4094913 | 159478 | None | code01 | Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work -Do in ordinary / soft rock without blasting upto 1.5m depth.
a) Combined footing and b) Sump excavation | Cum | 102.0 | 102.0 | 715.58 | False | None | None | False | None | False | 72989.16 | 0 |
4094914 | 159478 | None | code02 | Earth work excavation for FOUNDATION by Mechanical means depth upto 1.50m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including cost of explosives, dressing of excavated surfaces, disposing off or levelling the excavated stuff or sorting & stacking the selected stuff for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, blasting materials, tools, usage of Machinery & all other appurtenaces required to complete the work In Hard Rock (Depth exceeding 1.5 m, but not exceeding 3 m) | Cum | 425.0 | 425.0 | 266.24 | False | None | None | False | None | False | 113152.0 | 0 |
4094915 | 159478 | None | code03 | Providing and laying in position plain cement concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse ggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machineries, curing, and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork shall be paid separately) Mix 1:4:8(M5) Using 40 mm nominal size graded crushed coarse aggregates | Cum | 5664.0 | 5664.0 | 82.95 | False | None | None | False | None | False | 469828.8 | 0 |
4094916 | 159478 | None | code04 | Providing and laying in position Reinforced cement concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials,quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork to be paid eparately) M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates | Cum | 6630.0 | 6630.0 | 159.7415 | False | None | None | False | None | False | 1059086.145 | 0 |
4094917 | 159478 | None | code4.1 | Form work for centering (Foundation upto Plinth) | Cum | 198.9 | 198.9 | 159.7415 | False | None | None | False | None | False | 31772.58435 | 0 |
4094918 | 159478 | None | code4.2 | Stairs Portion: Stilt to Ground floor | Cum | 6630.0 | 6630.0 | 2.234 | False | None | None | False | None | False | 14811.42 | 0 |
4094919 | 159478 | None | code4.3 | Stairs Portion:Ground to first floor | Cum | 6696.3 | 6696.3 | 2.234 | False | None | None | False | None | False | 14959.5342 | 0 |
4094920 | 159478 | None | code4.4 | Stairs Portion:First to second floor | Cum | 6762.6 | 6762.6 | 2.234 | False | None | None | False | None | False | 15107.6484 | 0 |
4094921 | 159478 | None | code4.5 | Stairs Portion:Second to terrace | Cum | 6828.9 | 6828.9 | 2.234 | False | None | None | False | None | False | 15255.7626 | 0 |
4094922 | 159478 | None | code4.6 | Cills & Lintels: Ground floor | Cum | 6630.0 | 6630.0 | 5.4375 | False | None | None | False | None | False | 36050.625 | 0 |
4094923 | 159478 | None | code4.7 | Cills & Lintels:First Floor | Cum | 6696.3 | 6696.3 | 5.4375 | False | None | None | False | None | False | 36411.13125 | 0 |
4094924 | 159478 | None | code4.8 | Cills & Lintels:Second Floor | Cum | 6762.6 | 6762.6 | 5.4375 | False | None | None | False | None | False | 36771.6375 | 0 |
4094925 | 159478 | None | code4.9 | Form work for centering (Beams, Lintels) | Cum | 3978.0 | 3978.0 | 25.58 | False | None | None | False | None | False | 101757.24 | 0 |
4094926 | 159478 | None | code5 | Providing and laying in position Reinforced cement concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, wellcompacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing and all the other appurtenances required to complete the work as per technical specifications. (The cost of steel reinforcement & formwork to be paid separately) M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates | Cum | 6336.0 | 6336.0 | 27.09 | False | None | None | False | None | False | 171642.24 | 0 |
4094927 | 159478 | None | code5.1 | First Floor | Cum | 6399.36 | 6399.36 | 4.3739 | False | None | None | False | None | False | 27990.160704 | 0 |
4094928 | 159478 | None | code5.2 | Second Floor | Cum | 6462.72 | 6462.72 | 4.3739 | False | None | None | False | None | False | 28267.291008 | 0 |
4094929 | 159478 | None | code5.3 | Head Room | Cum | 6526.08 | 6526.08 | 2.916 | False | None | None | False | None | False | 19030.04928 | 0 |
4094930 | 159478 | None | code5.4 | Form work for centering (Columns) | Cum | 4435.2 | 4435.2 | 52.25 | False | None | None | False | None | False | 231739.2 | 0 |
4094931 | 159478 | None | code6 | Providing and laying in Reinforced cement concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necesary, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing and all other appurtenances required to complete the work as per technical specifications. (The cost of steel einforcement & formwork to be paid separately) M20 Design Mix Using 20 mm nominal size graded crushed coarse aggregates Stilt Floor | Cum | 6323.0 | 6323.0 | 59.98 | False | None | None | False | None | False | 379253.54 | 0 |
4094932 | 159478 | None | code6.1 | Ground Floor | Cum | 6386.23 | 6386.23 | 59.98 | False | None | None | False | None | False | 383046.0754 | 0 |
4094933 | 159478 | None | code6.2 | First Floor | Cum | 6449.46 | 6449.46 | 59.98 | False | None | None | False | None | False | 386838.6108 | 0 |
4094934 | 159478 | None | code6.3 | Second Floor | Cum | 6512.69 | 6512.69 | 59.98 | False | None | None | False | None | False | 390631.1462 | 0 |
4094935 | 159478 | None | code6.4 | Terrace HR Slab | Cum | 6575.92 | 6575.92 | 7.41 | False | None | None | False | None | False | 48727.5672 | 0 |
4094936 | 159478 | None | code6.5 | Form work for centering (Plinth Beams, Roof Beam and Roof Slab) | Cum | 3161.5 | 3161.5 | 259.42 | False | None | None | False | None | False | 820156.33 | 0 |
4094937 | 159478 | None | code7 | Providing Size Stone masonry with hard stone in foundation & plinth with Cement mortar 1:6 (1 cement : 6 coarse sand) SSM Foundation | Cum | 6389.0 | 6389.0 | 19.051 | False | None | None | False | None | False | 121716.839 | 0 |
4094938 | 159478 | None | code8 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m | Cum | 266.0 | 266.0 | 749.59 | False | None | None | False | None | False | 199390.94 | 0 |
4094939 | 159478 | None | code9 | Providing and constructing load bearing wall with Solid Concrete blocks of size 400x200x200mm having block density more than 1800kg/m3 and minimum compressive strength of 4.00 N/mm2 conforming to IS 2185 (Part - I) - 2005 and constructed with CM 1:4 as per IS 2572:2005 including cost of all materials, labour, scaffolding and curing, usage charges of machinery etc complete as per specifications-GF | Sqm | 1310.0 | 1310.0 | 352.44 | False | None | None | False | None | False | 461696.4 | 0 |
4094940 | 159478 | None | code9.1 | First Floor | Sqm | 1323.1 | 1323.1 | 352.44 | False | None | None | False | None | False | 466313.364 | 0 |
4094941 | 159478 | None | code9.2 | Second Floor | Sqm | 1336.2 | 1336.2 | 352.44 | False | None | None | False | None | False | 470930.328 | 0 |
4094942 | 159478 | None | code9.3 | Head Room | Sqm | 1349.3 | 1349.3 | 192.71 | False | None | None | False | None | False | 260023.603 | 0 |
4094943 | 159478 | None | code10 | Providing and constructing load bearing wall with Solid Concrete blocks of size 400x100x200mm having block density more than 1800kg/m3 and minimum compressive strength of 4.00 N/mm2 conforming to IS 2185 (Part - I) - 2005 and constructed with CM 1:4 as per IS 2572:2005 including cost of all materials, labour, scaffolding and curing, usage charges of machinery etc complete as per specifications- GF | Sqm | 1104.0 | 1104.0 | 167.39 | False | None | None | False | None | False | 184798.56 | 0 |
4094944 | 159478 | None | code10.1 | First Floor | Sqm | 1126.08 | 1126.08 | 167.39 | False | None | None | False | None | False | 188494.5312 | 0 |
4094945 | 159478 | None | code10.2 | Second Floor | Sqm | 1137.12 | 1137.12 | 167.39 | False | None | None | False | None | False | 190342.5168 | 0 |
4094946 | 159478 | None | code11 | Providing and laying in position reinforced cement concrete of design Mix M20 with OPC @ 24kgs, with 12mm and down size graded granite metal coarse aggregates @0.05175m3 and fine aggregtes @ 0.0345m3, with superplastisiser @0.225lts, machine mixed, well compacted for plain chajja of 7.5 cms. average thickness, upto ground floor level, including cost of all materials, labour, HOM finishing, curing, complete but excluding cost of reinforcement as per specifications - GF | Sqm | 367.0 | 367.0 | 11.04 | False | None | None | False | None | False | 4051.68 | 0 |
4094947 | 159478 | None | code11.1 | First Floor | Sqm | 372.0 | 372.0 | 11.04 | False | None | None | False | None | False | 4106.88 | 0 |
4094948 | 159478 | None | code11.2 | Second Floor | Sqm | 377.0 | 377.0 | 11.04 | False | None | None | False | None | False | 4162.08 | 0 |
4094949 | 159478 | None | code11.3 | Form work for centering (Chejjas) | Cum | 165.15 | 165.15 | 7.45 | False | None | None | False | None | False | 1230.3675 | 0 |
4094950 | 159478 | None | code12 | Providing RCC loft (atta) 7.5 cms thick with cement concrete design mix M20 using clean granite or trap jelly of 20 mm and down size with necessary reinforcements at 20 cms centre to centre as per design including form work, centring, curing, etc., complete (exclusive of cost of steel and fabrication charges)-GF | Sqm | 357.0 | 357.0 | 50.76 | False | None | None | False | None | False | 18121.32 | 0 |
4094951 | 159478 | None | code12.1 | Form work for centering (Loft) | Cum | 160.65 | 160.65 | 11.42 | False | None | None | False | None | False | 1834.623 | 0 |
4094952 | 159478 | None | code13 | Providing Honne wood frames of doors, windows, clerestory windows, ventilators and other frames, wrought, framed or assembled including making plaster groves (excluding cost of cement concrete and side clamps), but including cost of materials, labour, usage charges complete as per specifications | Cum | 138074.0 | 138074.0 | 3.6585 | False | None | None | False | None | False | 505143.729 | 0 |
4094953 | 159478 | None | code14 | Providing and fixing in position fully panelled Honne wood shutters for doors with , stiles and rails of 35mm. thick with bottom and lock rails 180mm wide top rail and stiles 100mm wide as per drawing and panels of 25mm thick including cost of materials, labour, usage charges complete as per specifications. (excluding cost of fixtures) - GF | Sqm | 7085.0 | 7085.0 | 69.93 | False | None | None | False | None | False | 495454.05 | 0 |
4094954 | 159478 | None | code15 | Providing & fixing 30mm thick factory made rigid foam Prelam Panelled Door Shutters made from M.S. tube of 19x19mm, 19 gauge for stiles and 15x15mm for top & bottom rails, covered with heat moulded Prelaminated PVC C Channel of 5mm thick sheet & 30x50mm wide to form stiles & 5mm thick & 75mm wide Prelaminated PVC Sheets for top rail, lock rail & bottom rail on either side & 5mm thick, 20mm wide cross PVC sheet as gap insert for top rail & bottom rail, Panelling of 5mm thick PVC sheet Prelaminated on either side fitted in the M.S. frame, Sealed to the stiles & rails with PVC Designer beading on either side & joined together with solvent cement adhesive etc., Complete as per manufacturers specification & direction of Engineer-in-charge fixed to frames with 3 nos of 75mm Aluminium hinges | Sqm | 2366.0 | 2366.0 | 21.42 | False | None | None | False | None | False | 50679.72 | 0 |
4094955 | 159478 | None | code16 | Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete. Fixed to steel windows by welding. Weighing 21Kgs/Sqm-GF | Kgs | 131.0 | 131.0 | 3518.99 | False | None | None | False | None | False | 460987.69 | 0 |
4094956 | 159478 | None | code17 | Providing and fixing stainless steel 304 grade for staircase railings, balconies, ramps, with hand rail, 50mm dia 16 guage hollow pipe welded to vertical hollow 50mm dia pipe of 16 guage, stainless steel vertical pipe spaced at 1.20m regular intervals and 5 Nos of 25mm dia. Stainless steel hollow horizontal pipe are welded to vertical 50mm dia hollow pipe. The entire assembly is fixed to staircase concrete by using expansion bolts by drilling concrete etc., complete including cost of materials, labour, HOM of and electrical charges, etc., complete as per specifications-Stilt- GF | Sqm | 5017.0 | 5017.0 | 58.8 | False | None | None | False | None | False | 294999.6 | 0 |
4094957 | 159478 | None | code17.1 | First Floor | Sqm | 5017.0 | 5017.0 | 58.8 | False | None | None | False | None | False | 294999.6 | 0 |
4094958 | 159478 | None | code17.2 | Second Floor | Sqm | 5017.0 | 5017.0 | 58.8 | False | None | None | False | None | False | 294999.6 | 0 |
4094959 | 159478 | None | code18 | Providing and fixing hand rail of approved size by welding etc. to
steel ladder railing, balcony railing, staircase railing and similar
works, including applying priming coat of approved steel primer. M.S.
tube including cost of materials, labour, usage charges of machinery
complete as per specifications and as per directions of the Engineerin-
Charge | Kgs | 138.0 | 138.0 | 60.0 | False | None | None | False | None | False | 8280.0 | 0 |
4094960 | 159478 | None | code19 | Providing 18 mm cement plaster in two coats under layer 12 mm thick cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) and a top layer 6 mm thick cement plaster with cement mortar 1:3 (1 cement : 3 coarse sand) finished rough with sponge to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labor, curing complete as per specifications and as per directions of Engineer-in-charge-Stilt Staircase | Sqm | 366.0 | 366.0 | 76.94 | False | None | None | False | None | False | 28160.04 | 0 |
4094961 | 159478 | None | code19.1 | Ground Floor | Sqm | 369.66 | 369.66 | 262.96 | False | None | None | False | None | False | 97205.7936 | 0 |
4094962 | 159478 | None | code19.2 | First Floor | Sqm | 373.32 | 373.32 | 262.96 | False | None | None | False | None | False | 98168.2272 | 0 |
4094963 | 159478 | None | code19.3 | Second Floor | Sqm | 376.98 | 376.98 | 262.96 | False | None | None | False | None | False | 99130.6608 | 0 |
4094964 | 159478 | None | code19.4 | Terrace | Sqm | 380.64 | 380.64 | 231.4 | False | None | None | False | None | False | 88080.096 | 0 |
4094965 | 159478 | None | code20 | Providing 15 mm cement plaster on rough side of single or half brick wall finished with a floating coat of neat cement of mix: 1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge-GF | Sqm | 349.0 | 349.0 | 465.43 | False | None | None | False | None | False | 162435.07 | 0 |
4094966 | 159478 | None | code20.1 | First Floor | Sqm | 355.98 | 355.98 | 465.43 | False | None | None | False | None | False | 165683.7714 | 0 |
4094967 | 159478 | None | code20.2 | Second Floor | Sqm | 359.47 | 359.47 | 465.43 | False | None | None | False | None | False | 167308.1221 | 0 |
4094968 | 159478 | None | code21 | Providing 12 mm cement plaster finished with a floating coat of neat cement of mix :1:3 (1 cement: 3 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge-Parking Floor Ceiling | Sqm | 323.0 | 323.0 | 232.3 | False | None | None | False | None | False | 75032.9 | 0 |
4094969 | 159478 | None | code21.1 | Ground Floor | Sqm | 326.23 | 326.23 | 188.67 | False | None | None | False | None | False | 61549.8141 | 0 |
4094970 | 159478 | None | code21.2 | First Floor | Sqm | 329.46 | 329.46 | 188.67 | False | None | None | False | None | False | 62159.2182 | 0 |
4094971 | 159478 | None | code21.3 | Second Floor | Sqm | 332.69 | 332.69 | 188.67 | False | None | None | False | None | False | 62768.6223 | 0 |
4094972 | 159478 | None | code22 | Providing 15 mm cement plaster on rough side of single or half brick wall finished with a floating coat of neat cement of mix 1:3 (1 cement: 3 fine sand) including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge-Stilt-Rough Plastering for Steps | Sqm | 366.0 | 366.0 | 14.39 | False | None | None | False | None | False | 5266.74 | 0 |
4094973 | 159478 | None | code22.1 | GF -Rough Plastering for Toilets | Sqm | 369.66 | 369.66 | 70.32 | False | None | None | False | None | False | 25994.4912 | 0 |
4094974 | 159478 | None | code22.2 | FF-Rough Plastering for Toilets | Sqm | 373.32 | 373.32 | 70.32 | False | None | None | False | None | False | 26251.8624 | 0 |
4094975 | 159478 | None | code22.3 | SF-Rough Plastering for Toilets | Sqm | 376.98 | 376.98 | 70.32 | False | None | None | False | None | False | 26509.2336 | 0 |
4094976 | 159478 | None | code23 | Providing and fixing suitable plaster mesh manufactured out of hot dipped galvanised iron of nominal thickness 0.35mm with a zinc coating of 120gms per m2 width, along route of walls chipped for services, junction between RCC and brick walls including cost of materials, labour for fixing complete as per specifications. (length of mesh only be measured for payment suitable plaster mesh 150mm wide- GF | m | 25.0 | 25.0 | 295.93 | False | None | None | False | None | False | 7398.25 | 0 |
4094977 | 159478 | None | code23.1 | First Floor | m | 25.0 | 25.0 | 295.93 | False | None | None | False | None | False | 7398.25 | 0 |
4094978 | 159478 | None | code23.2 | Second Floor | m | 25.0 | 25.0 | 295.93 | False | None | None | False | None | False | 7398.25 | 0 |
4094979 | 159478 | None | code24 | Extra for providing throating or drip moulding to R.C.C.chajja with plastering (labour charges only ) as per specifications-Chejjas | m | 27.0 | 27.0 | 131.82 | False | None | None | False | None | False | 3559.14 | 0 |
4094980 | 159478 | None | code25 | Forming groove of uniform size in the top layer of plaster as per approved pattern including repair to the edges of panels and finishing the groove complete as per specifications and direction of the Engineer-in-charge: 20 mm to 25 mm wide to required depth | m | 66.0 | 66.0 | 1008.0 | False | None | None | False | None | False | 66528.0 | 0 |
4094981 | 159478 | None | code26 | Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete as per specifications and as per directions of Engineer incharge-Parking floor Ceiling, Inside Plastering and Ceiling Plastering | Sqm | 100.0 | 100.0 | 232.3 | False | None | None | False | None | False | 23230.0 | 0 |
4094982 | 159478 | None | code26.1 | Ground Floor | Sqm | 100.0 | 100.0 | 654.11 | False | None | None | False | None | False | 65411.0 | 0 |
4094983 | 159478 | None | code26.2 | First Floor | Sqm | 100.0 | 100.0 | 654.11 | False | None | None | False | None | False | 65411.0 | 0 |
4094984 | 159478 | None | code26.3 | Second Floor | Sqm | 100.0 | 100.0 | 654.11 | False | None | None | False | None | False | 65411.0 | 0 |
4094985 | 159478 | None | code27 | Providing and laying Cement concrete flooring 40 mm thick with 20mm nominal size stone aggregate using 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a floating coat of neat cement, including cement slurry complete | Sqm | 451.0 | 451.0 | 300.4 | False | None | None | False | None | False | 135480.4 | 0 |
4094986 | 159478 | None | code28 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3 kg/ m2 including grouting the joints with white cement and matching pigments etc., complete- GF | Sqm | 1145.0 | 1145.0 | 124.42 | False | None | None | False | None | False | 142460.9 | 0 |
4094987 | 159478 | None | code28.1 | First Floor | Sqm | 1145.0 | 1145.0 | 124.42 | False | None | None | False | None | False | 142460.9 | 0 |
4094988 | 159478 | None | code28.2 | Second Floor | Sqm | 1145.0 | 1145.0 | 124.42 | False | None | None | False | None | False | 142460.9 | 0 |
4094989 | 159478 | None | code29 | Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : Flamed finish granite stone slab Black, Cherry Red, Brown, Cat Eye, River Pink or equivalent. - Stilt - Step landing.- GF | Sqm | 2466.0 | 2466.0 | 36.35 | False | None | None | False | None | False | 89639.1 | 0 |
4094990 | 159478 | None | code29.1 | First Floor | Sqm | 2466.0 | 2466.0 | 36.35 | False | None | None | False | None | False | 89639.1 | 0 |
4094991 | 159478 | None | code29.2 | Second Floor | Sqm | 2466.0 | 2466.0 | 36.35 | False | None | None | False | None | False | 89639.1 | 0 |
4094992 | 159478 | None | code29.3 | Steps | Sqm | 2466.0 | 2466.0 | 14.39 | False | None | None | False | None | False | 35485.74 | 0 |
4094993 | 159478 | None | code30 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/m2 including pointing the joints with white cement and matching pigment etc., complete-GF | Sqm | 1076.0 | 1076.0 | 12.78 | False | None | None | False | None | False | 13751.28 | 0 |
4094994 | 159478 | None | code30.1 | First Floor | Sqm | 1076.0 | 1076.0 | 12.78 | False | None | None | False | None | False | 13751.28 | 0 |
4094995 | 159478 | None | code30.2 | Second Floor | Sqm | 1076.0 | 1076.0 | 12.78 | False | None | None | False | None | False | 13751.28 | 0 |
4094996 | 159478 | None | code31 | Providing skirting, dadooing, rises of steps with colour glazed tiles 6mm thick on 10mm thick cement plaster 1:3 and jointed with white cement slurry over existing rough plaster surface using glazed tiles of approved make and size including cost of materials, labour, complete as per specifications-GF | Sqm | 1449.0 | 1449.0 | 59.08 | False | None | None | False | None | False | 85606.92 | 0 |
4094997 | 159478 | None | code31.1 | First Floor | Sqm | 1449.0 | 1449.0 | 59.08 | False | None | None | False | None | False | 85606.92 | 0 |
4094998 | 159478 | None | code31.2 | Second Floor | Sqm | 1449.0 | 1449.0 | 59.08 | False | None | None | False | None | False | 85606.92 | 0 |
4094999 | 159478 | None | code32 | Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two coat applied @ 1.67 ltr/10 m² over and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per pecifications and as per directions of Engineer-in-charge | Sqm | 174.0 | 174.0 | 1097.21 | False | None | None | False | None | False | 190914.54 | 0 |
4095000 | 159478 | None | code33 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade :New work (two coats) over and including water thinnable priming coat with cement primer after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge | Sqm | 137.0 | 137.0 | 2369.29 | False | None | None | False | None | False | 324592.73 | 0 |
4095001 | 159478 | None | code34 | Applying priming coat: With ready mixed pink or Grey primer of approved brand and manufacture on wood work (hard and soft wood) including preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, cost of materials, abour complete as per specifications and as per directions of Engineer-in-charge | Sqm | 53.0 | 53.0 | 67.54 | False | None | None | False | None | False | 3579.62 | 0 |
4095002 | 159478 | None | code35 | Painting wood work with Deluxe Multi Surface Paint of required shade. Two coat applied @ 0.90 ltr/10 m² over an under coat of primer applied @0.75 ltr/10 m² of approved brand and manufacture to give an even shade including preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, sand papering and knotting , cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge | Sqm | 138.0 | 138.0 | 67.54 | False | None | None | False | None | False | 9320.52 | 0 |
4095003 | 159478 | None | code36 | Painting Steel work with Deluxe Multi Surface Paint to give an even shade. Two coat applied @ 0.90 ltr/10 m² over an under coat of primer applied @ 0.80 ltr/10 m² of approved brand and manufacture including preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge | Sqm | 139.0 | 139.0 | 670.28 | False | None | None | False | None | False | 93168.92 | 0 |
4095004 | 159478 | None | code37 | Providing Thermo-Mechanically Treated bars of grade Fe-550 Steel reinforcement for RCC work including straightening, cutting, bending, placing in position, binding and anchoring to adjacent members whereever necessary complete as per Design including cost of material, labour, usage charges complete as per specifications. (The laps and wastages shall not be measured separately) | t | 89457.0 | 89457.0 | 55.0 | False | None | None | False | None | False | 4920135.0 | 0 |
4095005 | 159478 | None | code38 | Providing and laying integral cement Based waterproofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc., consisting of following application. (a) Applying and grouting a slurry coat of neat cement using 2.75 kg/m2 of cement admixed with proprietary water proofing compound conforming to IS :2645 over the RCC slab after cleaning the surface before treatment. (b) Laying cement concrete using broken brick bats 25mm to 100mm size with 50% of cement mortar 1:5 admixed with proprietary water proofing compound conforming IS:2645 over 20m thick layer of cement mortar 1:5 admixed with proprietary water proofing compound to required slope and treating similarly the adjoining walls upto 300mm height including rounding off junctions of walls and slabs. (c) After two days of proper curing, applying a second coat of cement lurry admixed with proprietary water proofing compound (d) Finishing the surface with 20mm thick jointless cement mortar of mix 1:4 admixed with proprietary water proofing compound and finally finishing the surface with trowel and neat cement slurry and making of 300x300mm square. (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test including cost of materials, labour complete as per specifications | Sqm | 817.0 | 817.0 | 180.0 | False | None | None | False | None | False | 147060.0 | 0 |
4095006 | 159478 | None | code39 | Providing and laying plat form using prepolished, water cut / gang saw 40mm thick telephonic Black Granite. Laid on existing vertical-supports and fixing in CM 1:3 proportion. Including cutting to required shape, pattern with paper joints, including full rounding for nosing, finished with cement mortar, pointed with colour pigments to match the colour of slab making through jointing with sealant, making holes 25mm x 12 mm grooves in joints including cost of all materials, mortar, labour, curing etc., complete as per specification-Kitchen | Sqm | 2937.0 | 2937.0 | 24.77 | False | None | None | False | None | False | 72749.49 | 0 |
4095007 | 159478 | None | code40 | Providing edge moulding to 18mm thick Granite stone counters, vanities
etc including machine polishing to edge to give high gloss finish etc.
complete as per design approved by Engineer-in-charge | Sqm | 328.0 | 328.0 | 22.86 | False | None | None | False | None | False | 7498.08 | 0 |
4095008 | 159478 | None | code41 | Providing & fixing of 2.5 track x 2-panel sliding windows made out of multi chambered UPVC (Matching to RAL-9016) sections and with minimum TiO2 (Titanium Dioxide) at 6PHR with TPE (Thermo Plastic Elastomer) and lead free, gaskets -grey color having isolated drainage and reinforced with Galvanized Iron profile through-out the window frame. The outer frame having an overall size of 94mm width x 45mm height with reinforcement of 1mm thickness and Sash with overall size of 39mm x 58mm with GI reinforcement of 1.5mm and mesh sash of size 25mm x 42mm. Coextruded Glazing bead for fixing of glass shall be of size 20mm x 24 mm. Windows shall be provided with 5mm plain float glass standard hardware& single point locking system with touch lock. Wall thickness of frame & sash shall be of 2mm-2.5mm. Maximum possible size :1819mmx1819mm. The cost is inclusive of all fixtures and separate charges for minor T&Ps shall not be made W1,W2,W3,W4 & Ventilator | Sqm | 6551.0 | 6551.0 | 73.17 | False | None | None | False | None | False | 479336.67 | 0 |
4095009 | 159478 | None | code42 | Manufacturing, supplying and fixing wooden ward robe of 0.60m deep using 19mm thick vinyl bonded water proof block board, shutters all round ward robe, lockable drawers with sliding channels, cupboard drapery hangers, curtain rods with end brackets, openable shutters with 19mm x 6mm thick plain teak wood beading, lipping 1.5mm thick commercial ply vertical support finished in approved 1mm lamination sheet of approved colour, shade and quality on all exposed surfaces. Inner surface painted with 2 coats of white synthetic enamel paint over 2 coats of Patti, one coat of wood primer, including cost of bras fittings, parlimentary hinges, C handles, tower bolts, magnetic catches, approved brand lock, adhesives, synthetic resins, nails, screws etc., complete including cost of all materials, labour charges, complete as per specification | Sqm | 8960.0 | 8960.0 | 65.36 | False | None | None | False | None | False | 585625.6 | 0 |
4095010 | 159478 | None | code43 | Providing and fixing storage unit of 0.30m width made out of 19mm thick commercial ply vertical support finished in approved 1.0mm laminate with 12mm thick ply packing internally finished with enamel paint of approved colour and shade shelves shall be formed out of 19mm ply finished with enamel paint of approved shade colour and 19mm thick shutters formed out of 19mm thick ply finished 1.00mm thick laminate of approved shade and colour etc., complete the rate includes cost of all materials, labour charges, complete as per specification-Kitchen Storage Units | Sqm | 4356.0 | 4356.0 | 22.86 | False | None | None | False | None | False | 99578.16 | 0 |
4095011 | 159478 | None | code44 | Providing and fixing Chorinated Poly Venyl Chloride (CPVC) pipeshaving thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipe with clamp at 1.00 meter spacing. This includes jointing of pipes and fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete (concealed work including cutting chases and good the walls etc.)15 mm nominal OD Pipes | m | 309.0 | 309.0 | 200.0 | False | None | None | False | None | False | 61800.0 | 0 |
4095012 | 159478 | None | code45 | Providing and fixing Chorinated Poly Venyl Chloride (CPVC) pipeshaving thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipe with clamp at 1.00 meter spacing. This includes jointing of pipes and fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete (concealed work including cutting chases and good the walls etc.)20 mm nominal OD Pipes | m | 379.0 | 379.0 | 500.0 | False | None | None | False | None | False | 189500.0 | 0 |
4095013 | 159478 | None | code46 | Providing and fixing Chorinated Poly Venyl Chloride (CPVC) pipes conforming to IS 15778, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipe with clamp at 1.00 meter spacing. This includes jointing of pipes and fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete (concealed work including cutting chases and good the walls etc.)25 mm nominal OD Pipes | m | 477.0 | 477.0 | 300.0 | False | None | None | False | None | False | 143100.0 | 0 |
4095014 | 159478 | None | code47 | Providing and fixing Chorinated Poly Venyl Chloride (CPVC) pipes conforming to IS 15778, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipe with clamp at 1.00 meter spacing. This includes jointing of pipes and fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete (concealed work including cutting chases and good the walls etc.)32 mm nominal OD Pipes | m | 557.0 | 557.0 | 350.0 | False | None | None | False | None | False | 194950.0 | 0 |
4095015 | 159478 | None | code48 | Providing and fixing ball valve (brass) of approved quality, High or low
pressure, with plastic floats complete : 25mm Nominal Bore | Nos. | 332.0 | 332.0 | 6.0 | False | None | None | False | None | False | 1992.0 | 0 |
4095016 | 159478 | None | code49 | Providing and fixing brass stop cock of approved quality:15 mm nominal bore | Nos. | 299.0 | 299.0 | 60.0 | False | None | None | False | None | False | 17940.0 | 0 |
4095017 | 159478 | None | code50 | Providing and fixing brass bib cock of approved quality :20 mm nominal bore | Nos. | 305.0 | 305.0 | 24.0 | False | None | None | False | None | False | 7320.0 | 0 |
4095018 | 159478 | None | code51 | Providing and fixing unplasticised PVC connection pipe with brass unions :45 cm length-15 mm nominal bore | Nos. | 91.0 | 91.0 | 60.0 | False | None | None | False | None | False | 5460.0 | 0 |
4095019 | 159478 | None | code52 | Providing and placing on terrace (at all floor levels) polyethylene water storage tanks IS 12701 marked with cover and suitable locking arrangements and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank | Ltr | 9.0 | 9.0 | 6000.0 | False | None | None | False | None | False | 54000.0 | 0 |
4095020 | 159478 | None | code53 | Waterproofing of RCC Terrace / podium slab / toilet / utilities / water retaining structure by preparing teh surface by chipping and cleaning and grouting of Honey comb, voids, creacks / construction joints with cement slurry (1 kg cement added in 10 ltr of water) added with 100gm of inorganic accelerator, followed by spraying of liquid biological modified alkaline earth silicates @ 0.40 ltr per m2 on whole surface to reduce the micro porosity and allowing it to dry, curing the surface for the silicates to penetrate deeper into the concrete and spraying waterproofing impregnate liquid containing silane and silanol linear copolymer @ 0.50 ltr per m2 and finally applying polymer slurry made out of cross linked acrylic / styrene / butadiene & cement in the ratio of 1:0.1, @ 0.50kg/m2 on the whole surface, including all labour charges tools and equipments, all complete as per the specification | Sqm | 817.0 | 817.0 | 125.38 | False | None | None | False | None | False | 102435.46 | 0 |
4095021 | 159478 | None | code54 | Providing and fixing Stainless Steel A ISI 304 (18/8) kitchen sink as per
IS:13983 with C.I. brackets and stainless steel plug 40 mm, including
painting of fittings and brackets, cutting and making good the walls
wherever required :Kitchen sink with drain board 510x1040 mm bowl depth 250 mm | Each | 5618.0 | 5618.0 | 6.0 | False | None | None | False | None | False | 33708.0 | 0 |
4095022 | 159478 | None | code55 | Providing and fixing white vitreous china pedestal type water closet
(European type) with seat and lid, 10 litre low level white vitreous china
flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm
flush bend, overflow arrangement with specials of standard make and
mosquito proof coupling of approved municipal design complete,
including painting of fittings and brackets, cutting and making good
the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid | Each | 5977.0 | 5977.0 | 6.0 | False | None | None | False | None | False | 35862.0 | 0 |
4095023 | 159478 | None | code56 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and
floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests | Each | 4884.0 | 4884.0 | 6.0 | False | None | None | False | None | False | 29304.0 | 0 |
4095024 | 159478 | None | code57 | Providing and fixing wash basin with C.I. brackets, 15 mm dia CP Brass
single hole basin mixer of approved quality and make, including painting
of fittings and brackets, cutting and making good the walls wherever
required: using White Vitreous China Wash basin size 550x400 mm
with a 15 mm CP Brass single hole basin mixer | Each | 3082.0 | 3082.0 | 12.0 | False | None | None | False | None | False | 36984.0 | 0 |
4095025 | 159478 | None | code58 | Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings | Each | 1432.0 | 1432.0 | 12.0 | False | None | None | False | None | False | 17184.0 | 0 |
4095026 | 159478 | None | code59 | Providing and fixing Chorinated Poly Venyl Chloride (CPVC) pipes conforming to IS 15778, having thermal stability for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipe with clamp at 1.00 meter spacing. This includes jointing of pipes and fittings with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete (concealed work including cutting chases and good the walls etc.) 65 mm nominal OD Pipes | m | 1400.0 | 1400.0 | 200.0 | False | None | None | False | None | False | 280000.0 | 0 |
4095027 | 159478 | None | code60 | Providing and laying cinder concrete in cement 1:15 ( 1 cement : 15 cinder of 12.5mm nominal gauge) on terraced roof or sunken slabs, laid to slope ompacting, including cost of materials, labour, curing complete as per specifications | Cum | 2017.0 | 2017.0 | 21.56 | False | None | None | False | None | False | 43486.52 | 0 |
4095028 | 159478 | None | code61 | Providing and fixing CI Nahani trap of approved make conforming to ISI specifications and construction of Cistern in M15 as directions (Rate is inclusive of cost of materials and fixtures and conveyance of materials to work spot).12.5 cms x 7.5 cms | Each | 237.0 | 237.0 | 36.0 | False | None | None | False | None | False | 8532.0 | 0 |
4095029 | 159478 | None | code62 | Providing and fixing 7.5 cms to 15.00 cms dia NP grating 100 mm dia | Each | 125.0 | 125.0 | 90.0 | False | None | None | False | None | False | 11250.0 | 0 |
4095030 | 159478 | None | code63 | Providing and fixing CP Brass 15mm nominal dia single lever telephonic wall mixer of quality & make as approved by Engineer in charge | Each | 5562.0 | 5562.0 | 12.0 | False | None | None | False | None | False | 66744.0 | 0 |
4095031 | 159478 | None | code64 | Providing and fixing C.P. brass shower rose with 15 or 20 mm inlet 100mm diameter | Each | 257.0 | 257.0 | 12.0 | False | None | None | False | None | False | 3084.0 | 0 |
4095032 | 159478 | None | code65 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour.14.40.1 450 mm long towel rail with total length of 495 mm, 78 mm wide and effective height of 88 mm, weighing not less than 170 g | Each | 478.0 | 478.0 | 12.0 | False | None | None | False | None | False | 5736.0 | 0 |
4095033 | 159478 | None | code66 | Providing and fixing of PTMT Angle Stop Cock each of 15mm nominal bore weighing not less than 85Grams | Each | 166.0 | 166.0 | 24.0 | False | None | None | False | None | False | 3984.0 | 0 |
4095034 | 159478 | None | code67 | Providing and fixing 8mm dia C.P/S.S Jet with flexible tube upto 1 Mtr long with S.S Triangular plate to European type W.C of Quality and make as approved by Engineer in charge | Each | 272.0 | 272.0 | 6.0 | False | None | None | False | None | False | 1632.0 | 0 |
4095035 | 159478 | None | code68 | Providing and fixing to wall, ceiling and floor, high density polyethylene pipes 6.00 kgf/sq.cm working pressure 110mm outside diameter raising mains and exposed distribution pipes with special flange, compression type fittings, wall clips, making good the wall, ceiling and floor including cost of all materials, labour charges, HOM of equipments and testing, excluding cost of fittings, complete as per specifications | m | 495.0 | 495.0 | 250.0 | False | None | None | False | None | False | 123750.0 | 0 |
4095036 | 159478 | None | code69 | Providing and fixing to wall, ceiling and floor, high density polyethylene pipes 6.00 kgf/sq.cm working pressure 140mm outside diameter raising mains and exposed distribution pipes with special flange, compression type fittings, wall clips, making good the wall, ceiling and floor including cost of all materials, labour charges, HOM of equipments and testing, excluding cost of fittings, complete as per specifications | m | 617.0 | 617.0 | 200.0 | False | None | None | False | None | False | 123400.0 | 0 |
4095037 | 159478 | None | code70 | Constructing brick masonry inspection chamber 600 x 600mm and 450mm depth (clear inside dimension) for single pipeline, using table moulded non-modular bricks of class designation 50 in cement mortar 1:5, C.I. cover with frame (light duty) 600x600mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23kg and weight of frame 15kg) R.C.C top slab with cement concrete M 15 with 20mm and down size granite metal, foundation concrete M 5 with 40mm and down size granite metal inside plastering 12mm thick with cement mortar 1:3, finish smooth with a floating coat of cement on walls and bed concrete complete as per standard design including cost of materials, labour charges, curing complete as per specifications | Nos. | 6278.0 | 6278.0 | 12.0 | False | None | None | False | None | False | 75336.0 | 0 |
4095038 | 159478 | None | code71 | Wall bores in upto 45 cm thick upto 45 cm thick | Nos. | 78.0 | 78.0 | 90.0 | False | None | None | False | None | False | 7020.0 | 0 |
4095039 | 159478 | None | code72 | Wall bores in size stone masonry upto 45 cm thick | Nos. | 187.0 | 187.0 | 60.0 | False | None | None | False | None | False | 11220.0 | 0 |
4095040 | 159478 | None | code73 | Providing and Filling in foundation with granite / trap broken metal 100mm and down size with approved M-Sand including hand packing, ramming, watering including cost of all materials and labour with all lead and lift complete as per specifications | Cum | 1476.0 | 1476.0 | 53.25 | False | None | None | False | None | False | 78597.0 | 0 |
4095041 | 159478 | None | code74 | Providing sand cement bed with 5% cement with all leads for all materials and lifts machine mixed, laid in layers of 15 cms. Thick and well compacted for foundation including curing cost, cost of all materials, machinery, labour including preparing surface, etc., complete as per specifications | Cum | 3244.0 | 3244.0 | 79.87 | False | None | None | False | None | False | 259098.28 | 0 |
4095042 | 159478 | None | code75 | Providing and filling murrum / gravely soil ( CNS soil ) for foundation or around pipes including cost of all materials, labour, spreading soil in layers of 100 to 150 mm, breaking clods, watering, compaction by earth masters to achieve density control of not less than 90 percent etc., complete with all lead and lifts | Cum | 820.0 | 820.0 | 399.36 | False | None | None | False | None | False | 327475.2 | 0 |
4095043 | 159478 | None | code76 | Concealed Conduit System: Supplying……mm dia 2mm2.5mm thick heavy gauge PVC conduit pipe with suitable size bends, metal/PVC junction boxes adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary-19/20mm dia 2mm thick | m | 66.0 | 66.0 | 2500.0 | False | None | None | False | None | False | 165000.0 | 0 |
4095044 | 159478 | None | code76.1 | 25mm dia 2mm thick | m | 78.0 | 78.0 | 1300.0 | False | None | None | False | None | False | 101400.0 | 0 |
4095045 | 159478 | None | code77 | Groove cutting: Supplying .….dia 2mm/2.5mm thick heavy gauge PVC conduit pipe with bends, metal junction boxes adhesive paste etc., and bracing U or J hooks and cement plastering up to the surface of the brick level and run with 18 SWG GI fish wire run through out the conduit wherever necessary-19/20mm dia 2mm thick | m | 68.0 | 68.0 | 2500.0 | False | None | None | False | None | False | 170000.0 | 0 |
4095046 | 159478 | None | code77.1 | 25mm dia 2mm thick | m | 79.0 | 79.0 | 900.0 | False | None | None | False | None | False | 71100.0 | 0 |
4095047 | 159478 | None | code78 | Supplying and fixing PVC/metal conduit accessories.Deep junction box-25mm deep junction box | Each | 49.0 | 49.0 | 150.0 | False | None | None | False | None | False | 7350.0 | 0 |
4095048 | 159478 | None | code78.1 | Supplying and fixing PVC/metal conduit accessories-Special type junction box-19/20mm special type junction box | Each | 56.0 | 56.0 | 200.0 | False | None | None | False | None | False | 11200.0 | 0 |
4095049 | 159478 | None | code79 | Supplying and flush mounting powder coated metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 1-3Way | Each | 124.0 | 124.0 | 50.0 | False | None | None | False | None | False | 6200.0 | 0 |
4095050 | 159478 | None | code79.1 | 4-5Way | Each | 137.0 | 137.0 | 32.0 | False | None | None | False | None | False | 4384.0 | 0 |
4095051 | 159478 | None | code79.2 | 6Way | Each | 173.0 | 173.0 | 38.0 | False | None | None | False | None | False | 6574.0 | 0 |
4095052 | 159478 | None | code79.3 | 8Way | Each | 219.0 | 219.0 | 40.0 | False | None | None | False | None | False | 8760.0 | 0 |
4095053 | 159478 | None | code79.4 | 10-12Way | Each | 261.0 | 261.0 | 35.0 | False | None | None | False | None | False | 9135.0 | 0 |
4095054 | 159478 | None | code80 | Point wiring using copper wire with switch Supplying and wiring adopting loop system in existing PVC conduit /casing capping using copper PVC insulated multi strand 2x1.5m2m copper wire with a 6Amps flush type SP control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block complete of each outlet-Short point up to 3Mtr from tapping point to out let via switch | Each | 269.0 | 269.0 | 80.0 | False | None | None | False | None | False | 21520.0 | 0 |
4095055 | 159478 | None | code80.1 | Medium point above 3Mtr up to 6Mtr from tapping point to out let via switch | Each | 379.0 | 379.0 | 130.0 | False | None | None | False | None | False | 49270.0 | 0 |
4095056 | 159478 | None | code80.2 | Long point above 6Mtr up to 10Mtr from tapping point to out let via switch | Each | 555.0 | 555.0 | 320.0 | False | None | None | False | None | False | 177600.0 | 0 |
4095057 | 159478 | None | code81 | Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with necessary supporting back plate with required nos. of machine screws, bolts, nuts etc., complete on the existing metal / pvc box 1-3 model-Group A 1-3 module | Each | 161.0 | 161.0 | 50.0 | False | None | None | False | None | False | 8050.0 | 0 |
4095058 | 159478 | None | code81.1 | 4 module | Each | 175.0 | 175.0 | 32.0 | False | None | None | False | None | False | 5600.0 | 0 |
4095059 | 159478 | None | code81.2 | 6 module | Each | 234.0 | 234.0 | 38.0 | False | None | None | False | None | False | 8892.0 | 0 |
4095060 | 159478 | None | code81.3 | 8 module | Each | 284.0 | 284.0 | 40.0 | False | None | None | False | None | False | 11360.0 | 0 |
4095061 | 159478 | None | code81.4 | 10 module | Each | 344.0 | 344.0 | 35.0 | False | None | None | False | None | False | 12040.0 | 0 |
4095062 | 159478 | None | code82 | Supplying and fixing of modular switch/ Socket/stepped electronic fan regulator/ dimmer/telephone socket etc on existing modular switch plate-Using Group "A" materials-6 Amps one way | Each | 102.0 | 102.0 | 400.0 | False | None | None | False | None | False | 40800.0 | 0 |
4095063 | 159478 | None | code82.1 | 6 Amps two way | Each | 166.0 | 166.0 | 40.0 | False | None | None | False | None | False | 6640.0 | 0 |
4095064 | 159478 | None | code82.2 | stepped fan regulator | Each | 357.0 | 357.0 | 24.0 | False | None | None | False | None | False | 8568.0 | 0 |
4095065 | 159478 | None | code82.3 | 16 Amps one way switch | Each | 180.0 | 180.0 | 36.0 | False | None | None | False | None | False | 6480.0 | 0 |
4095066 | 159478 | None | code82.4 | 6 Amps 3way socket | Each | 171.0 | 171.0 | 120.0 | False | None | None | False | None | False | 20520.0 | 0 |
4095067 | 159478 | None | code82.5 | 32 Amps DP switch | Each | 326.0 | 326.0 | 36.0 | False | None | None | False | None | False | 11736.0 | 0 |
4095068 | 159478 | None | code83 | Supplying and fixing of PVC casing and capping on the wall or ceiling using necessary materials like bends, screws at an interval of 300mm etc., as required-25mm | m | 35.0 | 35.0 | 120.0 | False | None | None | False | None | False | 4200.0 | 0 |
4095069 | 159478 | None | code84 | Supplying PVC / GI flexible conduitpipe 25m2m dia fixing on surface over inverted tapered wooden plugs or phill plugs or rawl plugs and clamped using heavy gauge saddles at an interval of 300mm using NF screws and the either end of the pipe terminated completely-25mm | m | 22.0 | 22.0 | 24.0 | False | None | None | False | None | False | 528.0 | 0 |
4095070 | 159478 | None | code85 | Supplying and fixing one of 230volts ding dong bell and a flush type bell push with gang box fixed on necessary wooden or rawl plugs using NF screws | Nos. | 246.0 | 246.0 | 6.0 | False | None | None | False | None | False | 1476.0 | 0 |
4095071 | 159478 | None | code86 | Supplying and fixing of round or oblong type bulk head fitting glass cover-Group A | Nos. | 70.0 | 70.0 | 12.0 | False | None | None | False | None | False | 840.0 | 0 |
4095072 | 159478 | None | code87 | Supplying of feet -PVC Batten with integrated LED tube W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI greater than 80. Power Input: 220-240V at 50/60Hz & Power factor greater than 0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition. LED light fitting 1 x 4-36/40 W | Nos. | 1269.0 | 1269.0 | 108.0 | False | None | None | False | None | False | 137052.0 | 0 |
4095073 | 159478 | None | code88 | Supplying capacitor type ceiling fan complete with down rodblades, shackle, canopies etc, for operation on 230 V, 50 cycles.Single phase AC supply conforming to ISS-374- 1979 and withdouble ball bearing system.(48"sweep 1200mm) Regular model(Khaitan, Crompton Greaves, Orient, Polar, Bajaj, Usha, Havells, Almonard)-Group A | Nos. | 2984.0 | 2984.0 | 24.0 | False | None | None | False | None | False | 71616.0 | 0 |
4095074 | 159478 | None | code89 | Supplying of 1440rpm heavy duty exhaust fan with bracketblades suitable to operate on 230V 50Hz, AC Supply complete. 12" sweep-Group A | Nos. | 2969.0 | 2969.0 | 18.0 | False | None | None | False | None | False | 53442.0 | 0 |
4095075 | 159478 | None | code90 | Fixing all types and all capacities fluorescent / false ceiling / spot light / CFL fittings indoor on the wall ceiling / rafters / girders using 23/0.0076" twin twisted pvc insulated wires, required nos. of round blocks and clamps (if required) a)On wall/ceiling/rafters/girders-Group A | Nos. | 122.0 | 122.0 | 108.0 | False | None | None | False | None | False | 13176.0 | 0 |
4095076 | 159478 | None | code91 | Fixing a ceiling / wall mounting fan of all capacities and all types to the existing S hook with fan regulator to the existing board together with supplying and fixing a 5 ampers ceiling rose, necessary length of 23/0.0076 inch pvc insulated twin twisted copper wire and wiring completely | Nos. | 171.0 | 171.0 | 24.0 | False | None | None | False | None | False | 4104.0 | 0 |
4095077 | 159478 | None | code92 | Fixing one exhaust fan in the nitch already left in the wall with bolts and nuts and 5 amps ceiling rose with sufficient length of 23/0.0076 inch pvc insulated twin core wire of approved make | Nos. | 492.0 | 492.0 | 18.0 | False | None | None | False | None | False | 8856.0 | 0 |
4095078 | 159478 | None | code93 | Supplying and fixing of Shunt trip suitable for MCCB.CBCT | Nos. | 1703.0 | 1703.0 | 1.0 | False | None | None | False | None | False | 1703.0 | 0 |
4095079 | 159478 | None | code94 | Supplying of on load change over switches 4 poles, AC 23A Duty, 415V, 50Hz, AC Supply. (Open Execution ) 200Amps | Nos. | 13230.0 | 13230.0 | 1.0 | False | None | None | False | None | False | 13230.0 | 0 |
4095080 | 159478 | None | code95 | Supplying and fixing of class A (medium duty) GI pipe of wall thickness of not less than 3.25mm on pole/wall/drain crossing with necessary clamping arrangements for UG cable of 1.1 kv class (65m2m to 150m2m) | m | 407.0 | 407.0 | 10.0 | False | None | None | False | None | False | 4070.0 | 0 |
4095081 | 159478 | None | code96 | Supplying and fixing of heavy duty cable glands suitable for UG cable of 1.1 kv class (metal only) 45mm dia | Nos. | 220.0 | 220.0 | 4.0 | False | None | None | False | None | False | 880.0 | 0 |
4095082 | 159478 | None | code97 | Heat Shrinkable Outdoor Type Cable Termination
Kit for XLPE Cable (outdoor HT kit 3x95m2m)-Group A | Kit | 3976.0 | 3976.0 | 2.0 | False | None | None | False | None | False | 7952.0 | 0 |
4095083 | 159478 | None | code98 | Heat Shrinkable Indoor Type Cable Termination Kit
for XLPE Cable (indoorr HT kit 3x95m2m)-Group A | Nos. | 3138.0 | 3138.0 | 2.0 | False | None | None | False | None | False | 6276.0 | 0 |
4095084 | 159478 | None | code99 | Heat Shrinkable Type Transition Jointing Kit for
XLPE Cable (HT kit 3x95m2m)-Group A | Nos. | 8811.0 | 8811.0 | 1.0 | False | None | None | False | None | False | 8811.0 | 0 |
4095085 | 159478 | None | code100 | Wiring for lighting/power circuit using one of FRLS PVCinsulated 1100V grade, multistrand copper wire with lowconductor resistance single core in open or concealed system ofwiring with specified IS-94:confirming to latest amendments-1.5m2m | m | 26.0 | 26.0 | 4000.0 | False | None | None | False | None | False | 104000.0 | 0 |
4095086 | 159478 | None | code100.1 | 2.5 m2m | m | 42.0 | 42.0 | 2500.0 | False | None | None | False | None | False | 105000.0 | 0 |
4095087 | 159478 | None | code100.2 | 4 m2m | m | 63.0 | 63.0 | 2000.0 | False | None | None | False | None | False | 126000.0 | 0 |
4095088 | 159478 | None | code101 | Supplying and fixing 230 Volts 20/40W Florocent Lamp Holder-Group A | Each | 148.0 | 148.0 | 400.0 | False | None | None | False | None | False | 59200.0 | 0 |
4095089 | 159478 | None | code102 | Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materialsand C Type curve, indicator ON or OFF energy cross-3 with Short circuit breaking capacity of 10K and complete wiring asrequired confirming to IEC 60898:6-32 Amps SP-Group A | Each | 415.0 | 415.0 | 52.0 | False | None | None | False | None | False | 21580.0 | 0 |
4095090 | 159478 | None | code103 | Fabricating supplying and mounting MS box made out....SWG suitable for floor /wall mounting, fully weather proofwith provision for better heat dissiaion, rovided withhinged front cover, equipped with tamper proof lockingarrangements, with suitable size clA with necessary cableentry pipe with gland and box should be finished with7tanks treatment with powder coated paint and finally finishedwith approved colour etc., complete-14SWG | Sq CM | 0.5 | 0.5 | 25000.0 | False | None | None | False | None | False | 12500.0 | 0 |
4095091 | 159478 | None | code104 | Supplying and fixing angle iron frame work fabricated out of M.S. angle iron and M.S. Flat with bolts, washers etc., and painted with 2 coats of red oxide and then two coats of approved paint. 75x75x6 mm | m | 555.0 | 555.0 | 5.0 | False | None | None | False | None | False | 2775.0 | 0 |
4095092 | 159478 | None | code104.1 | 50x100x50x6mm C channel | m | 756.0 | 756.0 | 5.0 | False | None | None | False | None | False | 3780.0 | 0 |
4095093 | 159478 | None | code105 | Supplying and fixing Moulded Case Circuit Breaker (MCCB)over the existing wood/panel board using necessary screws,bolts, nuts, necessary phase separators, handle and wiringcomplete. Protection of Overload and Short circuit in ThermalMagnetic Release. Micro processor release shall have Earth Fault as per IS-13947. (Icu=100% lcs). In 4P MCCB, all Polesshould have protection for Short-Cicrcuit/Over Load. ForMicroprocessor MCCBS Facility for segregating Priority andNon-Priority loads must be available in the MCCB. MCCB shallbe provided with double insulation (insulation between frontcover and internal power circuits to void any accidentalcontact with live current carrying path with the front coveropen). Multi-pole breakers shall be designed to break all thepoles simultaneously and they shall have a single mechanism: 4 Pole-200Amps 35kA-Group A | Each | 39118.0 | 39118.0 | 2.0 | False | None | None | False | None | False | 78236.0 | 0 |
4095094 | 159478 | None | code106 | Supplying fixing and wiring earth electrode for grounding of lifts, transformers, DG sets etc using 40mm dia 2.9mm thick 2.5 Mtr long GI pipes with GI funnel with mesh and suitable size reducer fixed on the top of the earth electrode. The funnel should be enclosed in a CC chamber of 400x400x400mm with a cast iron cover. The earth electrode shall have staggered holes of 12mm dia and the electrode should be covered 150mm around with alternate layers of salt and charcoal from the bottom of the CC chamber. The connection from the electrode is to be established through GI strip using GI bolts and nuts | Each | 2498.0 | 2498.0 | 13.0 | False | None | None | False | None | False | 32474.0 | 0 |
4095095 | 159478 | None | code107 | Supplying of 1.1 KV LT UG cable XLPE or Heat resistant PVC insulated, PVC extruded Inner sheath armoured UG LT cable as per IS-1554 (Part-1) or IS-7098 Part-1, Armouring strip thickness in average +5% and resistivity 14 Ohms/Kms (Max) as per IS-3975 3.5 core 70 m- Class 'A' PVC Cable- 3.5 core 70m 2m | m | 423.67 | 423.67 | 250.0 | False | None | None | False | None | False | 105917.5 | 0 |
4095096 | 159478 | None | code108 | Labour charges for laying of 1.1 KV class UG cable when supplied agency in existing trench GI pipe / stoneware pipe / on wall / on pole as required. 25 Sq mm to 75 Sq mm-In existing trench/duct-25m2m to 75m2m | m | 23.65 | 23.65 | 150.0 | False | None | None | False | None | False | 3547.5 | 0 |
4095097 | 159478 | None | code108.1 | On wall/structure-25m2m to 75m2m | m | 23.65 | 23.65 | 150.0 | False | None | None | False | None | False | 3547.5 | 0 |
4095098 | 159478 | None | code109 | Digging of trench of 0.6m deep x 0.50 Mtr wide refilling the trench to the required ground level and consolidating etc., complete-in soil (hard) | m | 102.0 | 102.0 | 340.0 | False | None | None | False | None | False | 34680.0 | 0 |
4095099 | 159478 | None | code110 | 11 kV, 3 Core, XPLE HTUG Cable with pressure extruded inner sheeth, ROUND WIRE ARMOURED as per IS-7098 (Part-2) Armouring wires dia and Resistivity as per IS-3975 95 mm2, (54 GI Wires - 2.5 mm Dia)-3Cx95mm2 | m | 889.66 | 889.66 | 450.0 | False | None | None | False | None | False | 400347.0 | 0 |
4095100 | 159478 | None | code111 | Supplying, installation, testing and commissioning of solar hot water heater comprising of solar flat plate collector of size 2120x1040x100mm and stainless steel hot water storage tank with stainless steel heat exchanger absorber made of copper sheet and copper tube of following capacity aluminium box collector with appropriate capacity electrical back up arrangement excluding inlet and outlet pipes. SS Model with 100mm thick of 48kg/m3 density rock wool insulation with 22 SWG aluminium cladding - 200 litre capacity | Nos. | 46914.0 | 46914.0 | 6.0 | False | None | None | False | None | False | 281484.0 | 0 |
4095101 | 159478 | None | code112 | Supply and laying double walled corrugated HDPE pipe with necessary connecting sockets/couplings/tees/bends of same materials in existing trench as per IS 14930 part-II suitable for drawing under ground cables (160mm OD/ 135mm ID) | m | 561.0 | 561.0 | 45.0 | False | None | None | False | None | False | 25245.0 | 0 |
4095102 | 159478 | None | code113 | Supply, erection, testing and commissioning of KVA aluminium wound distribution transformer 11kv/433v with off load tap switch, buchholtz relay winding temperature indicator, oil temperature indicator, marshalling box with wiring, oil level indicator with +5% to -10% steps of 2.5% HT and LT bushing with all standard accessories as per latest IS standard technical specifications 100kva Distribution Transformer - 3 Phase, 11kV/433V - Amorphous Core with Oil as per IS-1180 (Part-1): 2014 as per IS-11171 100 kVA, Aluminium Wdg, Star 2 (5 Star) | Nos. | 220185.0 | 220185.0 | 1.0 | False | None | None | False | None | False | 220185.0 | 0 |
4095103 | 159478 | None | code114 | Load Break Switch with Panel | Nos. | 73239.0 | 73239.0 | 1.0 | False | None | None | False | None | False | 73239.0 | 0 |