | 75.0 | False | None | None | False | None | False | 22200.0 | 0 | 4044593 | 156944 | None | CVL137 | Construction of brick masonry inspection chambers of internal dimension 600x600 mm and depth 600mm(inner dimension) with modular bricks in CM 1:6, bed concrete 150mm thick with 1;3:6, platering 12mm thick with CM 1:4, CC 1:2:4 coping 75mm thick for provding and fixing CI cover and frame with weight to be not less than 38kgs and necessary locking arrangemnets with MS flats and painting with two or more coats with black paint etc. complete as directed by the engineer in charge of work | No | 7416.0 | 7416.0 | 8.0 | False | None | None | False | None | False | 59328.0 | 0 | 4044594 | 156944 | None | CVL138 | Construction of brick masonry inspection chambers of internal dimension 450x450 mm and depth 600mm(inner dimension) with modular bricks in CM 1:6, bed concrete 150mm thick with 1;3:6, platering 12mm thick with CM 1:4, CC 1:2:4 coping 75mm thick for provding and fixing CI cover and frame with weight to be not less than 38kgs and necessary locking arrangemnets with MS flats and painting with two or more coats with black paint etc. complete as directed by the engineer in charge of work | No | 6198.0 | 6198.0 | 13.0 | False | None | None | False | None | False | 80574.0 | 0 | 4044595 | 156944 | None | CVL139 | Clearing and grubbing road land including uprooting rank vegetation, grass, bushes, shrubs, saplings and trees girth up to 300 mm, removal of stumps of trees cut earlier and disposal of unserviceable materials and stacking of serviceable material to be used or auctioned, including removal and disposal of top organic soil not exceeding 150 mm in thickness.
By Mechanical Means using Dozer | Sqm | 3.93 | 3.93 | 5000.0 | False | None | None | False | None | False | 19650.0 | 0 | 4044596 | 156944 | None | CVL140 | Lean concrete: Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators,including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, and all the other appurtenances required to complete the work as per technical specifications.
Mix 1:5:10 Using 40 mm nominal size graded crushed coarse aggregates | Cum | 5338.0 | 5338.0 | 345.0 | False | None | None | False | None | False | 1841610.0 | 0 | 4044597 | 156944 | None | CVL141 | Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.
M 40 Design Mix Using 20 mm nominal size graded crushed coarse aggregates | Cum | 7898.1 | 7898.1 | 135.0 | False | None | None | False | None | False | 1066243.5 | 0 | 4044598 | 156944 | None | CVL142 | Providing, laying, spreading and compacting graded stone aggregates to wet mix macadam specifications including premixing the materila with water at OMC in mechanical mix plant carriage of mixed material by tipper to site,laying in uniform layers with paver/grader in sub-base/base course on well prepared surface and compacting with vibratory roller to achieve the desired density. | Cum | 2559.0 | 2559.0 | 194.4 | False | None | None | False | None | False | 497469.6 | 0 | 4044599 | 156944 | None | CVL143 | Construction of subgrade and earthen shoulders with approved material obtained from borrow pits with all lifts and leads, transporting to site, spreading, grading to required slope and compacted to meet requiremnt of table No.300-2 | Cum | 493.0 | 493.0 | 86.3999 | False | None | None | False | None | False | 42595.1507 | 0 | 4044600 | 156944 | None | CVL144 | Bituminous layer for oil sump: Providing and laying of 1.5 mm thick SBS modified self adhesive single stick waterproofing membrane, with minimum elongation of 300% and puncture resistance of greater than200 N (as per ASTM E154), with an overlap of 100mm on the side and 100mm in vertical lapping over a coat bituminuos primer @ 0.25 l/m2, complete including surface preparation as per the methodology and site condition & placing the dimple board over the SBS membrane. The cost is nclusive of surface preparation, crack filling, repair of loose mortar etc. completely as per specification. | Sqm | 761.0 | 761.0 | 52.8 | False | None | None | False | None | False | 40180.8 | 0 | 4044601 | 156944 | None | CVL145 | Providing and fixing false flooring as per KPTCL specfication including cost of structural steel, fasle flooring materials, labour charges, etc., complete as per direction of engineer in charge of work. | Sqm | 5500.0 | 5500.0 | 300.0 | False | None | None | False | None | False | 1650000.0 | 0 | 4044602 | 156944 | None | CVL146 | Providing and fixing modular cable cealing system as per KPTCL specfication including cost of materials, labour charges, etc., complete as per direction of engineer in charge of work. | No | 20000.0 | 20000.0 | 7.0 | False | None | None | False | None | False | 140000.0 | 0 | 4044603 | 156944 | None | CVL147 | Double Leaf doorset - Insulated Fire rated doorset (FD 120) - Staircase / exit pathway application / Refuge area. Providing and fixing of ISI marked fire doors as per IS 3614:2021, 120 minutes fire rating with 30 minutes insulation double leaf doorset tested to IS/ISO 3008. Doorset shall include grooved step frame profile of 125x75mm, made of 1.2mm GI (120GSM) and 60mm thick shutter made of 1.2mm GI (120GSM) with infill of 120kg density mineral wool. Grooved frame shall include EPDM smoke seal. Include hardwares, minimum 6nos SS ball bearing hinges of SS304 100x89x3mm, 1no of Single point Panic device and external trim with key cylinder on active leaf and 1no two point Panic device on the inactive leaf, tested as per EN1125 and CE marked. 2no of Door closer with spring size of EN 3-5, as per EN1154 and CE marked. 1no door coordinator for sequencing. 2nos vision panel 200 x 300 with 6mm clear fire rated glass and finished in desired colour of powder coating not less than 50microns including suitable anchors & fire rated puff grouting all inclusive for fixing of doorset - for staircase / exit pathway / Refuge area applications. | Sqm | 20000.0 | 20000.0 | 25.0 | False | None | None | False | None | False | 500000.0 | 0 | 4044604 | 156944 | None | CVL148 | Design, fabrication, supply, erection, testing and commissioning of EOT crane consisting of double girder box type construction, rail mounted end carraiges with long and cross travel arrangement, main and auxiliary hoists of specified capacity, rails, pendant control, gear boxes, electric motors, brakes, rope drums, wire ropes, sheaves, end buffer stoppers, pendant operated DSL bus bars with all accessories for main and auxiliary hoists for handling GIS modules including cost of all materials,machinery, labour,cutting, aligning,welding, finishing, cleaning, greasing, applying two coats of zinc chromate red oxide primer and three coats of synthetic enamel paint and all other ancillary operations complete as per specifications and approved drawings. | Tonne | 212100.0 | 212100.0 | 10.0 | False | None | None | False | None | False | 2121000.0 | 0 | 4044605 | 156944 | None | CVL149 | Supply, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type horizontal/vertical air handling units made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters,belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 plus and minus 10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification | No | 276004.0 | 276004.0 | 4.0 | False | None | None | False | None | False | 1104016.0 | 0 | 4044606 | 156944 | None | CVL150 | Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sqmm) for integration within AHU room- Damper | Sqm | 8784.0 | 8784.0 | 1.0 | False | None | None | False | None | False | 8784.0 | 0 | 4044607 | 156944 | None | CVL151 | Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. | Sqm | 9105.0 | 9105.0 | 10.0 | False | None | None | False | None | False | 91050.0 | 0 | 4044608 | 156944 | None | CVL152 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
(a) Thickness 0.63 mm sheet | Sqm | 1080.0 | 1080.0 | 400.0 | False | None | None | False | None | False | 432000.0 | 0 | 4044609 | 156944 | None | CVL153 | Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
(b) Thickness 0.8 mm sheet | Sqm | 1263.0 | 1263.0 | 80.0 | False | None | None | False | None | False | 101040.0 | 0 | 4044610 | 156944 | None | CVL154 | Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. | Sqm | 7046.0 | 7046.0 | 3.0 | False | None | None | False | None | False | 21138.0 | 0 | 4044611 | 156944 | None | CVL155 | Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications -
Fire damper | Sqm | 10659.0 | 10659.0 | 3.0 | False | None | None | False | None | False | 31977.0 | 0 | 4044612 | 156944 | None | CVL156 | Supplying, fixing acoustic lining on walls of AHU rooms with 50mm thick, density 32 kg/cum resin bonded glass fiber insulation friction fixed in 610mm x 610mm frame work made of 25x50x50x50x25mm made out of 0.6mm thick GI sheet U shaped channel and covered with reinforced fibre glass tissue and finished with 0.8mm perforated aluminium sheet etc., complete as required and as per specifications. | Sqm | 1229.0 | 1229.0 | 160.0 | False | None | None | False | None | False | 196640.0 | 0 | 4044613 | 156944 | None | CVL157 | Supplying and installing following size of perforated hot dipped galvanised iron cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with GI suspenders including GI bots & nuts, etc., as required.
100mm width x 50mm depth x 1.6mm thickness | m | 669.0 | 669.0 | 600.0 | False | None | None | False | None | False | 401400.0 | 0 | 4044614 | 156944 | None | CVL158 | Design, supplying, erecting testing and commissioning of-Passenger /Bed-cum-passenger hospital lift with speed of 1mtr per second ,variable voltagevariable frequency drive, with r without machine room for the available wellsize ,operatingat 415V3 phase 50cycles ACsupply, powdercoated /StainlessSteel car entrance doors enclosures with suitable colour vinyl flooring, LED car illumination, emergency light, inter com and fan as desired by the user, central opening /side opening door with or without attendant operation, 7segment display buttons, call registerindicator, firemandrive, SShandrails n sidecar, full length infrared curtainin cardoor, automatic rescuede vice with batteries, voice announcing in regional/ international languages, Braille buttons with one year warranty and maintenance with necessary scaffolding and minor civil works like fixing of guiderail, counterweight etc., The total product and servicess hall adhere to IS14665/2016 (with latest amendments) part/ section1to5 with regards to general guidelines of fire safety rated doors, MRLL beams, pressure switch, manual change over fo doors during emergency, ARD of 10 times with sufficient battery backup and standard dimensions of chair car and door openings for all sizes and capacities of lifts including fitness certificate and duly observing all other safety norms prescribed and adhere to CPWD specifications, PCB Norms, National Electricity Code (NEC), NBC-2016, IEC and Karnataka State Lifts, Escalators and Passengers Conveyers Act 2012 and Rules 2014. The Supplier shall be registered in government Electrical Inspectorate in the State of Karnataka. With Out Machine Room-SS Finish. 15 passengers 4 Stops. | No | 1964217.61 | 1964217.61 | 1.0 | False | None | None | False | None | False | 1964217.61 | 0 | 4044615 | 156944 | None | CVL159 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. | l | 9.0 | 9.0 | 4000.0 | False | None | None | False | None | False | 36000.0 | 0 | 4044616 | 156944 | None | CVL160 | Industrial type lift: Industrial lift of minimum 3.5 Ton (of size 3Mx 6m). The size and capacity is indicative only. The size shall be sufficient to move GIS module of largest dimension (LxBxH) and maximum weight. The successfuk bidder has to provide adequate sizing during execution. The rate is inclusive of lift room also and other civil works. | No | 3000000.0 | 3000000.0 | 1.0 | False | None | None | False | None | False | 3000000.0 | 0 | 4044617 | 156944 | None | CVL161 | Electrification:
Supplying heavy gauge PVC conduit pipe ……mm dia ....... mm thick confirming to IS 2509 with suitable size bends, metal/PVC junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary.
19/20mm dia 2mm thick. | m | 66.0 | 66.0 | 830.0 | False | None | None | False | None | False | 54780.0 | 0 | 4044618 | 156944 | None | CVL162 | Supplying heavy gauge PVC conduit pipe ……mm dia ....... mm thick confirming to IS 2509 with suitable size bends, metal/PVC junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary.
25mm dia 2mm thick. | m | 78.0 | 78.0 | 830.0 | False | None | None | False | None | False | 64740.0 | 0 | 4044619 | 156944 | None | CVL163 | Supplying heavy gauge PVC Conduit Pipe ….dia .......mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering up to the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary.
19/20mm dia 2mm thick. | m | 68.0 | 68.0 | 830.0 | False | None | None | False | None | False | 56440.0 | 0 | 4044620 | 156944 | None | CVL164 | Supplying heavy gauge PVC Conduit Pipe ….dia .......mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering up to the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary.
25mm dia 2mm thick. | m | 79.0 | 79.0 | 830.0 | False | None | None | False | None | False | 65570.0 | 0 | 4044621 | 156944 | None | CVL165 | Supplying and fixing sheet metal box made out of 18 SWG sheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc. 100x75x65mm | No | 118.0 | 118.0 | 30.0 | False | None | None | False | None | False | 3540.0 | 0 | 4044622 | 156944 | None | CVL166 | Supplying and fixing sheet metal box made out of 18 SWG sheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc. 135x75x65mm | No | 139.0 | 139.0 | 30.0 | False | None | None | False | None | False | 4170.0 | 0 | 4044623 | 156944 | None | CVL167 | Supplying PVC/GI flexible conduit pipe…mm dia fixing on surface over inverted tapered wooden plugs or phill plugs or rawl plugs and clamped using heavy gauge saddles at an interval of 300mm using NF screws and on either end of the pipe terminated completely. 25mm | m | 22.0 | 22.0 | 130.0 | False | None | None | False | None | False | 2860.0 | 0 | 4044624 | 156944 | None | CVL168 | Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet.
Short point upto 3Mtr from tapping point to out let via switch box | No | 269.0 | 269.0 | 60.0 | False | None | None | False | None | False | 16140.0 | 0 | 4044625 | 156944 | None | CVL169 | Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet.
Medium point above 3Mtr upto 6Mtr from tapping point to out let via switch box. | No | 379.0 | 379.0 | 90.0 | False | None | None | False | None | False | 34110.0 | 0 | 4044626 | 156944 | None | CVL170 | Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet.
Long point above 6Mtr upto 10Mtr from tapping point to out let via switch box. | No | 555.0 | 555.0 | 90.0 | False | None | None | False | None | False | 49950.0 | 0 | 4044627 | 156944 | None | CVL171 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 1.5 mm2 | m | 26.0 | 26.0 | 850.0 | False | None | None | False | None | False | 22100.0 | 0 | 4044628 | 156944 | None | CVL172 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments. 2.5 mm2 | m | 42.0 | 42.0 | 3100.0 | False | None | None | False | None | False | 130200.0 | 0 | 4044629 | 156944 | None | CVL173 | Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS-694:confirming to latest amendments.
4 mm 2 | m | 63.0 | 63.0 | 2100.0 | False | None | None | False | None | False | 132300.0 | 0 | 4044630 | 156944 | None | CVL174 | Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/ Stone/ C.C wall. 1-2 way | No | 138.0 | 138.0 | 45.0 | False | None | None | False | None | False | 6210.0 | 0 | 4044631 | 156944 | None | CVL175 | Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/ Stone/ C.C wall. 3 way | No | 159.0 | 159.0 | 30.0 | False | None | None | False | None | False | 4770.0 | 0 | 4044632 | 156944 | None | CVL176 | Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/ Stone/ C.C wall. 4-5 way | No | 177.0 | 177.0 | 30.0 | False | None | None | False | None | False | 5310.0 | 0 | 4044633 | 156944 | None | CVL177 | Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone / C.C wall. 6Way. | No | 220.0 | 220.0 | 25.0 | False | None | None | False | None | False | 5500.0 | 0 | 4044634 | 156944 | None | CVL178 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 1 to 2 Module | No | 137.0 | 137.0 | 45.0 | False | None | None | False | None | False | 6165.0 | 0 | 4044635 | 156944 | None | CVL179 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 3 Module | No | 161.0 | 161.0 | 30.0 | False | None | None | False | None | False | 4830.0 | 0 | 4044636 | 156944 | None | CVL180 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 4 Module | No | 175.0 | 175.0 | 30.0 | False | None | None | False | None | False | 5250.0 | 0 | 4044637 | 156944 | None | CVL181 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 6 Module | No | 234.0 | 234.0 | 25.0 | False | None | None | False | None | False | 5850.0 | 0 | 4044638 | 156944 | None | CVL182 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A One Way Switch | No | 102.0 | 102.0 | 115.0 | False | None | None | False | None | False | 11730.0 | 0 | 4044639 | 156944 | None | CVL183 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A Two Way Switch | No | 166.0 | 166.0 | 45.0 | False | None | None | False | None | False | 7470.0 | 0 | 4044640 | 156944 | None | CVL184 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.6A Three Way socket | No | 171.0 | 171.0 | 35.0 | False | None | None | False | None | False | 5985.0 | 0 | 4044641 | 156944 | None | CVL185 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293.Stepped Fan Regulator Two Module | No | 357.0 | 357.0 | 10.0 | False | None | None | False | None | False | 3570.0 | 0 | 4044642 | 156944 | None | CVL186 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 1293. 32A DP Switch. | No | 326.0 | 326.0 | 25.0 | False | None | None | False | None | False | 8150.0 | 0 | 4044643 | 156944 | None | CVL187 | Supplying and fixing of modular switch & connected accessories on existing modular switch plate as per IS 3854 and IS 12933 6/16A Universal Socket. | No | 236.0 | 236.0 | 25.0 | False | None | None | False | None | False | 5900.0 | 0 | 4044644 | 156944 | None | CVL188 | Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws,bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuit in Thermal Magnetic Release. Micro processor release shall have Earth Fault as per IS-13947. (Icu=100% lcs). In 4P MCCB, all Poles should have protection for Short-Cicrcuit/Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open). Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism.FOUR Pole.100 A 25 kA | No | 8487.0 | 8487.0 | 6.0 | False | None | None | False | None | False | 50922.0 | 0 | 4044645 | 156944 | None | CVL189 | Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 6-32 A SP | No | 415.0 | 415.0 | 11.0 | False | None | None | False | None | False | 4565.0 | 0 | 4044646 | 156944 | None | CVL190 | Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 50-63 A SP | No | 811.0 | 811.0 | 11.0 | False | None | None | False | None | False | 8921.0 | 0 | 4044647 | 156944 | None | CVL191 | Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898. 6-32 A TPN | No | 1717.0 | 1717.0 | 6.0 | False | None | None | False | None | False | 10302.0 | 0 | 4044648 | 156944 | None | CVL192 | Supplying, fixing and wiring Earth Leakage Miniature Circuit Breaker (ELMCB) 240/450V upto 300mA sensitivity on existing wood/panel board.16-25 A 2 pole | No | 4277.0 | 4277.0 | 6.0 | False | None | None | False | None | False | 25662.0 | 0 | 4044649 | 156944 | None | CVL193 | Supplying, fixing and wiring earth leakage relay with corebalanced current transformer suitable for single phase 50 Hz AC with latest microcontroller based, digital readout of percentage leakage current, programmable delay/auto/ manual reset facility suitable to mount on DIN rail/ flush mounting on panel board. | No | 9255.0 | 9255.0 | 2.0 | False | None | None | False | None | False | 18510.0 | 0 | 4044650 | 156944 | None | CVL194 | Supplying, fixing and wiring 3 Phase Digital Ammeter / Voltmeter | No | 1425.0 | 1425.0 | 2.0 | False | None | None | False | None | False | 2850.0 | 0 | 4044651 | 156944 | None | CVL195 | Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 230/440VAC. 50 Hz 12/24V D.C. | No | 515.0 | 515.0 | 2.0 | False | None | None | False | None | False | 1030.0 | 0 | 4044652 | 156944 | None | CVL196 | Supplying exhaust fan of 1440 RPM of 300 mm (12") size with bracket blades complete for light duty suitable to operate on 230V 50Hz, AC Supply. | No | 1492.0 | 1492.0 | 5.0 | False | None | None | False | None | False | 7460.0 | 0 | 4044653 | 156944 | None | CVL197 | Supplying of 1440rpm heavy duty exhaust fan with bracket blades suitable to operate on 230V 50Hz, AC Supply complete.15" Sweep (450 mm) | No | 4446.0 | 4446.0 | 5.0 | False | None | None | False | None | False | 22230.0 | 0 | 4044654 | 156944 | None | CVL198 | Supplying capacitor type ceiling fan complete with down rod blades, shackle, canopies etc, for operation on 230 V, 50 cycles. Single phase AC supply conforming to ISS-374- 1979 and with double ball bearing system.48" Sweep (1200 mm) Regular model | No | 2984.0 | 2984.0 | 5.0 | False | None | None | False | None | False | 14920.0 | 0 | 4044655 | 156944 | None | CVL199 | Supplying wall mounting fan suitable to operate at singlephase 230v AC. supply.
400 mm Sweep | No | 3212.0 | 3212.0 | 5.0 | False | None | None | False | None | False | 16060.0 | 0 | 4044656 | 156944 | None | CVL200 | Supplying of .. TR Invertor type split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 V with hermetically sealed inverter compressor with air cooled condenser, latest R410A / R-32 refrigerant fan motor, start & run capacitors, relay & over load protector internal unit, with one indoor & one outdoor unit The condenser unit will be placed outside the room avoid noise including standard length of suitable size copper tubing covered with nitrile rubber insulation tube. suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote unit.5 star.
2 Ton capacity | No | 67399.0 | 67399.0 | 21.0 | False | None | None | False | None | False | 1415379.0 | 0 | 4044657 | 156944 | None | CVL201 | Installation charges for split type air conditioner with allied works for one indoor and one outdoor unit is to be mounted on suitable Angle Iron support upto 3.0 Ton split/cassette type A/C. | No | 3175.0 | 3175.0 | 21.0 | False | None | None | False | None | False | 66675.0 | 0 | 4044658 | 156944 | None | CVL202 | Supplying and installation of insulated refrigerant copper tubing of 5/8" and 3/8" with polythene foam insulation 3 core 80 stand copper wiring between indoor and outdoor unit Leak testing oil and gas charging for additional piping length of tube. Split | m | 1549.0 | 1549.0 | 80.0 | False | None | None | False | None | False | 123920.0 | 0 | 4044659 | 156944 | None | CVL203 | Extra for Fabrication supply and fixing of Stand fabricated using slotted angle /L angle of size 6mm x 50mm for mounting out door/indoor A.C. unit/ Batteries. | No | 4807.0 | 4807.0 | 21.0 | False | None | None | False | None | False | 100947.0 | 0 | 4044660 | 156944 | None | CVL204 | Supplying of .....feet -PVC Batten with integrated LED tube ....W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI greater than 80. Power Input: 220-240V@ 50/60Hz & Power factor greater than0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition.
LED light fitting 1 x 4' - 20/22 W | No | 690.0 | 690.0 | 25.0 | False | None | None | False | None | False | 17250.0 | 0 | 4044661 | 156944 | None | CVL205 | Supplying of recess mounting non integral type ........ LED w luminaire comprising of pressure decast/extruded aluminium housing, with spring loaded false ceiling clA, Power LEDs with CCT 6500 degree K, CRIgreater than 70%. efficacy greater than 100 lumen per W, 120degree beam spread, lifegreater than 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level LEDs are driven by HF electronic driver integrated in a separate control gear assembly., with PF greater than 0.95, power loss shouldlesser than 5% of lamp Wage., short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition.
LED modular down light 1'x1' / 18W | No | 3138.0 | 3138.0 | 25.0 | False | None | None | False | None | False | 78450.0 | 0 | 4044662 | 156944 | None | CVL206 | Supplying of recess mounting non integral type ........ LED w luminaire comprising of pressure decast/extruded aluminium housing, with spring loaded false ceiling clA, Power LEDs with CCT 6500 degree K, CRIgreater than 70%. efficacy greater than 100 lumen per W, 120degree beam spread, lifegreater than 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level LEDs are driven by HF electronic driver integrated in a separate control gear assembly., with PF greater than 0.95, power loss shouldlesser than 5% of lamp Wage., short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition.
LED modular down light 2'x2' / 36W W | No | 4553.0 | 4553.0 | 70.0 | False | None | None | False | None | False | 318710.0 | 0 | 4044663 | 156944 | None | CVL207 | Supplying of recess mounting non integral type ........ LED w luminaire comprising of pressure decast/extruded aluminium housing, with spring loaded false ceiling clA, Power LEDs with CCT 6500 degree K, CRIgreater than 70%. efficacy greater than 100 lumen per W, 120degree beam spread, lifegreater than 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level LEDs are driven by HF electronic driver integrated in a separate control gear assembly., with PF greater than 0.95, power loss shouldlesser than 5% of lamp Wage., short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition.
LED modular down light 2'x2' / 40-42 W | No | 4861.0 | 4861.0 | 50.0 | False | None | None | False | None | False | 243050.0 | 0 | 4044664 | 156944 | None | CVL208 | INDUSTRIAL HIGHBAY LUMINAIRE ( INTEGRAL TYPE) Industrial medium/high bay luminaire with integral type Control gear, copper wound ballast, visor glass assembly and including supply of lamps. 100W, 240V, LED Highbay luminare | No | 2500.0 | 2500.0 | 25.0 | False | None | None | False | None | False | 62500.0 | 0 | 4044665 | 156944 | None | CVL209 | Supply of LED floodlight luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate/clear glass material, delivering superior light output Rated life Burning Hrs 50000 hr @ Lumen Maintenance of 70%, CCT greater than 5500K, IP 66 optical and electrical compartment & impact resistance of complete luminaire greater than IK08. Power Factor greater than0.9 with mains, Surge Protection- Min 5KV along with Over voltage/ Overload, short circuit/ miss-wiring protection. Compatible for pole mauling with outer dia of 40mm to 50mm. Universal Voltage driver to operate wide voltage range from 100 V to 270V 50/60Hz application. Compliance to IS 10322/ IEC 60598, LM 79 & LM 80 Adherence with RoHS. UL approved MCPCB. Top access street light with single screw to ensure ease of maintenance at the sight site location with minimized minimal tools. LED Light fixture with ....... W System Power consumption. LED Efficiencygreater than 1301m/w, nominal CRI greater than75. Luminaire manufacturer should have in- house facility accredited by NABL / CPRI & any Government certified agency & Design & Development facility certified by ISO 9001:2008. Housing with supplier word mark / name shall be Engraved /Embossing on the die cast housing / Body part Warranty of 2 Years against any manufacturing defect working under standard electrical conditions as mentioned above should be given by LED manufacturer & Cree/Nichia/ Lumileds/Osram make LED Source. LED Flood light 150W. | No | 12490.0 | 12490.0 | 5.0 | False | None | None | False | None | False | 62450.0 | 0 | 4044666 | 156944 | None | CVL210 | Supplying and fixing of LED Bulkhead of 10W with IP65 protection and IK08 impact resistance suitable for surface and wall mounting applications. | No | 842.0 | 842.0 | 27.0 | False | None | None | False | None | False | 22734.0 | 0 | 4044667 | 156944 | None | CVL211 | Supply and fixing Battery operated portable fluoresent lamps | No | 1000.0 | 1000.0 | 12.0 | False | None | None | False | None | False | 12000.0 | 0 | 4044668 | 156944 | None | CVL212 | Fixing all types and all capacities of fluorescent /false ceiling / spot light / CFL / LED fittings indoor on the wall/ ceiling / rafters / girders using 23/0.0076" twin twisted PVC insulated wires, required Nos of round blocks and clA.On wall/ ceiling / Rafter / Girders. | No | 122.0 | 122.0 | 235.0 | False | None | None | False | None | False | 28670.0 | 0 | 4044669 | 156944 | None | CVL213 | Fixing a ceiling / Wall mounting fan of all capacities and all types to the existing 'S'' hook with fan regulator to the existing board together with supplying and fixing 5 A. ceiling rose, necessary length of 23 / 0.0076 inch PVC insulated twin twisted copper wire and wiring.. | No | 171.0 | 171.0 | 10.0 | False | None | None | False | None | False | 1710.0 | 0 | 4044670 | 156944 | None | CVL214 | Extra length of GI pipe of class B 19mm dia for down rod. | m | 197.0 | 197.0 | 30.0 | False | None | None | False | None | False | 5910.0 | 0 | 4044671 | 156944 | None | CVL215 | Fixing one exhaust fan after making a suitable notch in the wall and finishing with cement mortar and colouring to match the existing wall or brackets, with bolts and nuts and a 5 A, ceiling rose with sufficient length of 23 / 0.0076 inch PVC insulated twin core wire of approved make with wire mesh and wooden frame.. | No | 707.0 | 707.0 | 10.0 | False | None | None | False | None | False | 7070.0 | 0 | 4044672 | 156944 | None | CVL216 | Supplying, erecting, testing and commissioning of voltage stabilizer suitable for 170 to 270 v input and load variation from no load to full load, with over load protection, spike suppression, operating at 00 C to 400 C. Range etc., complete.
5kVA Capacity | No | 9666.0 | 9666.0 | 2.0 | False | None | None | False | None | False | 19332.0 | 0 | 4044673 | 156944 | None | CVL217 | Earthing : Supplying and fixing and wiring earth electrode for grounding circuits IC cutouts and other equipments on the meter board in the pit. The pits should be filled up with equal proportion of salt and charcoal 150mm around the pipe to complete depth. The connection from the pipe to the conduits etc. is to established through GI wire of sizes as per clause 7.3.3 of IS 732 using 12mm bolts, nuts, washers and check nuts, the pipe shall have 16 through holes of 12mm dia. | Job | 3510.0 | 3510.0 | 7.0 | False | None | None | False | None | False | 24570.0 | 0 | 4044674 | 156944 | None | CVL218 | Refilling available earth around trenches/pipelines, cables in layers not exceeding 20 cms in depth, compacting each deposited layer by ramming after watering with a lead upto 50 m, and lift upto 1.5 m. Including cost of all labour complete as per specifications | Cum | 160.0 | 160.0 | 2138.0 | False | None | None | False | None | False | 342080.0 | 0 | 4044675 | 156944 | None | CVL219 | Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm including the cost of materials, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer in-charge of works as per the standard procedure. | Sqm | 177.3 | 177.3 | 3450.0 | False | None | None | False | None | False | 611685.0 | 0 | 4044676 | 156944 | None | CVL220 | Earth work excavation for pipeline trenches in all kinds of soils by mechanical means as per drawing and technical specifications, including setting out, construction of shoring, strutting, barricading, caution lights, bracing, using sight rails & bonding rods at every 100 mm wherever necessary as directed, removal of stumps and other deleterious matter, dressing of sides and levelling the bottom of trench to the extent required , utilising the available excavated earth locally for the work etc., and all other appurtenances complete in the following strata.
All kind of soil Depth upto 1.50 m | Cum | 262.0 | 262.0 | 10213.98 | False | None | None | False | None | False | 2676062.76 | 0 | 4044677 | 156944 | None | CVL221 | Earth work excavation for pipeline trenches by mechanical means as per drawing and technical specifications, including setting out, construction of shoring, strutting, barricading, caution lights, bracing, using sight rails & bonding rods at every 100 mm wherever necessary as directed, removal of stumps and other deleterious matter, dressing of sides and levelling the bottom of trench to the extent required , utilising the available excavated earth locally for the work and all other appurtenances to complete in the following strata.
Ordinary/soft rock (without requiring blasting) Depth upto 1.50 m | Cum | 454.0 | 454.0 | 3647.78 | False | None | None | False | None | False | 1656092.12 | 0 | 4044678 | 156944 | None | CVL222 | Earth work excavation for pipeline trenches by mechanical means as per drawing and technical specification, including setting out, construction of shoring, strutting, cost of blasting materials, barricading, caution lights, bracing, using sight rails & bonding rods at every 100 mm wherever necessary as directed, removal of stumps and other deleterious matter, dressing of sides and levelling the bottom of trench to the extent required , utilising the available excavated earth locally for the work and all other appurtenances to complete in the following strata.
Hard rock (blasting prohibited) Depth upto 1.50 m | Cum | 1014.0 | 1014.0 | 729.5799 | False | None | None | False | None | False | 739794.0186 | 0 | 4044679 | 156944 | None | CVL223 | Dismantling of Flexible pavements and disposal of dismantled materials and stacking serviceable and unserviceable materials separately
By Mechanical Mean Bituminous courses | Cum | 322.0 | 322.0 | 3487.0 | False | None | None | False | None | False | 1122814.0 | 0 | 4044680 | 156944 | None | CVL224 | Dismantling of Flexible pavements and disposal of dismantled materials and stacking serviceable and unserviceable materials separately
By Mechanical Mean Granular course | Cum | 53.0 | 53.0 | 3336.5 | False | None | None | False | None | False | 176834.5 | 0 | 4044681 | 156944 | None | CVL225 | Dismantling of cement concrete pavement by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 m3 in volume and stock piling at designated locations and disposal of dismantled materials and stacking serviceable and unserviceable
materials separately | Cum | 563.0 | 563.0 | 80.0 | False | None | None | False | None | False | 45040.0 | 0 | 4044682 | 156944 | None | CVL226 | Providing M-Sand : Supplying and filling in plinth, foundations / UG cable work with approved M-sand including watering, ramming, consolidating and dressing. The rate includes the cost of material, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer- in-charge of works as per the standard procedure. | Cum | 1965.0 | 1965.0 | 14591.62 | False | None | None | False | None | False | 28672533.3 | 0 | 4044683 | 156944 | None | CVL227 | Supplying and Providing pre cast RCC Protection Covers using M20 grade Concrete, steel of approved size/shape (as per the approved drawings) to be laid in UG cable works. The rate includes the cost of material, labour charges, loading, unloading, handling, transportation charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer-in-charge of works as per the standard procedure. | Sqm | 1298.0 | 1298.0 | 5994.5 | False | None | None | False | None | False | 7780861.0 | 0 | 4044684 | 156944 | None | CVL228 | Refilling available earth around trenches/pipelines, cables in layers not exceeding 20 cms in depth, compacting each deposited layer by ramming after watering with a lead upto 50 m, and lift upto 1.5 m. Including cost of all labour complete as per specifications | Cum | 160.0 | 160.0 | 200.0 | False | None | None | False | None | False | 32000.0 | 0 | 4044685 | 156944 | None | CVL229 | Removal of Unserviceable Soil with Disposal upto a suitable distance as directed by the Engineer incharge of work | Cum | 85.0 | 85.0 | 14591.62 | False | None | None | False | None | False | 1240287.7 | 0 | 4044686 | 156944 | None | CVL230 | Supplying and Providing Pre cast Cable Route/ Joint marker using M15 grade Concrete, MS rods of approved size/shape (as per the approved drawings) to be laid in UG cable works. The rate includes the cost of material, labour charges, loading, unloading, handling, transportation charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer-in-charge of works as per the standard procedure. | No | 342.0 | 342.0 | 264.0 | False | None | None | False | None | False | 90288.0 | 0 | 4044687 | 156944 | None | CVL231 | Providing and laying of warning tape / Caution tape / detector tape for HDPE pipes of 200 mm wide, 300 micron thick, blue in colour confoming to relevant ISS with latest amendments with appurtenances., complete. | m | 8.0 | 8.0 | 16086.0 | False | None | None | False | None | False | 128688.0 | 0 | 4044688 | 156944 | None | CVL232 | Supplying and construction of RCC M20 Cable Joint Bays to accommodate jointing of UG Cable as per specifications, drawings. The rate includes the cost of material, labour charges, curing, form work, centering& scaffolding, loading, unloading, handling, transportation charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer-in-charge of works as per the standard procedure.
For 66kV UGC | No | 199742.0 | 199742.0 | 13.0 | False | None | None | False | None | False | 2596646.0 | 0 | 4044689 | 156944 | None | CVL233 | Supplying and construction of RCC M20 Cable Joint Bays to accommodate jointing of UG Cable as per specifications, drawings. The rate includes the cost of material, labour charges, curing, form work, centering& scaffolding, loading, unloading, handling, transportation charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer-in-charge of works as per the standard procedure.
For 220kV UGC | No | 389954.42 | 389954.42 | 18.0 | False | None | None | False | None | False | 7019179.56 | 0 | 4044690 | 156944 | None | CVL234 | Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, and all the other appurtenances required to complete the work as per technical specifications.
Mix 1:2:4 Using 20 mm nominal size graded crushed coarse aggregates | Cum | 6243.0 | 6243.0 | 590.0 | False | None | None | False | None | False | 3683370.0 | 0 | 4044691 | 156944 | None | CVL235 | HDD method for laying of 110 kV and 66 kV UG Cables: Installation of 3 rows of HDPE pipes PE 80 PN6 of 160 mm dia using Horizontal directional drilling technique (HDD method) including preparing and setting up the plant and equipment, preparing and installation of new pipe work materials and commissioning system or making the system ready for commissioning by HDD operation including all excavation, shoring/strutting etc., drilling, stringing, ramming and pulling back the new work on the design bore path alignment, proper disposal of drilling fluid and restoration of site after completion etc., for HDD technique suiting Indian conditions in all types of soil. | Ckt Mtrs | 8384.0 | 8384.0 | 1000.0 | False | None | None | False | None | False | 8384000.0 | 0 | 4044692 | 156944 | None | CVL236 | HDD method for 220 kV DC UG Cable work: Installation of 3 rows of HDPE pipes PE 80 PN6 of 250 mm dia using Horizontal directional drilling technique (HDD method) including preparing and setting up the plant and equipment,preparing new pipe work materials, installing new pipe work and commissioning system or making the system ready for commissioning by HDD operation including excavation, shoring/ strutting etc., drilling, stringing, ramming and pulling back the new work on the design bore path alignment, proper disposal of drilling fluid and restoration of site after completion etc., for HDD technique suiting Indian conditions in all types of soil | Ckt Mtrs | 16889.0 | 16889.0 | 800.0 | False | None | None | False | None | False | 13511200.0 | 0 | 4044693 | 156944 | None | CVL237 | Providing, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with latest ammendments and conveying to work site including loading and unloading at both destinations and rolling and lowering into trenches, laying true to line and jointing of pipes and specials with electrofusion welding, giving hydraulic test as per relevant ISS with all lead and lifts including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excation, testing and commissioning. The rate is exclusive of required specials and fittings wherever necessary like saddle Tee, stub ends, flanged sets, bedns, reducers etc. complete (Contractor will make his own arrangements for procuring water for testing) etc. complete. NOTE: Upto 110mm dia Coil shall be used.
HDPE Grade PE80-PN6.0,250mm dia | m | 2170.0 | 2170.0 | 3492.0 | False | None | None | False | None | False | 7577640.0 | 0 | 4044694 | 156944 | None | CVL238 | Providing, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with latest ammendments and conveying to work site including loading and unloading at both destinations and rolling and lowering into trenches, laying true to line and jointing of pipes and specials with electrofusion welding, giving hydraulic test as per relevant ISS with all lead and lifts including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excation, testing and commissioning. The rate is exclusive of required specials and fittings wherever necessary like saddle Tee, stub ends, flanged sets, bedns, reducers etc. complete (Contractor will make his own arrangements for procuring water for testing) etc. complete. NOTE: Upto 110mm dia Coil shall be used.
HDPE Grade PE80-PN6.0,160mm dia | m | 959.0 | 959.0 | 2916.0 | False | None | None | False | None | False | 2796444.0 | 0 | 4044695 | 156944 | None | CVL239 | Construction of Granular Sub-Base of grading VI material as per design mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401 | Cum | 2533.0 | 2533.0 | 3039.91 | False | None | None | False | None | False | 7700092.03 | 0 | 4044696 | 156944 | None | CVL240 | Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying inuniform layers with paver/grader in sub-base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density | Cum | 2559.0 | 2559.0 | 3304.25 | False | None | None | False | None | False | 8455575.75 | 0 | 4044697 | 156944 | None | CVL241 | Prime Coat over WMM/WBM: Providing and applying primer coat with SS1 grade Bitumen Emulsion on prepared surface of granular base including cleaning of road surface and spraying primer at the rate of 0.70 kg per m2 using mechanical means | Sqm | 41.0 | 41.0 | 13217.0 | False | None | None | False | None | False | 541897.0 | 0 | 4044698 | 156944 | None | CVL242 | Dense Graded Bituminous Macadam Grading - II for traffic less than 20 MSA
Providing and laying Dense Graded Bituminous Macadam with 120 TPH capacity HMP batch type using crushed aggregates of specified grading, premixed with bituminous binder VG-30, @ 4.5 per cent by weight of total mix and filler, transporting the hot mix to work site, laying with mechanical paver finisher to the required grade, level and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per MoRTH specification clause No. 505 complete in all respects. | Cum | 9526.0 | 9526.0 | 991.28 | False | None | None | False | None | False | 9442933.28 | 0 | 4044699 | 156944 | None | CVL243 | Tack coat on Bituminous surface:Providing and applying tack coat with VG-10 Bitumen using pressure distributor at the rate of 0.20 kg/m2 on the prepared bituminous surface cleaned with mechanical broom | Sqm | 12.0 | 12.0 | 13217.0 | False | None | None | False | None | False | 158604.0 | 0 | 4044700 | 156944 | None | CVL244 | Bituminous Concrete Grading II for traffic less than20 MSA
Providing and laying Bituminous Concrete with 100 TP capacity hot mix plant batch type using crushed aggregates of specified grading, premixed with bituminous binder VG-30, @ 5.4 per cent of mix and filler, transporting the hot mix to work site, laying with mechanical paver finisher to the required grade, level and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per MORTH specification clause No. 507 complete in all respects | Cum | 10865.0 | 10865.0 | 528.68 | False | None | None | False | None | False | 5744108.2 | 0 | 4044701 | 156944 | None | CVL245 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights,including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work.
In ordinary/soft rock without blasting upto 1.5 m depth. | Cum | 363.0 | 363.0 | 46.36 | False | None | None | False | None | False | 16828.68 | 0 | 4044702 | 156944 | None | CVL246 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights,including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work.
In ordinary/soft rock without blasting Depth exceeding 1.5 m but not exceeding 3 m depth | Cum | 425.0 | 425.0 | 69.52 | False | None | None | False | None | False | 29546.0 | 0 | 4044703 | 156944 | None | CVL247 | Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to complete the work as per technical specifications.
Mix 1:3:6 Using 20 mm nominal size graded crushed coarse aggregate | Cum | 6217.0 | 6217.0 | 3.43 | False | None | None | False | None | False | 21324.31 | 0 |
|
|
---|